| 1 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth, forfoundation, laying of cable etc and getting out insoft/loosesoilcomplete all as specified and as directed |
| 2 | Returning, filling in, including spreading levelling watering and well ramming in layers not exceeding 25 cmas in soft/loose soil complete all as specified and as directed. |
| 3 | Removing excavated soilto a distance not exceeding 50 m anddepositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and as directed. |
| 4 | M&L for natural river sand as cushioning of cables including spreading and punning downcomplete all as specified and as directed.Note : Punned thickness shall be measured for payment purpose |
| 5 | Supply and Laying old size bricks , sub class \"B\" of size 230mm x 115 mm x 75 mm for cable protection complete all as specified and as directed. |
| 6 | Supply, laying, jointing and testing XLPE cable insulated, armoured, earthed, heavy duty electric cable with aluminium conductor , 1100 Volt grade, cross sectional area 95 sqmm 3.5 core including necessary cable lugs, glands, insulation tape etc complete all as specified and as directed.Make:- Finolex/ Gloster/ Polycab |
| 7 | Supply, commissioning erecting and testing complete of manufacturer or OEM manufactured, static silient (sound proof enclosure) Diesel Engine driven Generating set of capacity 82.5 KVA, water cooled, 415 volts (AC three phase, 4 wire system of supply) 50 Hz at power factor 0.8 minimum.The DG set shall consists of diesel engine coupled to a matching alternator, through flexible coupling and mounted on common base frame and complete with control panel standardized by manufacturer, fuel tank with mounting arrangements and inlet, outlet return inlet oil arrangements, exhaust pipe complete and suitable for conditions prevalent at Bamrauli (capacity of engine, alternators shall worked out taking all derating factors into consideration) including PCC foundation (of suitable size leaving at least 0.5m all around for ease of movement and 0.5m height), anti-vibration pads complete all as specified and directed, including all feature to comply with latest CPCBIV+ guidelines and comprising of followings:-(A) DIESEL ENGINE :- Diesel engine 1500 RPM, direct injection, Six cylinder, four stroke, conforming to conforming to IS:100001/ISO 3046/BS:649/BS:5514 amended upto date, for continous running capable of taking 10% overload for one hour in 12 hour, water cooled, naturally turbo charged, capable of giving adequate BHP to drive Alternator capable of delivery 82.5 KVA at outdoor atmospheric conditions at Bamrauli ( Taking all derating factor into consideration) fitting with the following accessories subject ot the design of manufacturer:- |
| 8 | (i) Dynamically balanced fly wheel. (ii) Air cleaner (iii) Electronic Governor class 1C(iv) Dry exhaust manifold with suitable exhaust residential grade silencer to reduce the noise level (v) Radiator cooling (vi)Radiator fan with guard (vii) Vaccum indicator (viii) Fuel filter and fuel houses (ix) Fuel injection pump (FIP) (x) Fan and water pump assesembly (xi) Lub oil filter and pump(xii) Electric starting system with battery charging alternator and axial type started motor including adequate number of high capacity maint free lead acid bty as per manufacturer recommendation including inter connecting cables/leads with terminals complete with starting/stopping switch voltmeter, etc01 set (xiii) Engine safety shut down system against lowoil pressure and high water pressure(xiv) Exhaust gas driven turbo charge(xv) Oil filter(xvi) Lub oil cooler |
