| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed pvc conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. (Group-A) |
| 2 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed pvc conduit as required.(a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 3 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed pvc conduit along with 1 No 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 4 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. |
| 5 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.a) 5/6 amps switch |
| 6 | a) 3 pin 5/6 amp socket outlet |
| 7 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). a) 4 way (4 + 12), Double door(Make- Legrand/L&T/Hager) |
| 8 | S/F following rating four pole, 415 Volts , isolator in the existing MCB DB complete with connection, testing & commissioning etc as reqd.a) 63 Amps (Make- Legrand/l&T/Hager) |
| 9 | S/F following rating four pole/single pole MCB in existing MCB DB complete with connection, testing & commissioning etc. as reqd.a) 6/16/25/32 amp SP MCB. (Make- Legrand/l&T/Hager) |
| 10 | S/F of MCB protected Socket outlet 4 module with metal box comprising of 01no. 25Amps socket and 01no. 25Amps Plug and 01no. 25Amps \"C\" series SPMCB for Split AC units i/c connection, testing etc. as required. (Make- Legrand /Havells/HPL/Standard) |
| 11 | Supply and fixing of 20 watt, LEDbox type fitting suitable for operation on 140 volts to 270 volts AC, 50Hz i/c fixing and connection etc. as required. (Phillips TMC-501 / 2 OR SS MAKE) |
| 12 | Supplying/Fixing of followingelectrical accessories in the light ftg / switch board/compound light connection, testing etc complete as required. |
| 13 | 20W LED Lamp |
| 14 | Brass batten/ angle holder |
| 15 | 1200 mm ceiling fan |
| 16 | S/F 40 mm dia PVC pipe on surface of wall for protection of cable etc. as reqd. |
| 17 | S/D 4 x 10 sqmm pvc insulated copper conductor cable in existing PVC pipe for extending 3 phase supplyto power plantwith copper socketing etc as reqd. (Make- Finolex/L&T/Cable corporation/Polycab) |
| 18 | Supplying/Fixing of following damaged / burnt out electrical accessories for the maintenance worksin the light ftg / switch board/compound light connection, testing etc complete as required. |
| 19 | 16/25sq mm Al socket |
| 20 | 10 sq mm cu socket |
| 21 | 4sqmm PVC insulated copper wire |
| 22 | Blanking plate |
| 23 | 63Amps 4 pole MCB |
| 24 | 63Amps 415VPorcelain Fuse unit |
| 25 | Stepped type Electronic Fan Regulator (Switch type) |
| 26 | ceiling rose |
| 27 | 1.5 mmsq 3 core copper cablecord |
| 28 | supply & laying of 6 mmsq 2core service wire |
| 29 | Supply of the following sizesPVC insulated & PVC sheathed Aluminium conductor armoured cable 650/1100 V. grade confirming to IS : 7098 (Part-1) 1988i/c transportation to respective sites etc. as required for replacement of faulty/burnt out cables. |
| 30 | 4 core 16 sqmm |
| 31 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. |
| 32 | Up to 35sqmm |
| 33 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. |
| 34 | Up to 35sqmm |
| 35 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size Up to 35sqmm direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. |
| 36 | Up to 35sqmm |
| 37 | S/F MV cable end terminationswith brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 38 | 4 X 16 sq. mm (28mm) |
| 39 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 40 | Supply of exhaust fans by a new complete set forreplacement of faulty/burnt outof380mm /15\" heavy duty1400 RPM Exhaust Fans having maximum free air delivering capacity not less than 3250m3/ hour(1910 CFM) and maximum sound level not more than 60-65 db. with a capacitor start and run type, continuously rated, totally enclosed and ruggedly built motor having pre-lubricated double ball bearingwith Class \"A\" and \"E\" insulation suitable for operation on 230 volts single phase 50 HZ AC supply with features forsmooth &silent operation todeliver the maximum output at lower operating cost. The impeller of the Exhaust Fan isto bepropeller type andboth hub and impeller are to be dynamically balances and frames and arms mounted on rubber bushing so that, vibration are virtually eliminated. (Make- Almonard HD (ISI) / Crompton Greavesor similar superior) (Excluding installation) |
