| 1 | Supply, installation, testing and commissioning of Dry Type Cast Resin Transformer, Indoor Type, Rating 3250 KVA (min), Voltage Ratio 11000/415Volt, 50 Hz, Off Circuit tap links, Tapping Voltage range : +05% to -05% @ 2.5% (4 STEPS/ 5 Position), Copper winding, Vector Group: Dyn11, Cooling: AN, Termination HV side : cable box, LV side: Bus duct as per detailed specification attached in Annexure”A”. Make : Siemens/ABB (Hitachi)/Schneider/Voltamp. |
| 2 | Supply Installation testing and commissioning of HT 11KV VCB panel having configuration Incomer 800Amps:02 Nos. and Outgoers 800Amps: 04 Nos.as per detailed specification attached in Annexure”B”. Make: Siemens/ABB/Schneider. |
| 3 | Supply Installation testing and commissioning of LT ACB Panel consisting of Configuration ACB Incomer 4000 Amp - 02 nos, ACB Bus Coupler 4000Amp - 01 no, ACB Outgoer 4000 Amp - 03 Nos, ACB Outgoer 2000Amp - 02 Nos., as per detailed specification attached in Annexure”C”. Make: Siemens/ABB/Schneider. |
| 4 | Supply, installation, testing and commissioning of sandwich type bus bar truckingwith supporting structure, 1000volt, L.T non-segregated phase, for efficient and trouble free operation, 3 phase, 4 wire, 415 volts, 50Hz, 75kA, 4 pole copper bus bar {SCP (3L+N+PE)} 5000Amps capacity after considering all de-rating factor suitable for horizontal and vertical runs confirming to IEC/EN 60439-1&2 & IP-65,bus bar made of electrolytic copper ETP 99.9% purity and sheet metal enclosure/housing made out of hot galvanized steel treated and painted with RAL 7035 and of size not less than 1.6mm thick, continuous running earth strip, including adaptor box for interconnection inside substation from transformer to LT ACB panel.Connectivity at ACB incomer side terminal and connectivity at transformer side LV terminal complete in ready to use condition. |
| 5 | Supply, Fixing and commissioning of thyrister control Automatic power factor correction panel for 3Phase 415/440 Volt and 50 Hz system of capacity 500 KVAr having ACB as incomer, as per detailed specification attached in Annexure”D”. Make: ABB(Hitachi)/SIEMENS/AREVA(Schneider)/EPCOS/Neptune/JAIVIC/Standard. |
| 6 | Rough excavation of earth n. exc.1.50 mtr depth getting out in soft/loose soil. |
| 7 | Demolition of PCC of any description and in any position not otherwise specifically provided.(Unreinforced) |
| 8 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm. soft & loose soil. |
| 9 | M&L of hardcore of gauge n exc. 63 mm, deposited, spread and levelled in layers n exc. 15 cm thick, watered and rammed to a true surface with stone. |
| 10 | M&L for spraying cement slurry 3.0 kg per sqm and rendering 12mm thick cement plaster 1:6 on fair faces of brick work or concrete on wall surfacesmaking even & smooth without using extra cement. |
| 11 | M&L for brick work with sub class \"B\" bricks, straight or curved on plan exc 6.0m mean radius built in cement mortar 1:4 at any height with proper scaffolding and safety. |
| 12 | M&L cement concrete 1:2:4 20.0 mm graded aggregate in foundation filling and mass concrete and finished surface even and smooth. |
| 13 | M&L for mild steel deformed bars 10mm diaand over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and includingmild steel wire (annealed) not less than 0.9mm dia or securing with clips. |
| 14 | S&F for roof trusses (framed), trussed, purlins, crane gantries, rails and fastenings and heavy bracket framing (Beam, tee, angle, channel or flat sections) including distance pieces, cleats etc.(Fe 410 -W(Gde-E- 250) quality- A.) |
| 15 | M&L for preparation of new iron surface apply one coat of red oxide and two coat of synthetic enamel paint on prepared surface.Make Apcolite-Asian Paints, Superlac Hi Gloss-Shalimar Paints,Luxol -Berger Paintall as directed by EIC. |
