Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | M&L for cement concrete1:4:8type D2,using 40mm graded stone aggregate as in foundations filling and mass concrete complete all as specified and directed. |
| 2 | M&L for PCC 1:3:6 type C2, using 40mm graded stone aggregate,asin foundation filling & mass concrete complete all as specified and directed. |
| 3 | M&L for PCC 1:2:4using 40mm graded stone aggregate, type B2 asin foundation filling & mass concrete complete all as specified and directed. |
| 4 | M&L for providing pain Cement Concrete(1:2:4) type B1 using 20mm graded crushed stoneaggregate as in surface channel and drain complete all as specified and directed. |
| 5 | M&L for PCC 1:2:4, type B-0,(using 12.5mm graded crushed sone aggregates) as in copping and the like including weathering, slightly rounded or chamfered angles and throating complete all as specified and directed. |
| 6 | M&L for Providing precast ce- ment concrete type B1, 1:2:4 using 20mm graded crushed stone aggregate in landings, cover slabs (for manholes etc.) chullah hoods, chajjas, water troughs, mangers, shelves and similar articles with plain faces etc. and setting in cement mortar 1:4 complete with joints to match complete all as specified and directed. |
| 7 | M&L for formwork to sides of concrete foundations, footings, bases of columns, raft and raft beams,sides and soffits (if any) of foundation and plinth beams; and similar work; vertical to rough finished surface complete all as specified and directed. |
| 8 | M&L forTMT bars 6 to 8mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and directed. |
| 9 | M&L forrolled sections as in main and cross beams, hip and jack rafters, purlins where connected to comman rafters and running railsfixed with angle cleats or other connecting plates conforming to Fe 410 W (Gde E-250) quality-A including welded to rafter,purlin complete all as specified and directed. |
| 10 | M&L for Plates (plain or chequered) channels, square cut or notched (ordinary and counter sunk) forming holes, without any attachment etc conformingFe-410W(GdeE-250) quality -A complete all as specified and directed. |
| 11 | S&F Pre- painted coloured trapezoidal profiled Galvalume/ Zincalume sheet with min thickness 0.50mm TCT confirming to IS - 513(AZ-150 GSM, Al Zn allay metalic coating with 550 Mpa yield stress as per AS-1397) as in roof covering/cladding towall, fixed with self tapping screws colour exterior coat of silicon modified polyster/BHP x RW paint system 20 micron top coat applied over 5 micron primer and 5 micron polyster back coat applied over 5 micron primer , all fixed with galvanized self drilling self tapping fastner (12-14 x 55 with EPDM seals) complete all as specified and directed. |
| 12 | S&F Pre- painted coloured plain sheet Galvalume/ Zincalume sheet with min thickness 0.50mm TCT confirming to IS - 513(AZ-150 GSM, Al Zn allay metalic coating with 550 Mpa yield stress as per AS-1397) as in roof covering/cladding towall, fixed with self tapping screws colour exterior coat of silicon modified polyster/BHP/ XRW paint system 20 micron top coat applied over 5 micron primer and 5 micron polyster back coat applied over 5 micron primer , all fixed with galvanized self drilling self tapping fastner (12-14 x 55 with EPDM seals) complete all as specified and directed. |
| 13 | M&L for 75mm thick PCC 1:3:6 type C2(Using 40mm graded stone aggregate) as in sub base of floor complete all as specified and directed. |
| 14 | Dismantling of floor, hearth or wall tiling / Paving Blocks including cement mortar bedding (but not backing), removing serviceable tiles to store and rubbish off the premises etc complete all as specified and directed. |
| 15 | M&L for two coats of synthetic enamel paint over one coat of red oxideon new steel surfaces of any description over 10cm in width or girthincluding preparation of surfaces complete all as specified and directed. |
| 16 | Dismantling of stone slabs and tiles of any description or thickness in floors, approachs, dado/Partitions laid bedded and pointed in any mortaretc complete all as specified and directed |
| 17 | Demolition of cement concretein ground floorand paving n.exc 15 cm thickness( below or above ground level) complete all as specified and directed. |
