| 1 | Overhauling and servicing of Split type AC of capacity 1.5/2.0 TR of any make at different locations at Mil Stn Lekhapani, testing the unit complete with the following tasks :- (a) Overhauling & servicing.(b)Inspection opening washing the condensor coil and cooling coil with chemical followed with pressurized water jet complete. (c)Inspection and treatment of leakage of refrigerant in the system. (d) Checking of operation of blower motor, condesnor motor and swing motor for noise free operations. (e) Oiling of condensor / blower motors and checking the earth continuity. (f) Inspection of all electrical parts / connections and rectification of any small defect. (g) Checking of functional of electronic remote control unit /PCB to ensure satisfactory functioning of indoor/outdoor unit complete. (h) Inspection and treatment of leakage water from indoor unit.(j) Replacing minor spares (ie groomet rubber/rubber lining/washers/nuts&bolt) as required Note:- During servicing of unit, if any major spares / parts are required to be replaced it shall be measured and paid separately under respective items mentioned here- in - after as per direction. |
| 2 | All as per item 1.00 above but for Window type AC of capacity 1.5 / 2.0 TR. |
| 3 | S&F in replacement blower motor for Indoor unit of same specification/make as per existing one, suitable for all type split type AC 1.5/2.0 TR capacity complete including taking out of old unserviceable one,complete all specified anddirected. |
| 4 | S&F in replacement blower fan for indoor unit, of same specification/make as per existing one suitable for all type split type AC 2.0/1.5 TR capacity complete including taking out of old unserviceable one complete all specified anddirected. |
| 5 | S&F in replacement blower fan with blower motor suitable for window type AC, of same specification/make as per existing one suitable for all type window type AC 2.0/1.5 TR capacity complete including taking out of old unserviceable one complete all specified anddirected. |
| 6 | S&F in replacement condensor fan motor with blade for outdoor unit, of same specification/make as per existing one, suitable for all type split/window type AC 1.5/2.0TR capacity complete including taking out of old unserviceable one complete all specified anddirected. |
| 7 | S&F in replacement hermitically type sealed, scroll or reciprocating , variable/ fixed speed compressor for all type split/windowAC of capacity 1.5/2.0 TR as per existing including brazing work, laying of extra copper tubing, pressure testing, dehydration, gas charging upto required level and testing on full load for satisfactory functioning complete all as specified and directed by Engineer-in-charge Make : Copeland/Danfoss/kirloskar/ suitable for LG/Carrier/Blue star/Voltas/Hitachi/As per site requirement |
| 8 | M&L for rewinding of condensor fan motor of all split/window type AC of cap 1.5/2.0 TR including replacement of gun metal bushes, testing for noise free operation and refixing at its existing location complete all as specified and as directed by Engineer-in-charge |
| 9 | S&F in replacementcomplete PCB with Remote control unit for invertor/non invertor type split/window AC of cap 1.5 TR/2.0 TR, microprocessor based with transmission and receiving unit, cord less with features of digital display, mode selection, timer, temperature control or as per exsting specification and model complete all as specified and directed Make : Suitable for Blue Star / LG / Carrier/ Voltas/Hitachi/Samsung ACs |
| 10 | Dismantling and taking out voltage stablizer, capacity 3 KVA to 5 KVA, any type, any specification, repair/replacement electric circuit board, all cable connections, complete overhauling of the system including repairing/replacement of push on switch, transistor, capacitor, relay transistor, diode, condenser, zener, pre-set, IC, 12 volt transformer, 24 Volt transformer, voltmeter, PVC connector, indicator lamp, cutout, MCB/fuse, and any other parts as required for proper functioning of stabilizer complete alongwith testing, commissioning including transportationfrom site to workshop and back all as directed by the Engr-in-Charge |
| 11 | S&F in replacement copper tubing flexible of suitable dia including heavy duty nitrile rubber insulation complete all as specified and directed by Engineer-in-charge |
| 12 | S&F in replacement of flexible type water drain out pipe suitable for indoor unit tray with extra PVC pipe for out side of split AC as per existing type/model complete all as specified and directed. |
| 13 | Overhauling & servicing ofwater cooler any capacity by carrying out the following works at different location complete with the following tasks, all as specified and directed by Engineer-in-charge.(a) Inspection, taking down opening & dismantling descaling brushing cleaning of storage tanks (b) Examine water tightness of stotage tank after cleaning (c) Carry out operations of stop cock, push cock, float valve etc (d) Replace washer & glands of all taps to ensure water tightness (e) Inspect over flow and remove blockage obstruction if any (f) Inspection and treatment of leakage of refrigerant in the system. (g) Check thermostate, Relay capacitor,fan motor, compressor and test its functioning (h) Inspect drain pipe and remove blockage if any (j) Check & correct all electrical wiring and its functioning (k) Testing of water coolers after repairs for satisfactory functioning complete (l) Replacing minor spares (ie groomet rubber/rubber lining/washers/nuts&bolt) as required Note :- During servicing of unit, if anymajor spares / parts are required to be replaced it shall be measured and paid separately under respective items mentioned here- in - after as per direction. |
