| 1 | Supply and laying ,fixing or passing through pipe, laid in trenches or fixed to pole/wall or fixed to LT panel board,insulated, armoured heavy duty electric cable with aluminium conductor, XLPE1100 volts grade, cross-sectional area of size 240 Sqmm3.5 core with cable lugs of suitable size completeall as specified and directed. |
| 2 | All as per item No 01 but 185 Sqmm 3.5 Core Complete all as specified and directed. |
| 3 | All as per item No 01 but 120 Sqmm 3.5 Core Complete all as specified and directed. |
| 4 | All as per item No 01 but 95 Sqmm 3.5 Core Complete all as specified and directed. |
| 5 | All as per item No 01 but 50 Sqmm 3.5 Core Complete all as specified and directed. |
| 6 | All as per item No 01 but 35 Sqmm 3.5 Core Complete all as specified and directed. |
| 7 | All as per item No 01 but 25 Sqmm 4.0 Core Complete all as specified and directed. |
| 8 | All as per item No 01 but 10 Sqmm 2.0 Core Complete all as specified and directed. |
| 9 | Excavating in trenches n exc 1.5 m wide and n exc 1.5 m in depth for foundation or for shafts, well cesspits, manholes etc / for laying of cable/ pipe etc n exc 10 sqm on plan and n exc 1.5 m in depth and getting out in any type of soil complete all as specified and directed. |
| 10 | M&L for sand cushioning with dry and clean fine river sand for underground cable 8 cm before laying cable and 15 cm after laying and punned to 18 cm after laying of cablecomplete all as specified and directed.Note:- Punned thickness shall be considered for payment purpose. |
| 11 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm.complete all as specified and directed. |
| 12 | Removing excavated material (soil) to a distancen exc 50 Mtr and depositing where directed at a level not exc 1.5m above the starting point complete all as specified and directed. |
| 13 | Supply and laying bricks for cable protection , common burnt clay sub class \"B\" designation 75 for protection of UG cable laid in trenches with axis of the bricks perpendicular to the axis of the cable complete all as specified and directed. |
| 14 | S&F in repair galvanized steel water tubing(GI Pipe) light grade (ISI marked) with all fittings as in sleeving for cable protection & laid in trenches/ floor or fixed to wall,under culvert, under road and pole of following bore complete as specified and directed :-Note : MS Clamp, nut bolts and washer shall be measured and paid seperatly for fixing with pole etc. |
| 15 | 50mm bore |
| 16 | M&L for road cutting for laying cable and through GI pipe of suitable size making good with PCC 1:3:6 type C2 ( Using 40 mm graded stone aggregate) of 150mm x100 mm in respect of width and thicknesscomplete all as specified and directed. |
| 17 | M&L earthing complete with galvanised steel earth plate eletrode 600 x 600 x 6.0 mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of earth plate not less than 1.5 meters below ground level connected by 32 x 6 mm GI strip as earth lead by means of brass nuts and bolt, thimbles, check nuts, washers including concrete chamber of PCC 1:3:6 type c-1 using 20 mm graded stone aggregate, with fair finish, internal surface of concrete chamber shall be given internal dia 300mm x 300mm, 15mm thick plaster in CM 1:4 funnel with wire mesh, RCC pit cover of 320 x 320 x 80 m size (1:2:4) Type B1 using 20 mm graded stone aggregate, adequate quantity of common salt, charcoal etc all as shown in electrical plate No 3 of MES SSR Part-I (2009) and specified including and provision of GI strip upto 7.5 mtr long with 40 mm dia light grade GI pipe protection and watering pipe of GI 20 mm bore, medium grade, including all excavation and earth work and connecting the earthing strip to an earthing test point/panel including testing on completion complete all as specified and directed by Engr-in-Charge.(i)RCC pit cover shall be precast of RCC (1:2:4) type B1, 80 mm thick reinforced with XPM weighting not less than 4 Kg/Sqm in lieu of CI cover.(ii)Cost of additional GI strip more than 7.5 meter will be measured and paid seperately under relevant item. |
