Short dated tender - Tender For Electrical , Low Side Ac And Net Working Works Iob Shukla Ganj- Branch,Unnao ELECTRICAL PANEL (UPGRADATION AS / SPEC. BELOW) Design, manufacture, providing, storing & installing in position, effecting proper connection, testing and commissioning of panel made of 14 SWG, CRCA sheet steel. It shall be dust and vermin proof. It shall have compartmentalized construction with bus bar chambers, cable alley, cable glands plate etc. as required, duly painted from inside as well outside. It shall have the following - a. MAIN PANEL 3 Nos. (100 Amp.) Kit Kat switches with neutral links Incoming. 1 No. 100 Amp. TPN, MCCB (10 KA breaking capacity), Busbars. 125 Amp., 3 phase, 4 strips, 415 volts, 50 Hz. copper busbars with colour coded PVC heat shrinkable sleeves. Metering. 1 No. Voltmeter (range 0-500V), 3 phase. 1 No. Ammeter (range 0-200 Amp.), 3 phase with CT operation. 3 Nos. Phase Indication Lamps (red, yellow and blue). Outgoing. 2 Nos. (40 Amp.) TPN, MCCB for UPS DB. and L&F DB 1 No. (63 Amp.) TPN, MCCB for Power DB. 1 No. (80 Amp.) TPN, MCCB for A.C. DB. 1 No., 63 Amp. Three Phase Change Over for D.G. Set. 1 No., 63 Amp. Phase Selector / Rotary for U.P.S. The design of panel should be got approved by the Architect before manufacturing. Also, the provision for 1/2 spare outgoings should be considered for A.T.M. and future expansion. The job shall be completed, to the satisfaction of the Bank Engineer/Architect. 1 Job 2 UPS I/P, O/P AND DISTRIBUTION a. 40 AMP. DP MCB with Metal Eclouser for Input & Output 6 Nos. b. 4 WAY TPN DB (1 No. 40/63 AMP TP MCB and 12 NOS. 6-32 AMP. SPMCB) Horizontal type 0 No. c. 12 WAY SPN DB (1 No. 40/63 AMP DP MCB and 10 NOS. 6-32 AMP. SPMCB) Horizontal type 1 No. d. 20 AMP. 3/5 Pin Socket & Switch with plate and PVC Box 6 Nos. 3 RAW POWER & FAN, LIGHTING DB & AC DISTRIBUTION BOARD a. 4 WAY TPN DB (1 No.63/40/80 AMP. TP MCB and 12 NOS. 6-32 AMP. SPMCB) Horizontal type 3 Nos. b. 4 WAY TPN DB (1 No. 80 AMP. TP MCB and 12 NOS. 6-32 AMP. SPMCB) Vertical type 0 No. 4 CABLES a. Supplying, laying, testing & commissioning of 4 C X 25 sq.mm. at 1100 volts grade PVC insulated aluminum conductor armoured cable with 10 gauge earth copper wire including cables end termination using appropriate Lugs, Glands, termination accessories, Clamps etc. as required as per specification (Mains). 15 Mtr. b. Supplying, laying, testing & commissioning of 4 C X 10 sq.mm. at 1100 volts grade PVC insulated aluminum conductor armoured cable with 10 gauge earth copper wire including cables end termination using appropriate Lugs, Glands, termination accessories, Clamps etc. as required as per specification (Light & Fan DB) 55 Mtr. c. Supplying, laying, testing & commissioning of 4 C X 16 sq.mm. at 1100 volts grade PVC insulated aluminum conductor armoured cable with 10 gauge earth copper wire including cables end termination using appropriate Lugs, Glands, termination accessories, Clamps etc. as required as per specification (Power DB) (AC DB) & (GENERATOR). 25 Mtr. d. sitc of 2 x 6.0 sq.mm copper wire + 1 x 2.5 sqmm copper earth wire (rotary switch to ups and ups to ups db) in pvc pipe fixing on walls or chassing the walls and making it good with cement mortar of 1:5 ratio and painting compete with end termination/lugs and in all respect as required. (UPS to UPS DB). 25 Mtr. e. sitc of 2 x 2.5 sq.mm copper wire + 1 x 1.5 sqmm copper earth wire (electric panel to glow sign board) in pvc pipe fixing on walls or chassing the walls and making it good with cement mortar of 1:5 ratio and painting compete with end termination/lugs and in all respect as required. 