| 14 | Overhauling & servicing ofRefrigerator/Deep Freezer any capacity and make by carrying out the following works at different location of different establishment complete all as specified and directed by Engineer-in-charge (a) Inspection, taking down opening & dismantling, brushing washing cleaning of refrigerator (b) Check and correct earth continuity and all electrical wiring and its functioning complete(c) Check thermostate, Relay capacitor,fan motor, compressor and test its functioning (d) Rectification of minor defects, replacement of door rubber gasket, door bulb(e) Inspection and treatment of leakage of refrigerant in the system.(k) Testing after any repairs for satisfactory functioning complete (l)Replacing minor spares (ie groomet rubber/rubber lining/washers/nuts&bolt) as required Note :- During servicing of unit, if any major spares / parts are required to be replaced it shall be measured and paid separately under respective items mentioned here- in - after as per direction. |
| 15 | M&L for disconnecting the unserviceable sealed compressor unit from the Water Cooler (capacity 20/40 Ltrs) of any make & modeland S&F new hermetically sealed compressor unit, of existing specification, including brazing work, laying of extra copper tubing, pressure testing, dehydration, gas charging upto required level, connecting itwithboth refrigerant line & electrical line for smoothoperation on single phase 230 Volts, 50HZ AC supply and testing on full load for satisfactory functioningall as specified and as directed. |
| 16 | All as per Item No 15 above but capacity 40/80Ltrs. |
| 17 | All as per Item No 15 above but capacity 60/120Ltrs. |
| 18 | M&L for disconnecting the unserviceable sealed compressor unit from the Refrigerator (capacity 165 to 260 Ltrs) of any make & model and removing the same and S&F new hermetically sealed compressor unit, of existing specification, including brazing work, laying of extra copper tubing, pressure testing, dehydration, gas charging upto required level, connecting itwithboth refrigerant line & electrical line for smoothoperation on single phase 230 Volts, 50HZ AC supply and testing on full load for satisfactory functioningall as specified and as directed. |
| 19 | All as per Item No 18 above but capacity 280 to 315 Ltrs. |
| 20 | All as per Item No 18 above but capacity 340 to 480Ltrs. |
| 21 | M&L for disconnecting the unserviceable sealed compressor unit from the Deep Freezer (capacity upto 405 Ltrs) of any make & model and removing the same and S&F new hermetically sealed compressor unit, of existing specification, including brazing work, laying of extra copper tubing, pressure testing, dehydration, gas charging upto required level, connecting itwithboth refrigerant line & electrical line for smoothoperation on single phase 230 Volts, 50HZ AC supply and testing on full load for satisfactory functioningall as specified and as directed. |
| 22 | Supply and topping up/ full charging of Refrigerent Gas (R-32/R-410 A/R-134A/as per unit specification) for any type any specification of Air conditioners, Water coolers, Refrigerators & Deep freezers as per standard practice after pressure testing with filling of nitrogen gas, flushing out the system free from any oil / grease etc. cheking for leakages if any in the refrigerent system making good the leaking parts with necessary brazing/welding, ensuring leak proof system and testing for satifactory performance at different locations complete all as specified and as directed. (Note:- Cost of any type Refrigerent Gas included in the quoted rate) |
| 23 | S&F in replacement the following spare parts for Air conditioners, Water coolers, Refrigerators and Deep freezers of any make & model, completeall as specified and directed. |
| 24 | Thermostate switch suitable for water cooler/ Refrigerator/Deepfreezer |
| 25 | Starting relay kit suitable for water cooler/ Refrigerator/Deepfreezer |
| 26 | Connector open type suitable size as per existing for AC outdoor unit. |
| 27 | Condensor motor of suitable size as per existingincluding blade complete with clamps & boltsfor water cooler/ Refrigerator/Deepfreezer. |
| 28 | S&F 15 mm bore push cock brass body chromium plated for water coolercompleteall as specified and directed. |
| 29 | Filter strainer/drier as per existing same for refrigerator/Deep freezor/watercoolers/window AC completeall as specified and directed. |
| 30 | Evaporator cooling coil as per existing set for refrigerator/Deep freezor/watercoolers completeall as specified and directed. |
| 31 | S&F PVC insulated 3 core round flexible copper cable 1100 v grade of size 2.5 sqmm completeall as specified and directed. |