| 18 | Demolition of Concrete (reinforced) of any description and in any position not otherwise specifically provided for complete all as specified and directed. |
| 19 | Dismantling wrought iron or mild steel work of any description not otherwise provided for complete all as specified and directed. |
| 20 | Dimantling of Asbestos cement (corrugated,semi corrugated, etc.) sheets in roof coverings including ridges etc complete all as specified anddirected |
| 21 | M&L for 18-20mm thick Granite (of any type) work (table rubbed and polished) in steps, jambs, pillars, win dow-cills, cooking plat forms and like in cement mortar (1:4) including point ing in white cement (1:2) us ing marble dust with admix ture of pigment to match with shade of granite over and including 20mm thick bedding layer in cement mortar 1:6 including grinding and polishing complete all as specified and directed. |
| 22 | M&L for 75mm thick PCC 1:3:6 type C1(Using 20mm graded stone aggregate) as in plinth protectionfinishedeven and smoothwithout using extra cement complete all as specified and directed. |
| 23 | M&L for Glazed ceramic tiles coloured 300mmx 450mm , 6 to 7 mm thick as in skirting / dado, set and jointed in neat cement slurry and pointed in white or colour cement to match over and including 10 mm thick rendering in cement mortar 1:4 on fair faces of brick work or concrete surface etc complete all as specified andand as directed |
| 24 | M&L for exterior grade(Lequre coated), coloured glossyfinish rubber pressed, cement concrete designer chequered tiles of size 30cm x 30cm x 25mm thickset, jointed and pointed in neat cement slurry with grey cement and pigment to match the shade / colour / matrix of tiles as in floor etc. completeincluding provision of 20mm screed in cement moertar 1:6, complete all as specified and directed. |
| 25 | M&L for providing and laying 60mm thick factory made chamfered edge cement concrete paver block of M-35 grade with approved colour, design & pattern as in footparth, parks,lawns, drive ways or light traffic parking etc., of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over and including 50mm thick compacted bed of fine sand, compacting and proper embedding/ laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand; completeall as specified and directed. |
| 26 | Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits,manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in soft/loose soil complete all as specified and directed. |
| 27 | Excavating in trenchesexc1.5m but not exc 3.0m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n.exc 10sqm on plan and n.exc 1.5m in depth and getting out. in soft/loose soil complete all as specified and directed. |
| 28 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm complete all as specified and directed. |
| 29 | Removing excavated material (soil) n exc 50m and depositing where directed at a level n exc 1.5m above the starting point complete all as specified and directed. |
| 30 | M&L well burnt old size sub Class ‘B’ bricks, laidin trenches for cable protection complete all as specified and as directed by the Engineer-in-Charge. |
| 31 | M&L for in repair80mm dia GI pipe Light grade with all necessary fittings laid in trenches, fixed to wall/pole/under road/floor etc for cable protection complete all as specified and as directed. |
| 32 | M&L for in repair50mm dia GI pipe Light gradewith all necessary fittings laid in trenches, fixed to wall/pole/under road/floor etc for cable protection complete all as specified and as directed. |
| 33 | M&L for sand cushioning for protection of underground cable, consolidatedand compacted with clean dry sand complete all as specified and directed. |
| 34 | M&L for Cross arms, bracings, supports,clamps and back plates fabricated from structural steel sections including nuts, bolts, washers,welding, bending cold or hot,drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of aluminum paint complete all as specified & directed. |
