| 1 | M&L for Preventive maintenance including checking of street light wire connection by taking out power supply XLPE cable from GI protection pipe, taking out undergroung cable loop any type on pole to find out defect (loose connection /fault/ No power etc) on site and repairing to cable / wire connection & making new good tight connection along with new aluminium lugs, applying proper insulation by LT insulation tape in junction box, for proper power supply to light, as directed by engineer in charge.Note:- (i) Excavation work / removal & refixing of interlocking tiles, cost of ladders, any other T & P/ crane arrangment to approach the street light,labour, surrounding cleaning / cutting of grass / bushes / small tree branches for approacing to poleare included in unit rate quoted above.(ii) Contractor will deploy skilled electrian for execution of work and will able to find out the cable network for power supply to street light panel and street lights. |
| 2 | M&L for taking down the old unservisible street light from steel tublar pole (9 meter / 11 meter long) and fixing new LED street light/ flood light (45 W to 150 W) on the same pole complete all as specified and directed.Note : (i) The above item rate includes the cost of ladders, any other T & P/ crane arrangment to approach the street light,labour, surrounding cleaning / cutting of grass / bushes / small tree branches for approacing to pole all as directed and specified by Engineer-in-Charge. Contractor is requested to visit the site before quoting the tender. (ii) Contractor will deploy skilled electrian for execution of work and will able to find out the cable network for power supply to street light panel and street lights.(iv) Old unservisible Street light will be replaced by new LED light . New LED light will by issued by MES under schedule \"B\" free for fixing. (v) Old lights will be deposited to MES store yard. |
| 3 | S&F in replacement 1.5 Sqmm 3 core Rodent Resistant copper conductor cable, PVC insulated and PVC round sheathed, copper conductor (flexible) industrial cable, 1100 volt, confirming to IS : 694 including connecting the cable from street light to junction boxpassing through pole with and incl proper lugs and taking down of old unsv cable complete all as specified and directed.Note- (i) Cable is reqd to be connected from street light to junction box with proper lugs. (ii) Cable will be fixed from inside of pole. (iii) No Seprate payment payment will be issued for taking down and refixing of street light for connection of street light and cable. (iv) Flexible steel condute will be fixed between junction box and pole hole. Rate of conduit is included in unit rate quoted above. |
| 4 | Supply, fixing and testing in replacement SMC junction box of size 250 x 200 x105 mm made out of Polycarbonate material totally enclosed, dust and vermin proof, rain protected slanted roof top, door plasted with rubber gasket, IP 55 protection,with integrated membranes/metric knockouts for cable entry with cable glands,comprising with nut and bolt type bus bar 100 Amps for phases and neutral of required amps capacity for cable size 16/35 sqmm 4 core, protection and suitable size of connectwell type stud terminal (provision for socket bolting) - 04 nos suitable for internal wiring system including 06 amp MCB SP- 01 No, junction box should mounted on tubular/PCC pole with suitable clamp, nuts, bolts including removal of existing unsv junction box complete all as specified and directed. |
| 5 | Supply, laying, jointing, testing & commissioning 1100 volts heavy duty Rodent Resistant XLPE cable (ISI marked) with PVC insulated multi stranded aluminium conductor served with inner sheating of PVC tape armoured with galvanised steel strip or wire and overall PVC sheated cable of size 10 Sqmm nominal cross sectional area 2 core, laid in trenches, under road, ducts, pipes or fixed on poles, including all necessary clamps, nut, bolt washers incld taking down old U/S cable complete all as specfied and directed.Note : (i) Earth work, excavation shall be measured & paid separately under respective item of Schedule. |
| 6 | ,---ditto--- all as per srl item No 5 above but cable of size 16 Sqmm nominal cross sectional area 2 core cable complete all as specfied and directed. |
| 7 | ,---ditto--- all as per srl item No 5 above but cable of size 16 Sqmm nominal cross sectional area 4 core cable complete all as specfied and directed. |
| 8 | ,---ditto--- all as per srl item No 5 above but cable of size 25 Sqmm nominal cross sectional area 3.5 core cable complete all as specfied and directed. |
| 9 | ,---ditto--- all as per srl item No 5 above but cable of size 35 Sqmm nominal cross sectional area 3.5 core cable complete all as specfied and directed. |
| 10 | M&L for carefully removing foothpath interlocking tiles, fixed on laid cable or for laying of new cable,demolition of PCC and refixing old interlocking tiles carefully and making good the disturbed portion as per existing complete all as specified and directed by Engineer-in-Chagre. Note:- (i) Cable will be measured and paid seprately. (ii) Cement work to make surface good is included in unit rate quoted above. |
| 11 | Excavating in trenchs, n exc 1.5m wide and n exc 1.5m in depth for foundation, etc. or for laying of cables n exc 10sqm on plan and n exc 1.5m in depth and getting out in soft/loose soil complete all as specified and directed. |
| 12 | Removing excavated soil to a distance n. exc 50 m and depositing where directed at a level not exc 1.5 m above the starting point complete all as directed. |
| 13 | Returning, filling including spreading leveling watering and well ramming in layers n. exc 25 cm in soft/loose soil complete all as directed. |