| 41 | 380mm /15\" heavy duty1400 RPM, maximum free air deliverying capacity not less than 3250m3/ hour(1910 CFM) and maximum sound level not more than 60-65 db. |
| 42 | Installation of exhaust fan up to 450mm sweep in the existing opening with fastener/ GI nuts and bolts, including making good the damage, connection, testing, commissioning etc. as required |
| 43 | Making opening on brick wall of suitable size for fixing of 380mm sweep Exhaust Fans including making good the damages, minor civil works etc. complete as required. (For room BTS sites) |
| 44 | Installation ofgravity type Aluminum/ GIlouver shutters suitable for 380mm sweep exhaust fans with fastener /GI nuts and bolts etc. complete as required. |
| 45 | ITC of Split type Air conditioner unit i/c mounting/fitting of indoor and outdoor units at their respective locations, laying refrigerant pipe lines of 6 mtrs.length and connecting both the units after drilling holes in the wall if required, insulating the suction pipe with expanded polythelene foam tubing, laying drain pipe etc.to throwout the condensate water being formed in the indoor unit, leak testing of entire system, charging refrigerant gas in the unit, suitable electric wiring etc. complete as reqd. |
| 46 | Transporation of SPAC from Sub-Divisional Electrical store Balasore to site to and fro within 100 KM as reqd |
| 47 | S/F of suitable size powder coated of MS bracket (2 nos.) for fixing of the outdoor unit of the split A/C units on wall with anchor bolt after drilling holes etc. complete as reqd. |
| 48 | Supply ofHot pressed molded SMC Junction box, hinged double door type of following sizes suitable for application for fixing Electrical controls /switch gears/meters etc. with provision for cable entry/exit from bottom/side ,locking arrangements including supply and fixing of 2nos4 pole stud connectors, interconnections with suitable sizesingle core PVC insulated copper conductor cable with copper sockets/lugs including fixing onexisting pole / existing MS/GI angle stands etc. complete as required. |
| 49 | Size not less than 400mmX300mmX190mm (inside dimensions) (Make-Sintex model: SINTEX JB-4030/SS) |
| 50 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 51 | Providing and fixing 25 mm x 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 52 | Providing and fixing 25 mm x 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 53 | Providing and fixing of earth bus of 50 mm x 5 mm GIstrip of400 mm length on surface with suitable size insulators, drilling holes for connections etc. complete as required. |
| 54 | Supplying and laying of 40mm diaHDPE pipe of PN 8 for protection ofcable,GI strip complete as required.( Make : Oriplast /SS ) |
| 55 | Sypplying and Fixing of 30 Watt LED street light Fitting on the existing GI bracket/pole i/c connection testing etc complete as required.( Make - Havells ( Model -ENDURASUNDOWNSL30W) orSS make) |
| 56 | Sypplying and Fixing of 32mm dia L-class GI Pipe bracket for fixing of LED street light Fittingi/c connection testing etc complete as required. |
| 57 | Dismantling the existing all Electrical items like panel board, change over, XLPE cable, meter box, Distribution box & light & fan wiring from its old position & Shifting to new Room Position etc. complete as reqd. |
| 58 | Dismantling the existing life expaired old 1.5TR SAC/WAC units( Indoor & Out door units)from its position & Shifting of the Sub-divisional Electrical store Baalasore for scrapping. |
| 59 | Transportation of electrical dismantledmaterials of(2nos split AC, fans,ftiing,DB,MCB,wirings,cables,damage feeder box etc) from old BTS at Khaira to Electrical store at Balasore on road by engagement of required man power, tools & Plants, lifting, suitable transportation medium including loading Unloading at both ends complete as required. |
| 60 | S/F ofChange over switches of following ratings , fixing, connection & testing etc. as required. |
| 61 | 63Amp 4-pole on load change over switch in sheet steel enclosure , front handle type (Make: HPL Socomec /Havells / L & T) . |
| 62 | Charges formaking co-ordination and liaison withsupply company for obtaining Demand note / submittingtest reports for energisation of LT lineetc. complete as required.. |