| 35 | Supply and erecting steel tubular pole, swaged, complete with cast iron base plate, finial taper plug, bolts, nuts, washer and screws including painting with two coats of aluminium paint over one coat of red oxide primer on all exposed surfaces and tarring with black bituminous paints to portion embedded in PCC including numbering of poles with two coats of synthetic enamel paints, type 410-SP-31 (9 meter long) complete. (Note Excavation & Earth work andPCCfoundation/baseshall be measured and paid separately under relevant items of this BoQ) |
| 36 | S&F in repairs MCCB 63 Amps 4 pole, 415 V, breaking capacity 16 KA,Ics=100% ICU including spreader terminals & connected accessories both ends complete all as specified and directed. |
| 37 | S&F in repairs MCCB 100 Amps 4 pole, 415 V, breaking capacity 16 KA,Ics=100% ICU including spreader terminals & connected accessories both ends complete all as specified and directed. |
| 38 | S&F in repairsMCCB 160 Amps, 4 Pole, 415 V, adjustable type, with breaking capacity 36 KA, Ics=100 % ICU including spreader terminals & connected accessories both ends complete all as specified and directed. |
| 39 | S&F in repairsMCCB 200 Amps, 4 Pole, 415 V, adjustable type, with breaking capacity 36 KA,Ics=100 % ICU including spreader terminals & connected accessories both ends complete all as specified and directed. |
| 40 | S&F in repairsMCCB 250 Amps, 4 Pole, 415 V, Adjustable type, with breaking capacity 36 KA, 100 % ICUincluding spreader terminals & connected accessories both ends complete all as specified and directed. |
| 41 | S&F in repairsMCCB 320 Amps, 4 Pole, 415 V, adjustable type, with breaking capacity 36 KA, Ics=100% ICU including spreader terminals & connected accessories both ends complete all as specified and directed. |
| 42 | M & L for XLPE insulated GI wire/Strip armoured Electric power cable (Heavy duty) with stranded Aluminium conductor 1100 Volts grade, cross sectional area 150Sqmm 3.5 core laid in trench/pole/on wall completer all as specified and as directed. |
| 43 | M & L for XLPE insulated GI wire/Strip armoured Electric power cable (Heavy duty) with stranded Aluminium conductor 1100 Volts grade, cross sectional area 120Sqmm 3.5 core laid in trench/pole/on wall completer all as specified and as directed. |
| 44 | M & L for XLPE insulated GI wire/Strip armoured Electric power cable (Heavy duty) with stranded Aluminium conductor 1100 Volts grade, cross sectional area 95Sqmm 3.5 core laid in trench/pole/on wall completer all as specified and as directed. |
| 45 | M & L for XLPE insulated GI wire/Strip armoured Electric power cable (Heavy duty) with stranded Aluminium conductor 1100 Volts grade, cross sectional area 70Sqmm 3.5 core laid in trench/pole/on wall completer all as specified and as directed. |
| 46 | M & L for XLPE insulated GI wire/Strip armoured Electric power cable (Heavy duty) with stranded Aluminium conductor 1100 Volts grade, cross sectional area 25Sqmm 4.0 core laid in trench/pole/on wall completer all as specified and as directed. |
| 47 | M & L for XLPE insulated GI wire/Strip armoured Electric power cable (Heavy duty) with stranded Aluminium conductor 1100 Volts grade, cross sectional area 16Sqmm 4.0 core laid in trench/pole/on wall completer all as specified and as directed. |
| 48 | Dismantling of ACSR or AAC conductor from LT servicefeeder or distribution line complete all as specified and directed. |
| 49 | Dismantling cross armsof MS channels or angle sections etc complete all as specified and directed. |
| 50 | Dismantling insulators any type any sizes complete all as specifiedand directed. |
| 51 | M&L for earthing complete with galvanised steel earth plate electrode 60×60cm×6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised iron 25x4mm earth lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No.3 connected to earthing test point including testing on completion including watering GI pipe 20mm bore medium grade, 15mm bore light grade GI pipe for protection of earth lead including provision ofconcrete pit in PCC (1:3:6) type C1, pre-cast RCC (1:2:4) type B1 cover slab 54 cm x 54 cm x 5 cm including 8mm dia TMT bars both ways @ 15cm centre to centre with one handle for lifting made out of8mm dia MS bar, funnel & wire mesh, excavation and earth work in any type of soil complete including dismantling existing all as specified & directed. |
