Bids Are Invited For Supply and Delivery at site of Three Phase HT ToD Smart energy meter within built RF communication module with digital output for controls, Class 0.28 as per IS 14697, IEC 62052, Billing as per MERC latest amendment, Voltage 110V (L-L), Demand Interval 15/30 min programmable, ensure IP51, backlit LCD 6-digit Tamper legend indications, Local communication Optical port, RS 485 Port, Inbuilt RF communication module at PS-3 Transformer feeders. The meter should be able to record accurate readings as per existing set Up. coct wound type Supply and Delivery at site of HT Current Transformers (CT) suitable for metering, resin 120/5A 0.28 class accuracy, 10VA for metering and 5P10 protection class 15VA conforming to IS:2705 of 1992 (amended up to date) or with latest standards. Supply and Delivery of 6.6kV PTs, indoor type cast resin 6.6kV/110V, Class 0.28, 20 VA for metering and suitable for 6.6kV OCB type breakers, 50 Ha, breaker panel at the incoming side for energy meter reading with required wiring, mounting brackets, TP MCB for isolation, wires, etc. (Optional Item) Supply and Delivery at site of Three Phase HT ToD Smart energy meter with inbuilt RF communication module with digital output for controls, Class 0.28 as per IS 14697, IEC 62052, Billing sa per MERC latest amendment, Voltage 110V (L-L), Demand Interval 15/30 min programmable, ensure IP51, backlit LCD 6-digit Tamper legend indications, Local communication Optical port, RS 485 Port, Inbuilt RF communication module at Slo-19 Transformer feeders. The meter should be able to record accurate readings as per existing set up. Supply and Delivery at site of HT Current Transformers (CT) suitable for metering, resin cast wound type 75/5A 0.28 class accuracy, 10VA for metering and Protection class 5P10, 15VA conforming to IS:2705 of 1992 (amended up to date) or with latest standards Supply and Delivery of 6.6 kV PTs, indoor type cast resin 6.6kV/110V, Class 0.25, 20 VA for metering and suitable for 6.6kV OCB/VCB type breakers, 50 Ha, breaker panel at the incoming side for energy meter reading with required wiring, mounting brackets, TP MCB for isolation, wires, etc. (Optional Item) Supply and Delivery at site of Three Phase LT-TOD CT15A Smart energy meter with inbuilt RF communication module with digital output for controls, Class 0.58 as per IS 14697, IEC 62052, Billing as per MERC latest amendment, Voltage 240V (L-N), Demand Interval 15/30 min programmable, ensure IP51, backlit LCD 6-digit Tamper legend indications, Local communication Optical port, RS 485 Port, Inbuilt RF communication module. The meter should be able to record accurate readings as per existing cet up. Supply and Delivery at site of LT Current Transformers (CT) suitable for metering, resin cast ring type 400/5A 0.5S cla০০ accuracy, 10VA conforming to IS:2705 of 1992 (amended up to date) or with latest standards Supply and Delivery at site of Three Phase HT ToD Smart energy meter with inbuilt RF communication module with digital output for controls, Class 0.28 as per IS 14697, IEC 62052, Billing as per MERC latest amendment, Voltage 110V (L-L), Demand Interval 15/30 min programmable, ensure IP51, backlit LCD 6-digit Tamper legend indications, Local communication Optical port, RS 485 Port, Inbuilt RF communication module at Slo-12 Incomer feeder. The meter should be able to record accurate readings as per existing set up. Supply and Delivery at site of HT Current Transformers (CT) suitable for metering, resin cast wound type 75/5A 0.2S class accuracy, 10VA for metering and for protection 5P10, 15VA conforming to IS:2705 of 1992 (amended up to date) or with latest standards. Supply and Delivery of 6.6kV PTs, indoor type cast resin 6.6kV/110V, Class 0.28, 20 VA for metering and suitable for 6.6kV MOCB/VCB type breakers, 50 Hz, breaker panel at the incoming side for energy meter reading with required wiring, mounting brackets, TP MCB for isolation, wires, etc. (Optional Item) Installation, testing and Commissioning of above smart meters along with CT, PTs and training. All the accessories and miscellaneous items such as mounting accessories, cables, wires, pvc pipes, etc. shall be deemed to be included in the quoted price. Inspection, Testing, Rectification of control circuit of HTCB breakers along with providing DC supply from the existing battery charger. The job shall include repairs/replacement of relays wherever required. The control circuit shall be reinstated so as to enable tripping of breakers in event of fault/overcurrent, etc. All the material required for the subject work shall be deemed to be included within the quoted price for this item Total Quantity : 37