20 Mtr. 5 AC (SPLIT) POINT a. Point Wiring 2 No. 4.0 Sq.mm and 1 No. 2.5 Sq.mm Multistrand Copper Wire. 120 Mtr. b. 20 AMP. 3/5 Pin Socket with plate and PVC Box 6 Nos. 6 EARTHING a. Preparation and commissioning of earth pits with 600x600x3mm thick hot dipped copper electrode with watering arrangement, chamber, funnel, charcoal, salt etc. The electrode shall be connected with 25mmx3mm thick copper strip and terminated into the chamber with nut bolt arrangement. the rate shall inculde cost of earthing strip upto the chamber. Water Funnel with chamber cover 2 Nos. b. 12 SWG Bare Copper Earth Wire from earthing pit to UPS DB and Main DB 0 Mtr. c. 6.0 Sq.mm. Cu. Wire from earthing pit to UPS DB and Main DB. Also for A.T.M. & UPS. 95 Mtr. 7 U.P.S. POINT a. Supply & Installation of point wiring for UPS or stabilized power plug points on workstations / table for computers using 3 X1.5 Sq.mm copper conductor multi starnd FR PVC sheathed flexible wire pulled through floor raceways/conduit and taken upto table top using PVC rigid or flexible conduits run within wooden/metal partitions. Each point consisting of 3 nos of 5A , 2/3 pin sockets & 1 No., 15A Switch , wired together forming one point. The earth wire of green color only. 8 Nos. b. Supply & Installation of secondary point wiring(looped with above circuit) for UPS or stabilized power plug points consisting of 3 nos of 5A , 2/3 pin sockets & 1 No., 15A Switch , wired together forming one point. The earth wire of green color only 2 Nos. c. Supply & Installation of point wiring for UPS or stabilized power plug points for ATM machines using 3 X1.5 Sq.mm copper conductor multi starnd FR PVC sheathed flexible wire pulled through floor raceways/conduit and taken upto table top using PVC rigid or flexible conduits run within wooden/metal partitions. Each point consisting of 2 nos of 15A , 2/3/5 pin sockets & 1 No., 10A Switch , wired together forming one point. The earth wire of green color only. 2 Nos. 8 RAW POWER POINT a. Supply & Installation of point wiring for Raw power plug points on workstations / table for computers using 2X2.5+1X1.5 Sq.mm copper conductor PVC sheathed flexible wire pulled through floor raceways/conduit and taken upto table top using PVC rigid or flexible conduits run within wooden/metal partitions. Each point consisting of 1 nos of 16A , 2/3/5 pin sockets & 1 No., 16A Switch (Modular).The earth wire of green color only. 6 Nos. b. Supply & Installation of point wiring for Primary Raw power plug points using 2X2.5+1X1.5 Sq.mm copper conductor PVC sheathed flexible wire pulled through already laid floor raceways/conduit and taken upto table top using PVC rigid or flexible conduits run within wooden/metal partitions. Each point consisting of 2 nos of 16A 2/3/5 pin socket & 2 nos 16A Switch (Modular), wired together forming one point. The earth wire of green color only. 2 Nos. 9 LIGHT/FAN POINT Supply & Installation of concealed point wiring using 600v grade 1.5 Sq.mm copper conductor PVC insulated wires (with proper R,Y,B color code ) pulled through heavy gauge PVC conduits laid concealed over false ceiling including 2 Nos. 2.5 sqmm circuit wires from the relevant DB and also including 2.5 sqmm green color copper earth wire and switch plate, switches, etc. Each switch board consisting of 1 nos of 5A , 3/5 pin sockets & 1 No., 5A Switch as approved by the Banks Engineer/Architect. a. Primary light points including the cost of Switch 57 Nos. b. Secondary light points (Two downlights from one point) 19 Nos. c. MobileCharging point (1 nos of 5A sockets & 1 No., 5A Switch ) on tables / counters 6 Nos. d. Ceiling Fan Point including the cost of 5A Switch along with electronic regulator. 12 Nos. e. Exhaust Fan Point along with 10 AMP modular switch 3 Nos. 10 DATA CABLING & POINT Supplying and laying of D-Link make CAT-6 (UTP) cable a. Supplying and Installing D-Link make CAT-6 information outlet with plate & surface Box at individual Tables. This work includes supply and laying of CAT-6 cable in PVC conduits throughout the length, from the I/O hub to the point. 11 Nos. b. Supplying and fixing of 2.0 Mtr long crimped patch cord 11 Nos. c. Supplying and fixing of 1.0 Mtr long crimped patch cord 11 Nos. d. Jack Panel - 24 ports 1 No. e. SITC of 9U Rack including wire manager, power supply card, hardware etc. complete in all respects 1 No. 11 VOICE NETWORKING a. Supply and fixing of 20 pair telephone MDF consisting of tag blocks, disconnector type, complete with powder coated metal enclose, krone tag block mounting arrangement telephone distribution chart and locking arrangement [for P&T/EPABX] 2 Jobs b. Supplying and laying telephone cables 0.5mm dia electrolytic tinned copper conductors PVC insulated with gel and twisted pair with rip cord, through already laid PVC conduits/Raceways. The rate shall include termination at both ends on tag blocks. (i) 10 pair cable 25 Mtr. (ii) 2 pair cable 0 Mtr. c. 1 No. RJ11 Telephone socket with plate and box 2 No. 12 FIXTURES Providing, storing & installing in position, effecting proper connection, testing and commissioning of Light fitting, recessed in false ceiling, with all accessories. The job shall be complete, to the satisfaction of the Banks Engineer/Architect. a. LED 18 W tube 4-0 As specified in tender document or approved by SBIIMS/Architect. 