| 16 | M&L of formwork (Square/ Ractangular/ Polygonal) to sides of pillars,posts, struts, piers, columns and stanchions.(Rough finished surface of concrete.) |
| 17 | M&L cement concrete M-20 (1:1.5:3) 20.0 mm graded aggregate in foundation filling and mass concrete and finished surface even and smooth. |
| 18 | S & F of Pre- painted galvalume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick of an colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws as specified |
| 19 | S&F of expanded metal, cut to length, bent to shape required and tying with and including annealed mild steel wire not less than 0.9mm dia or fixing with galvanised steel staples supplied and fixed complete to wood or steel members.( exc 4.5kg/sqmtr) |
| 20 | S&F of Plates (plain or chequered Fe 410 -W (Gde E- 250) quality A ) 8 mm thick channels, square cut or notched (ordinary and counter sunk) forming holes, with cutting fixing over trench complete with all respect. |
| 21 | M & L Earthing complete withearth copper plate electrode 60×60cm × 3.15mm thick, buried directly in ground (earth pit not lessthan 2.25 metres deep below groundlevel) with top edge of the plate notless\"than 1.5 metres below normalground level, connected to earthlead 20x3 mmcopper strip by means of bolts, nuts, checknuts and washers of galvanised ironor steel all as shown in electrical or steel all as shown in electrical plate No. 3connected to earthing testpoint all as specified or indicatedincluding testing on completion. |
| 22 | M & L one 3 Pin socket outlet, 5Amp on the same board with other switches, with copper conductor cable size 1.5 Sq. mm.in PVC conduit. |
| 23 | M & L one 3 pin socket outlet, 5Amp independent with copper conductor cable of 1.5 Sqmm size in PVC conduit. |
| 24 | M & L One light point or one fan point controlled by one switch with cables 1.5 sq.mm with copper conductor cables mm sizein PVC conduit. |
| 25 | M & L for one 3 pin socket outlet, 15 Amps, independent with stranded copper conductorcables 4 sq. mm size in PVC conduit. |
| 26 | M & L PVC rectangular box for mounting switch sockets, fan regulator etc. with 3 mm thick plastic laminated sheet cover of size 175 x 100 x 50 mm deep. |
| 27 | M & L PVC rectangular box for mounting switch sockets, fan regulator etc. with 3 mm thick plastic laminated sheet cover of size 200 x 150 x 50 mm deep. |
| 28 | S & F switch piano flush type single pole one way 5 amp. |
| 29 | S & F switch piano flush type single pole one way 15 amp. |
| 30 | S & F socket outlet 5 Amps, 5 Pin flush type. |
| 31 | S & F socket outlet 2 in 1, 5 /15 Amps 6-pinflush type. |
| 32 | M & L Ceiling rose, 3 phase/PVC/ polycarbonate, isolated body. |
| 33 | S & F wiring for circuit/ submain wiring in suitable PVC conduit along with earth wire with 2 X 2.5 sq. mm. + 1 X 1.5 sq. mm size of FRPVC insulated copper conductor, single core cable in surface / recessed. |
| 34 | S & F wiring for circuit/ submain wiring in suitable PVC conduit along with earth wire with 2X 4.0 sq. mm. + 1 X 2.5 sq. mm size ofFR PVC insulated copper conductor, single core cable in surface / recessed. |
| 35 | S & F Rigid non-metallic PVC conduit, MMS grade, 25 mm dia. exclusive of boxes (junction/terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock, nuts, saddles, pipe, hooks, etc. |
| 36 | M & L sheet metal enclosure for DB, double door with 200 Amp rated busbar when MCBs to be used for single pole & neutral 4 way, 240 volts, AC. |
| 37 | Supply and fixing 6amps to 32 ampsrating ,240 volt , 10 KA ,\"C\" Curve miniature circuit breaker single pole. |
| 38 | Supply and fixing32 ampsrating ,240 volt , 10 KA ,\"C\" Curve miniature circuit breaker single pole and neutral. |
| 39 | Supply and fixing25 to 63 ampsrating , 415volt , 10 KA ,\"C\" Curve miniature circuit breaker tripplepole . |