| 52 | M&L for repair, serviceing and replacement of unserviceable accessories of LT Panel any make type/size includingwelding, brazing and drilling work etc complete all as specified and directed.including the followings.(a) Tightening of all loose conectiont of cableinside the panel and welding the broken door of the panel.(b)Clean all the rusted busbar through emery paper and fixing insulation heat shrink sleeves through out the busbar including strip connected with out going MCCB.(c) Cutthe damage insulation portion end of cable inside the panel and reconnecting its into positions after fixing the end termintion/Sleeves complete with suitable size of aluminium lugs and stainless steel nut bolts including excavation and earth work in any type of soilfor taking out the existing cable loop to fixing the end joint or reconnection in position.(d) Repair/Replacement ofburn/unserviceable voltmeter, ammeter,indication lamp including control wiring of the panel between voltmeter, Ammeter and their selector switch and CTs .(e)Repair/Replacement of all burn lugs inside the panel.(f) Replacement of all the GI rusted nut, bolts,and washers with made of stainless steel nuts, bolts and washers.(g) Cleanthe dust inside the panel by air blower/vaccum cleaner complete.Note : (a) The cost of nut bolts, washers, insulation tape, lugs etc essentially required to make the panel serviceable shall be deemed to be included in the quoted rate. (b) Other spare parts/accessories shall measured and paid separatelyunder relevant items of schedule. |
| 53 | Supply, installation, testing and commissioning 3 phase and neutral, 415 volts outdoor type LT panel board of size 900 mm height X 800 mm width X 500 mm depth (over all dimension)confirming to IS 8623, CPRI approved, factory fabricated &factroy assembled , waterproof,dust and vermin proof cubical type with locking arrangement , LT Panel made out of suitable size angle iron, channel and fabricated from 3.00 mm thick (minimum) CRCA sheet with anti corrosive coating and finally epoxy polyester powder coating of flint Grey shade (RAL-7032), independently housing for each control switch gear and indicating lamps with & includingbusbars made of pure copperduly insulated with heat retardent fire proof (HRFR) heat shrinkable sleeves of relevant colours. Bus bar shell be properly supported/mounted on epoxy insulators.All live parts and joints shall be insulated with (HRFR) shrouds, conforming to IS, including provn for cable gland and lugs for incoming and out going cable and connecting suitableearth strips .Suitable openable doors shall be provided of all operational switchgear and MCCBs and detchable cover shall be provided on all other accessories. Grouting the panel board in ground with & including suitable size foundation & plinth of PCC 1:3:6(type C-1 using 20 mm grade stone aggregate) complete.Panel shall be manufactured suitable for housing and including the following duly control wiring with multistranded copper condutor FRLS with colour coding incl connection with copper lugs complete for 3 phase 50 Hz electric supply :- |
| 54 | Incoming:(a) Copper strip busbar of current carrying capacity 400 Amps wrapped with PVC sleeves with maintained the colour code and provision of making holes with Copper nuts, bolts & washers for cable connections including hydrograpic insulators with nuts & bolts at both ends= 04 nos.(b) MCCB250 Amp, 4 Pole, 415 Volts, 36 KA rating with overload, short circuitfault protection 3 phase, Ics = 100% of Icu and total break time less than equal to 10 ms with Spreader terminal of both end side -03 Nos. Make: Schneider Cat no - LV525343 / Legrand Cat No: 420249/ Siemens, Cat: 3VA1225-4GE42-0AA0/ ABB, Cat No: 1SDA068111R1/ L&T (LK) Cat No : CM92109OOP1OG.(c) On load change over switch front handle open execution capcity 250 Amp 4 pole 415 volt AC 50 HZ suitable for horizontal and verticle mounting including terminal shrouds, source separator, phase barrier - 01 Nos(Make L&T, Siemen, ABB).(d) Digital type flush mounted 3 phase VAF + PF meter with input voltage measurement range 50-500VAC (P-P), Aux supply 30-300 Volt AC/DC, CT secondary site selectable 1-5A, Accuracy Cl-1-0.5.(e) RYBLED type indication lamp- Set of 03 |