| 14 | M & L Sand cushioning to under ground cable with screened and washed sand (non cohessive), 8 cm before laying cable and 15cm after laying and punned to 18cm after laying of cable complete all as specified and directed by Engineer-in-Charge.Note : Punned thickness shall be considered for payment purpose. |
| 15 | M & L bricks for protection cover to UG cable (with old size sub class B bricks, designation 75) with width of protection to equal to length of brick, laid dry and flat abutting each other with gaps between adjecent bricks not exceeding 10mm complete all as specified and directed. |
| 16 | S & F 80 mm bore GI tubing \"light grade\" with all fittings, fixed to wall/ pole with suitable size MS clamp, nut, bolt, washer etc or laid under road crossing etc as reqd for protection of cable incl taking down old pipe complete all as specified and directed.Note : Cost of MS clamp, nut bolt, washer and GI fittings etc shall be inclusive in the quoted rates. |
| 17 | M&L for drilling hole under road for laying of U/G cable through pipe of size up to 100 mm bore, complete all as specified and directed by engineer-in-charge. |
| 18 | M & L for scraping, cleaning and prepration of old painted / rusted surface of LT steel tubular pole 9/11 meter long, steel fitting fixtures with clamps fixed on same pole and applying two coat of aluminium paint over one coat of primer after prepration of steel surface and making of strip of 30 cm width (red and white in alternate band) upto 1500 mm height from bottom of the pole with synthetic enamel paint and writing pole No with enamel paint complete all as specified and directed by Engineer-in-Charge. Note:- (i) Time between two coat will be two days (ii) The above item rate includes the cost of ladders, any other T & P/ crane arrangment to approach the street light, labour, surrounding cleaning / cutting of grass / bushes / small tree branches for approacing to pole all as directed and specified by Engineer-in-Charge. (iii) Contractor is requested to visit the site before quoting the tender. |
| 19 | M & L for lowering light fixture arrangement having (8 to 10 lights) from the high mast light of height aprrox 20 meter, dismentling existing installed old model halide light / unservisible LED lights any type and installing new LED flood light along with proper connection and testing and rising properly to its original installed height complete all as specified and directed by engineer-in-charge. Note:-(i) New LED lights will be issued by MES under schedule \"B\"(ii) T&P required for above work such as ladder, Crane vehicle, menpower etc, are inclusive in the item rate.(iii) Rate of necessary arrangement for fixing LED light on existing bracket like reducer or extention of pipe by suitable size of GI pipe as per dia of LED light by welding etcare inclusive in the item rate. (iv) Old lights will be deposited to MES store yard. |
| 20 | Supply, install and testing of digital astronomical programmable time switchthreephase having astronomical switch function, On-Off switching times, three year power reserve, Auto / manual operation, supply terminal A1-A2, operating voltage 230 V AC, LCD display, Range 16 Ampsforstreet lighton off control all as specified and directed by engineer in charge. Make- Havells / L&T/ seimens as approved by GE |
| 21 | Supply, install, testing and commissioning of LT panel, board fabricated out 3.15mm thick CRCA steel sheet (Outdoor type) of size 600mm X 600mm X 300mm with openable shutters on both sides (Front and rear) having locking arrangement totally enclosed dust and vermin proof, protection class IP-65, weather proof, spray painted internally & externally with two coats of synthetic enamel paint over a coat of primer, danger notice sticker, mounted on 65mm X 65mm X 6mm angles iron stand grouted in PCC complete suitable for 440 volts, 3 phase, 4 wire, 50 Hz, with properly insulated colour coded aluminium bus bar, with approach for cable entry and for easy maintanance duly internally wired with FRLS, PVC insulated stranded copper conductor cable of suitable size including LED indicator for R, Y & B and comprising of the following :Incoming :-(i)MCCB 415 Volts of capacity 63 Amps 16 KA, 4 pole - 01 No(ii) Bus Bar :- 200 Amps, TPN, Aluminium Bus bars : 01 SetOutgoing :-(iii) MCB TPN, 32 Apms, 415 V -03 Nos(iv)3 ph LED multifunction metrer CI 0.5 -01 Set(v)LED indicator lamp –01 No (set of three)(vi) Din type Astronomiical Digiital Time switch 32 Amps along with contactor for street light |
| 22 | Material & Labour for Earthing complete with galvanised steel earth plate electrode 600mm×600m.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to using galvanised iron strip 25×4mm as earthing leadby means of bolts, nuts, check nuts and washers of galvanised iron or steel, 15 mm bore galvanised iron medium grade watering pipe, 40 mm bore galvanised iron light grade pipe for earth stripprotection, including all excavation earth work in any type of soil, PCC 1:3:6 type C1 for chamber of internal size 300 mm x 300 x300 mm with 120 mm thick wall and 700 mm x 700 mm x150 mm thick bed concrete, RCC 1:2:4,type B1, reinforced with welded steel wire fabric or XPM jali (weight not less than 4.00 Kg/Sqm)with cast iron frame, funnel with wire mesh, test point etc complete all as specified and directed.Note: (i) Earth strip and GI protection pipe up to length 7.5m shall deemed to be included in rate of above item. (ii) The earth resistance value shall be less than 5 Ohm. Failing to achieve the value contractor shall re-do without any extra cost. |
| 23 | Note:- The contract sum shall be calculated by deducting the amount shown in Credit Schedule attached to this tender, from total amount of Schedule \"A\"/BOQ |