4 No. b. Full Glow 20 X 20 LED 48 W slim Smart Panel of make As specified in tender document or approved by SBIIMS/Architect. 7 Nos. c. Full Glow 10 X 10 LED 25 W slim Smart Panel of make As specified in tender document or approved by SBIIMS/Architect. 11 Nos. d. Full Glow 6 X 6 LED 15 W slim Smart Panel of make As specified in tender document or approved by SBIIMS/Architect. 38 Nos. e. Full Glow 4 X 4 LED 15 W slim Smart Panel of make As specified in tender document or approved by SBIIMS/Architect. 0 Nos. f. Bracket Holder with LED Lamp, 7 Watt of make As specified in tender document or approved by SBIIMS/Architect. 3 Nos. g. Supply, installation, testing and commissioning of following fans with all fixing materials like white Polycarbonate 2 mm Hylem sheet cover, down rods, fan box as required etc. all complete as per the directions of Engineer-in-charge. (i) Wall mounted fans (METAL BODY) 400 mm dia. make As specified in tender document or approved by concerned office in charge. 0 Nos. (ii) Ceiling fans 1200/900 mm dia. make As specified in tender document or approved by concerned office in charge. 13 Nos. (iv) Supply & fixing of 300 mm exhaust fan Ventilair DX W with self-closing louvers and plastic body with all accessories etc. complete of make As specified in tender document or approved by concerned office in charge. 3 Nos. (iii) Supply & fixing of 150 mm INLINE exhaust fan for machanical vetilation with all accessories etc. complete of make As specified in tender document or approved by concerned office in charge. 0 Nos. h. CALL BELL Providing, storing & installing in position, effecting proper connection, testing and commissioning of Call Bell with all accessories. Fixtures - Anchor – City Ding Dong Door Bell. Bell Push - Anchor – Penta, Model – 50042. The job shall be complete, to the satisfaction of the Banks Engineer/Architect. 1 No. i. P/F Cove light in false ceiling of make As specified in tender document or approved by SBIIMS/Architect. 20 Mtr. 13 1 No. 125 Amp. TPN MCCB with enclosure (10 KA breaking capacity) at entrance for Power except UPS power supply 1 Job 14 DISTRIBUTION BOARD FOR A.T.M./E-LOBBY a. 4 WAY TPN DB (1 No. 63 AMP. TP MCB and 12 NOS. 6-32 AMP. SPMCB) Horizontal type 1 Job AIR-CONDITIONING - LOW SIDE WORK 15 REFRIGERANT PIPING Supplying and laying of Extra copper refrigerant piping with nitrile rubber pipe insulation, both of size as specified by the manufacturer suitable for 1.0 TR/ 1.5/2.0 TR Split type AC and 2.0/3.0 TR Cassette AC (From Indoor to outdoor Units) a. For1.0 TR/ 1.5/2.0 TR Split unit 120 Mtr. b. For 3.0 T Split unit 0 Mtr. 16 DRAIN PIPING Providing and fixing drain piping up to drain as directed by the engineer in charge with all accessories e.g. elbows, unions, sockets, reducers, reducing tees, nipples etc. Complete job including cutting chiseling in walls, fixing with GI clamps,floor and making good of all chases/ cuts etc. and discharging the drain into a floor trap/ gully as per site conditions with insulation, both as specified by the manufacturer. a 25 mm dia UPVC drain pipe for Split AC 55 Mtr. 17 ELECTRICAL CABLES Suitable IS/BIS standard Cable of 1.1-2.2 KV, Multi strand, FRLS 2- 4 C / 1.5/2.5 -6.0 Sqmm) as per design requirement of Peak load calculation of specific ACs system installed at site with 1”/1/2/2” PVC conduit pipe between indoor/outdoor unit a Supplying and laying of Extra Electrical interconnecting control cable from indoor to outdoor of size as specified by the manufacturer suitable for 1.0 TR/ 1.5/2.0 TR Split type AC. 130 Mtr. 18 CORE CUTTING a Core cutting member in Non RCC 6 Nos 19 REMOVING & REFIXING OF EXTISTING AC UNITS a Removing of existing ACs unit and refixing as desire location as per new layout plan including repairing and gas charging etc.