| 9 | (xvii) Engine main manual with spare part list(xviii) Suitable designed acoustic enclosure as per CPCB regulations (xix) Any other item not included / specified but is a standard design of the manufacturer.(B) Engine instrument panel : Engine instrument panel shall comprising of thefollowing:-(i) Starting on /off switch.(ii) water temp auge. (iii) Hour meter cum RPM indicator(iv) Lub oil pressure gauge (v) Lub oil temperature gauge (vi) Battery charging meter (vii) Safety alarm against high water temp and lub oil pressure.(viii) Any other item not included/specified but is a standard design of the manufacturer.(C) ALTERNATOR :- (Make: Kirloskar electric co/ Crompton/ Stemford) shall be self excited, self regulated, brush less for 82.5 KVA continous operation at the speed of 1500 RPM at 415 volts, 50Hz three phase, 4 wire system with advance electronic voltage regulator to ensure high voltage accuracy with +1% with class H insulation and SPDP enclosure directly coupled with engine through flexible couping and conforming to IS-4722 complete-01 No. Note:- Alternator should be able to deliver output rating at actual site condition. |
| 10 | (D)Common fabricated base frame for engine and alternator made from structural channel, jerk proof PCC 1:2:4 mix type B1 foundation including adequate number of suitable anti-vibration pads all as per manufacture recommendations is deemed to be included in the unit rate quoted by the contractor.Bottom mounted (or as per manufactures design) steel fuel tank fabricated out of 14 SWG MS sheet of capactiy not less than 12 hrs continous operation inside canopy withfuel level guage, drain plug locking arrangements etc with and including GI pipe connections duly laid as per engineering practice complete all as specifided and directed.Bypass arrangement by providing separate panel made out of 3mm thick CRCA sheet, outdoor type with connecting copper bus bar of suitable size from change over and set of 3 Nos indication lamp for R, Y and B and 2 Nos 4 pole on load change over switch front handle operated of capacity 63 Amp is to be installed near AMF panel complete all as specified and directed.(i) Hour run meter. (ii) Any other item not included/ specified but is a standard design to the manufacturer. |
| 11 | (E) AMF CONTROL PANEL :- Supply, fabricating and testing of factory mounted cubical automatic main failure panel with degree of protection IP-42 conforming to IS-2147, suitable for 82.5 KVA capacity DG Set, fabricated using 14 Gauge CRCA sheet, powder coated comprising of suitable rated bus bar, internal wiring with control fuse, provn of connecting incoming and outgoing leads/ bus bar as approved with and including following accessories:- (i) Master switch for auto/manual/reset/off-01 No.(ii) Ammeter digital type, 96X96 mm with CT\"s-03 Nos aux supply 230 vlts, AC, acuracyclass 1.(iii)Voltmeter digital type 96x96 mm to read 0-500 voltssupply 230 volts, accuracy class 1.0.(iv) Digital frequency meter-01 No aux supply 230 volts, AC(v) Push button start, stop, reset-01 No.(vi) Set of lamp for indicating load a set, low pressure, high cylinder temperature, load on mains, set fails at start, low oil presure.(vi) Battery charger connected to load. (vii) Transformer of adequate rating.(viii) Ractifiers |
| 12 | (ix) DC ampere meter and voltmeter. (x) Fault accept / reset push button. (xi) Set of relays and contactor suitable for 82.5 KVA DG Set for automatic start and automatically shut down of suitable rating and capacity adjustable to 70 to 100% and 2 Nos MCCB 4 pole, 100 Amp, 16 KA fixed on main supply and DG set supply.(xii) Make of AMF control panel shall be as per OEM recommendations. |
| 13 | Earthing complete with galvanized steel earth plate electrode 60 cm x 60cmx 6 mm thick buried direcly in ground vertically to a depth not less than 2.25 meters below normal ground level with the top edge of earth plate not less than 1.5 meters below ground level connected to galvanized iron strip 32 x 6 mm by means of bolts, nuts, check nuts and washers made out of galvanised iron or steel all as shown in electrical plate No.3 of SSR part I-2009 and earth wire protected by galvanized pipe light grade 40mm bore and through test point, filling of adequate quantity ofcharcol and common saltincluding necessary earth work and excavation in any type of soil, GI light grade 20mm bore watering pipe with funnel and wire mesh, PCC 1:2:4 type B-1 using 20 mm graded stone aggregate as inchamber with cast iron earthing pit cover having size 250 mmx250 mm, weight not less than 7.5 Kg conforming to relevant IS with framecomplete all as specified and directed and testing on completion. |