| 1 | Dismantling of four pole structure complete all as specified and as directed. |
| 2 | Supply, commissioning and testing Ring Main Unit (RMU) of 11 KV outdoor motorised extensible, SF6 gas insulated RMU with remote gas monitoring combo 11 KV, 630A, 21KA, 3sec, 01 Nos LBS as incomer and 2 Nos VCB as outgoing type-Safeplus-XT +CVV+with IEC 62271-200/100 with internal arc classified IAC AFL, with IP 54 as per enclosed annex technical BOM complete alongwith necessary foundation work complete all as specified and as directed.(Location:-01 x Near Kendriya Vidyalya and 01 x Harsan Enclave) |
| 3 | Supply, commissioning and testing ring main unit (RMU) of 11 KV outdoor motorised extensible, SF6 gas insulated RMU with remote gas monitoring combo 11 KV, 630A, 21KA, 3sec, 01 Nos LBS as incomer and 2 Nos VCB as outgoing with metering cubicle type -Safeplus-XT +CVV+metering cubicle with CT/PT, MFM and Aux Transformer for single phase and space provision for FRTU, with IEC 62271-200/100 with internal arc classified IAC AFL, with IP 54 as per enclosed annex technical BOM complete along with necessary foundation work complete all as specified and as directed. (Location:- Main receiving station) |
| 4 | M&L in replacement for earthing galvanised steel earth plate electrode 600X600X6 mm thick burried directly in ground (earth plate not less than 2.25 mtr deep below normal ground level with top edge of the plate less than 1.5 mtr below normal ground level) connected to GI strip 32x6 mmby means of bolts, nuts, check nuts, and washers, of galvanised iron or steel including GI pipe light grade 40 mm bore for protection of earth lead,GI funnel and wire mesh etc complete all as shown in Electrical plate no 3 of SSR 2009 (part- I) including necessary excavation earth work, form work. Earth pitof size 450X450X300 mm of PCC M-15 (Nominal mix) using stone aggregate earth pit cover of PCCand 20 mm bore light grade GI pipefor watering and charcoal dust,common salt, and connected to test point7.5 mtr from earth pit including testing on completion with earth resistance value, complete all as specified and as directed. |
| 5 | Supply and fix cable jointing kit for 11 KV grade cable for indoor termination, heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, aluminium conductor cable of size 50 sq mm to 95 sq mm complete all as specified and as directed. |
| 6 | Supply and fix cable jointing kit for 11 KV grade cable for indoor termination, heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, aluminium conductor cable of size 120 sq mm to 185 sq mm complete all as specified and as directed. |
| 7 | Supply and fix cable jointing kit for 11 KV grade cable for indoor termination, heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, aluminium conductor cable of size 240 sq mm to 300 sq mm complete all as specified and as directed. |
| 8 | Supply and fix cable jointing kit for 11 KV grade cable for outdoor termination, heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, aluminium conductor cable of size 50 sq mm to 95 sq mm complete all as specified and as directed. |
| 9 | Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 volts grade, of size 3 core 300 sq mm complete including liase with KSEB & PWD for rod crossing complete all as specified and as directed. |
| 10 | Excavating in trenches not exceeding 1.5 meter wide and not exceeding 1.5 meter in depth for foundation for erection of poles, stays, laying cables, stays etc and getting out in hard/ dense soil and in road cutting complete all as specified and as directed. |
| 11 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25cm in hard/dense soil complete all as specified and directed.NOTE: Riddled earth upto 20cm depth around cable for protection to be filled including spreading, levelling etc & punned down and the same shall be measured and paid separately. |
| 12 | Removing excavated material/surplus soil not exceeding 50 meters and depositing where directed at a level not exceeding 1.5 meter above starting point complete all as specified and as directed. |
| 13 | Supply and lay reinforced precast concrete cable cover class-HV, Type-1 flat, size 300mmx180mmx40mm complete all as specified and directed. |
| 14 | Supply and spreading in natural river sand as cushioning to cable by using IS sieve to separate the composite particle/roots etc amd refilling in trenches and compacted in layers to form a solid bed covering to cable complete all as specified and as directed. |