| 55 | Out going:-(a) MCCB 100 Amp, 4 Pole, 415 Volts, 36 KA rating with overload, short circuitfault protection 3 phase, Ics = 100% of Icu and total break time less than equal to 10 ms with Spreader terminal of both end side -03 Nos. Make: Schneider Cat no - LV510317 / Legrand Cat No: 420055/ Siemens, Cat: 3VA1110-3GE42-0AA0/ ABB, Cat No: 1SDA067406R1/ L&T(LK) Cat No : CM91712OOKOOG |
| 56 | Supply ,fabrication, installation and testing of LT out door type factory made CPRI Approved , junction box of size 900mmX600mmX400mm (over all dimension) made out of 3.15 mm thick CRCA sheet dully supported with mild steel angle iron of size 40X40X5mm vertical frame and legs with mild steel flat iron 25X5 mm in horizontal sides of the frame with front and back side openable ,single hinged door / shutter with locking arrengement and powder coated finish both internal and external steel surfaces after necessary preparation of steel surfaces including providing PCC (1:3:6) type C2 foundation of size 0.80m X 0.6m X 0.90m depth (0.30m below ground level and 0.60m above ground level ) and connections of all outgoing / incomming existing cable of any size drawing / digging out cable from loops in trenches inclusive of necessary excavation and earthwork as required and relaying the cables including the following fitment accessories all complete as specified and directed.(a)Alluminium bus bar of size 50 mm X 6 mm X 400mm long wrapped with PVC sleeves with maintained the colour code and provision of making holes as required with nuts, bolts & washers for cable connections including hydrograpic insulators with nuts & bolts at both ends= 04 nos.(b)Enamelled iron danger notice plate of 1.60 mm thick mild steel sheet of size 200 mm X 150mm , white with letters , figures and conventional skull and bones in signal red and fixed with nuts and bolts on door / shutter of JB for LT -01 No. |
| 57 | Supply only epoxy type insulator for support of busbar grade 1100 volt as per existing size complete all as specified and directed. |
| 58 | Materialonly for control wiring of the panel with 1.5 sq mm multistranded, PVC insulated copper conductor 1100 Volt grade FRLS cable complete all as specified and directed. |
| 59 | Supply only LED phase indicator lamp colour RED/YELLOW/BLUE AC 220 Volt 50 Hz. complete all as specified and directed. |
| 60 | Supply only Digital Ampmeter of any range, flush mounting type of size96 mm x 96 mm (4”x4”) square dial 3 phase four wire system with selector switchcomplete all as specified and directed.. |
| 61 | Supply only Digital voltmeter of range (0-500) volts, flush mounting type of size96 mm x 96 mm (4”x4”) square dial 3 phase 4 wire system with selector switchcomplete all as specified and directed. |
| 62 | Supply only cast resin insulated type CT, Ratio 200/5Awith capable of withstanding momentary short circuitand symmetricalshort circuit for 01secondcomplete all as specified and directed. |
| 63 | Supply only cast resin insulated type CT, Ratio 250/5Awith capable of withstanding momentary short circuitand symmetricalshort circuit for 01second. complete all as specified and directed. |
| 64 | Supply only cast resin insulated type CT, Ratio 300/5Awith capable of withstanding momentary short circuitand symmetricalshort circuit for 01secondcomplete all as specified and directed. |
| 65 | Supply only cast resin insulated type CT, Ratio 400/5Awith capable of withstanding momentary short circuitand symmetricalshort circuit for 01secondcomplete all as specified and directed. |
| 66 | Supply only copper bus bar any size (5x20, 10x20, 10x25, 10x40, 10x50,10x80) mmduly insulated with heat shrink busbar insulation sleevescomplete all as specified and directed. |
| 67 | Supply only aluminium bus bar any of any size duly insulated with heat shrink busbar insulation sleevescomplete all as specified and directed. |
| 68 | Supply only rubber door gasket of any size for existing doorcomplete all as specified and directed. |
| 69 | M&L in repair for replacement of MS sheet cover of LT panel board made out of any thick MS sheet as per required shape and size including necessary fabrication,welding and two coats of synthetic enamel painting over a coats of red oxide after proper preparation of steel surface complete and fixing accessories etc to match with existing panel surface complete all as specified and directed. |