| 18 | M&L earthing complete with galvanised steel earth plate eletrode 600 x 600 x 6.0 mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of earth plate not less than 1.5 meters below ground level connected by galvanised earth lead wire 4 mm earth lead by means of brass nuts and bolt, thimbles, check nuts, washers including concrete chamber of PCC 1:3:6 type c-1 using 20 mm graded stone aggregate, with fair finish, internal surface of concrete chamber shall be given internal dia 300mm x 300mm, 15mm thick plaster in CM 1:4 funnel with wire mesh, RCC pit cover of 320 x 320 x 80 m size (1:2:4) Type B1 using 20 mm graded stone aggregate, adequate quantity of common salt, charcoal etc all as shown in electrical plate No 3 of MES SSR Part-I (2009) and specified including and provision of GI strip upto 7.5 mtr long with 40 mm dia light grade GI pipe protection and watering pipe of GI 20 mm bore, medium grade, including all excavation and earth work and connecting the earthing strip to an earthing test point/panel including testing on completion complete all as specified and directed by Engr-in-Charge.(i)RCC pit cover shall be precast of RCC (1:2:4) type B1, 80 mm thick reinforced with XPM weighting not less than 4 Kg/Sqm in lieu of CI cover.(ii)Cost of additional GI strip more than 7.5 meter will be measured and paid seperately under relevant item. |
| 19 | M&L for design, supply, Fabrication, Installation, testing and Commissioning factory made, LT panel of size 1.5 m (L)x 0.85 m (B)x 1.8m(H), Out door type, totally enclosed, dust and vermin proof suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 hz, AC supply system, fully compartmentalised, both side openable, made out of 3.00 mm thick CRCA sheet steel, protection of enclosure IP-54 as per IS : 2147 of 1962 with pre-treatment and powder coated of approved colour including suitable frame work / support made out of suitable size of angle iron / flat iron, front opening type with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded copper conductor FRLS cable of adequate size (minimum 1.5 sqmm 4 core), including required civil works/anchoring bolts for fixing, PCC foundation etc with and including following all as specified and directed : -(a)Bus bar chamber :Electrically grade aluminium shrouded bus bar of capacity equal to 1.5 times of rated incoming control switch gear including inter connection of all switch gears, fixed on DMC insulators and provision of extension complete all as specified. |
| 20 | INCOMER :(i) MCCB 350Amps, 415Volts, 4 pole 50 Hz, 36 KA with adjustable ,microproseccsorrelease in built instantaneous protection, Ics = 100%=Icu(1 sec) completeincluding phase spreader all as specified and directed. 01 Nos. /L&T (ii) Multi function meter = 01 set.(iii) Phase Indication lamps (RYB), LED type - 01 No (set of three).(iv) CT( Current transformer)- Set of 3 Nos |
| 21 | Outgoing: (a)(i)MCCB 250 Amps, 415Volts, 4 pole 50 Hz, 36 KA with adjustable micro processor release , in built instantaneous protection, Ics = 100%=Icu(1 sec) completeincluding phase spreader all as specified and directed- 01 Nos (ii)MCCB 125 Amps 16 KA adjustable thermal release, 415Volts, 4 pole 50 Hz, 16 KA, all as specified and directed - 01 No. (iii)MCCB 40 Amps 16 KA adjustable thermal release, 415Volts, 4 pole 50 Hz, 16 KA, all as specified and directed - 02 No. |
| 22 | (i) CPRI Certification Degree of protection IP-54 (should have IEC:61439-1-2 & IEC:60529 tests).(ii)All the electrical switch gear like MCCBs, MCBs should be of same make, (ii)Drawing of panel board should be got approved from AGE(I) before fabrication.Note-: All type test certificate and design verification with switchgears(ACB/MCCB) conforming to IS/IEC: 61439/2011 Part-1 & 2, with 4000A short circuit test 65 KA shall be submitted by the contractor before execution of work |
| 23 | Material and Labor for Design, supply, Fabrication, Installation, testing and Commissioning factory made, LT Feeder of size 1.5 (L) x 0.85 (B)x 1.8 (H) , Out door type, totally enclosed, dust and vermin proofm suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 hz, AC supply system, fully compartmentalised, both side openable, made out of 3.00mm thick CRCA sheet steel, protection of enclosure IP-54 as per IS : 2147 of 1962 with pre-treatment and powder coated of approved colour including suitable frame work / support made out of suitable size of angle iron / flat iron, front opening type with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded copper conductor FRLS cable of adequate size (minimum 1.5 sqmm 4 core), including required civil works/anchoring bolts for fixing, PCC foundation etc with and including following all as specified and directed : -(a)Bus bar chamber :Electrically grade aluminium bus bar of capacity equal to 1.5 times of rated incoming control switch gear including inter connection of all switch gears, fixed on DMC insulators and provision of extension complete all as specified and directed. |