| 32 | S&F PVC insulated 4 coreround flexible copper cable 1100 v grade of size 2.5 sq mm completeall as specified and directed. |
| 33 | PCB with control unit complete for Refrigerator of any capacity, including features of digital display as per exsting specification and model, completeall as specified and directed. |
| 34 | Metal top plug of suitable for AC Socket completeall as specified and directed. |
| 35 | Overload protector suitable for water cooler/ Refrigerator/Deepfreezer completeall as specified and directed. |
| 36 | Expansion Valve/ NRV of suitable size as per existing for air compressor of AC, Refrigerator, Deep Freezer, Water cooler Note:- (for item sl No 1 to 23)(i) Contractor will provide well experienced 1 No AC/Ref Mech/Elect with Helper for attending complaint/above works on emergengy basis (within 2-4 Hrs) rectifying the defects and making equipments / Appliances satisfactory functional, in addition to man power required for execution of other routine works.(ii) All complaints should be attended with in 12 hours of reporting of complaints. Panelty charges for non attending complaints/above works with in 12 hrs shall be double the quoted rate as per connected item of the above works.(iii) All Tools & Plants required for repair work shall be provided/arranged by the contractor at his ownarrangement to trade men & helpers. |
| 37 | Dismantling ACSRconductors from the disturbed span including removing the binding with insulator, removing line spacer, of any size for LT/HT OH Line, etccomplete all specefied and as directed |
| 38 | M&L for Stringing and Fixing in position ofnew ACSR conductor in over Head lines conductor (squirrel/wessel/rabbit) including binding with aluminium binding wire complete all as specifiedand as directed |
| 39 | S&F pin type porcelain vitreous white brown or green insulators including one galvanizedsteel spindle two galvanized iron washers and onegalvanized iron nut 100 mm height, 65mm dia for 1100 volts grade complete including dismantling of old unserviceable insulator complete all as specifiedand as directed |
| 40 | S&F Shackle Type Porcelain, vitreous, white, brown or green insulator including galvanised mild steel straps, washers, insulator bolts, washers and nuts 75 x 90mm for 1100 volts grade complete including dismantling of old unserviceable insulator complete all as specifiedand as directed |
| 41 | M&L for disctype porcelain, vitreous 145 mm hight & 255 mm dia ball & socket type, white, brown or green,two-in-series assembly for tension clamps for conductors, working pressure 1100 Vup to 11 KV including galvanised mild steel straps washers insulator bolts & nuts including taking down old unserviceable insulator any type,any size complete all as specified & as directed |
| 42 | M&L for Pintype porcelain, vitreous 150 mm hight & 150 mm dia ball & socket type, white, brown or green,two-in-series assembly for tension clamps for conductors, working pressure 1100 Vup to 11 KV including galvanised mild steel straps washers insulator bolts & nuts including taking down old unserviceable insulator all as specified and directed. |
| 43 | M&L for cross arms, bracings, clamps and back plates fabricated from structural steel section including nuts, bolts, washers, drilling holes for bolts in any shapes or size all as directed & painting of one primer coat and under coat and one finishing coat including taking out unserviceable material complete all as specified and as directed by Engineer-in-Charge. |
| 44 | M&Lstay assembly complete with accessories as shown in elect plate no- 1 of SSRfor dia of stay rod 20 mm incl GI stay strand of size 7/3.15 mm (maximum length 11.00 mtr) to keep the pole in vertical position incl loop insulator stay all as specified and directed including dismantling and taking out old unsv stay assembly set complete (PCC will be measured and paid separately) |
| 45 | Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc as required 4mm dia galvanised iron or steel wire including taking down old unserviceable complete all as specified and as directed |
| 46 | M&L for steel tubular swaged poles complete with cast iron base plate, final taper plug, bolts, nutsand screws as specified type 410 SP- 31, 9 metre long including erection, painting with two coat of synthetic enamel paint over a coat of red oxide or primer complete including taking down old unserviceable complete all as specified & directed. (Note Excavation earth work and PCC paid and measured seperately) |
| 47 | All as per item No. 33 above, but type 410 SP-22, 8.5 metre long |
| 48 | M&L for cement concrete type D-2 1:4:8 (using 40 mm graded crushed stone aggregate) as in making good surfaces in road cutting, pole foundation, stay concrete etccomplete all as specified & directed. |
| 49 | M&L for plain cement concrete type C-1 1:3:6 (using 20 mmgraded crushed stone aggregate)as in coping including necessary form work and finishing exposed surface/white washing complete all as specified & directed. |
| 50 | Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtr depth for taking out/for laying under ground cables/pipes etc and getting out any type soil complete all as specified & directed. |
| 51 | Returning filling in including spreading, levelling, watering and well ramming in layers n-exc 25 cmcomplete all as specified & directed. |