| 24 | INCOMER :(i) MCCB 125Amps, 415Volts, 4 pole 50 Hz, 36 KA with adjustable ,microproseccsorrelease in built instantaneous protection, Ics = 100%=Icu(1 sec) completeincluding phase spreaderall as specified and directed. 01 Nos. Make : ABB /LEGRAND /SIEMENS /L&T (ii) Multifunction meter = 01 set.(iii) Phase Indication lamps (RYB), LED type - 01 No (set of three).(iv) CT( Current transformer)- Set of 3 Nos |
| 25 | Outgoing: (a)(i)MCCB 40 Amps, 415Volts, 4 pole 50 Hz, 25 KA with adjustable thermal magnetic release, in built instantaneous protection, Ics = 100%=Icu(1 sec) completeincluding phase spreader all as specified and directed- 05 No |
| 26 | (i) CPRI Certification Degree of protection IP-54 (should have IEC:61439-1-2 & IEC:60529 tests).(ii)All the electrical switch gear like MCCBs, MCBs should be of same make, (ii)Drawing of panel board should be got approved from AGE(I) before fabrication.Note-: All type test certificate and design verification with switchgears(ACB/MCCB) conforming to IS/IEC: 61439/2011 Part-1 & 2, with 4000A short circuit test 65 KA shall be submitted by the contractor before execution of work |
| 27 | M & L for design, supply, Fabrication, Installation, testing and Commissioning factory made, LT panel of size1.5 m (L) x 0.85 m(B)x 1.8 m (H) , Out door type, totally enclosed, dust and vermin proof suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 hz, AC supply system, fully compartmentalised, both side openable, made out of 3.00 mm thick CRCA sheet steel, protection of enclosure IP-54 as per IS : 2147 of 1962 with pre-treatment and powder coated of approved colour including suitable frame work / support made out of suitable size of angle iron / flat iron, front opening type with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded copper conductor FRLS cable of adequate size (minimum 1.5 sqmm 4 core), including required civil works/anchoring bolts for fixing, PCC foundation etc with and including following all as specified and directed : -(a)Bus bar chamber :Electrically grade aluminium shrouded bus bar of capacity equal to 1.5 times of rated incoming control switch gear including interconnection of all switch gears, fixed on DMC insulators and provision of extension. |
| 28 | INCOMER :(i) MCCB 250Amps, 415Volts, 4 pole 50 Hz, 36 KA with adjustable ,microproseccsorrelease in built instantaneous protection, Ics = 100%=Icu(1 sec) completeincluding phase spreaderall as specified and directed. 01 Nos. Make : ABB /LEGRAND /SIEMENS /L&T (ii) Multifunction meter = 01 set.(iii) Phase Indication lamps (RYB), LED type - 01 No (set of three).(iv) CT( Current transformer)- Set of 3 Nos |
| 29 | Outgoing: (a)(i)MCCB 125 Amps, 415Volts, 4 pole 50 Hz, 16 KA with adjustable microprocessor release , in built instantaneous protection, Ics = 100%=Icu(1 sec) completeincluding phase spreader all as specified and directed- 01 Nos (ii)MCCB 40 Amps 16 KA adjustable thermal release, 415Volts, 4 pole 50 Hz, 16 KA, all as specified and directed - 05 No. |
| 30 | (i) CPRI Certification Degree of protection IP-54 (should have IEC:61439-1-2 & IEC:60529 tests).(ii)All the electrical switch gear like MCCBs, MCBs should be of same make, (ii)Drawing of panel board should be got approved from AGE(I) before fabrication. Note-: All type test certificate and design verification with switchgears(ACB/MCCB) conforming to IS/IEC: 61439/2011 Part-1 & 2, with 4000A short circuit test 65 KA shall be submitted by the contractor before execution of work |
| 31 | Dismantling of ACSR conductor of any type complete all as specified and directed. |
| 32 | Dismantling of old unserviceable/defective (Pin type, shackle type etc) insulators of any size/type and removing materials from site of work complete all as specified and directed. |
| 33 | Dismantling of old cross-arms of mild steel channel or angle sections, etc, including mild steel bolts, nuts, washers, etc. and removing from site of work complete all asdirected. |
| 34 | Disamntling of old UG cable complete all as specified and directed. |
| 35 | S&F street light control panel16 A 3 pole,230 V analog time switch includingthree phase contactor outdoor type clamped on pole with MS clamp, nut bolt , washer etc complete all as specified and directed. |
| 36 | S&F flexible wire of 2.5 Sq mm 3 core from street light junction box to the street light complete all as specified and directed. |
| 37 | S&F thermoplastic cable junction box/enclosure (distribution box) for outdoor installation with knock outs for cable entry suitable for cable size 10-16 Sqm of dimension 300x200x105 mm with cable terminals andcomplete fitted on pole with new MS clamp, nut bolt duly painted with synthetic enamelled paint over one coat of red oxide Zink chrome primer on clamps complete all as specified and directed. |