| 52 | Removing excavated soil to a distance n-exc 50 mtr and depositing where directed at a level n-exc 1.5 mtr above the starting point complete all as specified & directed. |
| 53 | Supply and spreading fine river sand in trenches for cushioning of under ground cable/filling cable ducts complete all as specified & directedby Engr-in-Charge at site Note : - Only punned thickness shall be measured for payment purpose |
| 54 | Supply and lay burnt brick sub class ‘B’ of standard size laid in trenches as protection to cables complete all as specified & directed. |
| 55 | Boring of holes under road, pavement, hard standing by trenchless technologytechnique for 40-80 mm dia pipe , complete all as specified & directed. |
| 56 | M&L for PVC Flexible suction hose pipe (light grade), laid in trenches, under coping, bendor fixing on wall/pole/crossing nallah etc of 40mm bore,complete all as specified & directedby Engineer-in-Charge. |
| 57 | Supply and fixing GI pipe light grade for cable protection , laid in trenches or fixed on pole/wallfor passing LT cables ofsizes80 mm dia including taking out old rusted pipe complete all as specified & directed. |
| 58 | All as per item No 44 above but 40 mm dia all as specified and directed. |
| 59 | Supply and laying LT UG cable XLPE insulated heavy duty electric cable with aluminium stranded conductor, 1100 volts grade, cross sectional area 6 sq mm 2 core including taking out old unserviceable cable complete all as specified & directed. |
| 60 | All as per item No 46 above but 10 sq mm 2 core |
| 61 | All as per item No 46 above but 16 sq mm 4 core |
| 62 | Supply and laying LT UG cable XLPE insulated heavy duty electric cable with aluminium stranded conductor, 1100 volts grade, cross sectional area 25 sqmm 4 core (laying/ fixing against item Srl No 24 above taking down of ACSR conductor) complete all as specified & directed. |
| 63 | All as per item No 49 above but 50sq mm 3.5 core |
| 64 | All as per item No 49 above but 95Sq mm 3.5 core |
| 65 | Supply and fixing cable jointing kit straight through1100 V grade cable, heat shrink type joint complete with jointing material and accessories suitable for LT cable of size 6 Sqmm to 16 sqmm, Outdoor type complete all as specified & directed. |
| 66 | Supply and fixing cable jointing kit straight through for 1100 V grade cable, heat shrink type joint complete with jointing material and accessories suitable for LT cable of size 25 Sqmm to 50 sqmm, Outdoor type complete all as specified & directed. |
| 67 | Supply and fix cable jointing kit straight throughfor 1100 V grade cable, heat shrink type joint complete with jointing material and accessories suitable for LT cable of size 70 Sqmm to 120 sqmm, Outdoor type all as specified and directed. |
| 68 | S&F sheet metal enclousure MCCB VTPN DB (without MCCB) double door type AC 415 V 4 way with suitable size bus bar , suitable forMCCB upto125 Amps 4 pole, as incomer,flush to wall, IP 54, Isolated Neutral Bar and door earthing including taking down old one complete and making good of distructed surface all as specifed and directed. |
| 69 | S&F (in replacement) On load change over switch 63 Amps, 415V, AC 50 Hz, front operated handle, totally enclosed in sheet metal enclosure including fixingon wall with suitable accessories and connecting the cable end with suitable size lugs, nuts/bolts/washers etc, including taking out the existing unserviceable complete all as specified and directed. |
| 70 | Supply and fixing in repairs MCCB adjustable thermal & fixed magnetic release 4 pole 16 kA 125 Amps including taking out the existing unserviceable complete all as directed at site. |
| 71 | All as per item No 57 above but 16 kA100 Amps . |
| 72 | All as per item No 57 above but 16 kA 63 Amps . |
| 73 | S&F MCB 40 to 100 Amp TP&N, 240 volts 10 KA \"C\" series as fixed in repairs including taking down old unserviceable one complete all as specified and directed. |
| 74 | S&F MCB 25 to 32 Amp SP&N, 240 volts 10 KA \"C\" series with all incoming/outgoing connections with proper size lugs including taking down old unserviceable one complete all as specified and directed. |
| 75 | Material and labour for earthing complete with galvanized steel earth plate electrode 600mm X 600mm X 6mm buried directly in ground vertically to a depth not less than 2.25 meter below normal ground level (with top edge of earth plate not less than 1.5 meter below ground level) connected to galvanized iron earth lead wire 4mm dia, (main earthing lead ) by means of galvanized bolts, nuts and washers all as shown in electrical plate no 3 of MES Schedule Part-I (2009) with connected to earth test point & to main switch board with & including adequate quantity of charcoal dust and common salt alround earth plate & 15 mm dia GI pipe light grade for earth lead protection pipe for suitable length and GI pipe 20 mm dia light grade for watering pipe with funnel & wire meshincluding necessary earth work and PCC (1: 3 : 6) type C-1 for earth pit and 40 mm thick pre-cast RCC cover in 1 : 2 : 4 type B1 with 3 Nos 8 mm dia TMT bars both ways completeall as specified & directed by Engineer-in-Charge. |