| 70 | M&L for spray painting on existing steel surface of Panel/FPB/JB etc with two coats of synthetic enamel paint including one coat of red oxide on rusted area after proper cleaning and prepration of old painted surfaces steel / Iron of any description with spray machine complete all as specified and directed.Note:- Painting of panels / feeder filler boxes shall be carried out in different colour of paints as required at site and as directed). |
| 71 | Excavating and relaying of cables loops near the poles, panels, distribution box, cutting the damages/burnt parts of cable and reconnecting in the same position with aluminium thimbles/lugs of same size of cable, nuts bolts and washer (made of stainless steel) with proper insulation and cable sleeves etc complete all as specified and directed.Note : (i) Cost of nuts, bolts, washer, aluminium thimble/Lugs, insulation tape shall be deemed to be included in the quoted rate.(ii) Cost of sleeves measured and paid separately on relevant items of the schedule. |
| 72 | M&L for repair/serviceing and comprehensive maintenance of Air Circuit breaker (ACB) of make(Make: L&T/Legrand/C&S/ABB/Schneider) andany capacityby disconnecting the breaker from existing position and detecting the fault, replacement the defective parts with new one and , commossioning and testing the following :- (a) Tripping coil, spring holder. (b) Push buttom. (c)Contactor (d) Trip coil Supervision(e) Aux switch (f)UVT Coil (g) Miss insertion preventer, (h) Control terminal protection cover(j) Mechanical interlock etc complete all as specified and directed by Engineer-in-Charge.Note :-(i) All other Spare parts shall be measured and paid separately under relevant items. |
| 73 | Supply only shunt triping coil for ACB capacity 630 Amp any make as per sample in existing size complete all as specified and directed. |
| 74 | Supplyonly shunt Closing coilfor ACB capacity 630 Amp any make as per sample of existing in site completeall as specified and directed. |
| 75 | Supplyonly push buttom for manually On and OFF the ACB anycapacity and any make as per sample of existing in site completeall as specified and directed. |
| 76 | S& Fin repair of copper spreader terminal Kitsuitable for MCCB capacity 63 to100 Amp of any make and as per existing MCCB at site complete all asspecified anddirected. |
| 77 | S& Fin repair of copper spreader terminal Kitsuitable for MCCB capacity 125- 200 Amp of any make and as per existing MCCB at site complete all asspecified anddirected. |
| 78 | S& Fin repair of copper spreader terminal Kitsuitable for MCCB capacity 200 to 320 Amp of any make and as per existing MCCB at site complete all asspecified anddirected. |
| 79 | S& Fin repair of copper spreader terminal Kitsuitable for MCCB capacity 400 Amp of any make and as per existing MCCB at site complete all asspecified anddirected. |
| 80 | M&L forPainting ofsteel polewith cross arms, clamp of any length and shape for LT overhead line with single coat of aluminium paint including preparation of the existing surface including marking pole numbers in a 20 cm dia black circle with white letter painting of 3 Nos black & 02 Nos yellow bands width 30 cm by fluorescent paint in alternate layers upto 1.5 mtr heightabove theP.C.Ccopingandtwocoatofaluminiumpaintbeyond 1.5 meterheightcomplete all as specified and directed. |
| 81 | Relaying of old serviceablebrick as in cable protection completeall as specified and directed. |
| 82 | Taking out old unserviceable under ground cable of any size and any position from trenches, floors and wall and segrate the serviceable portion cable for reuse complete all as specified and directed. |
| 83 | Labour for drillinghole under the road with the help of bocki / by manual or by machinefor crossing GI tubingof any size 100 mm pipefor cable protection complete all as specified and directed. |
| 84 | Relaying of serviceable cable of any size retrieved here-in-above item after detecting the fault and making straight through jointing kit of 1100volt grade complete all as specified and directed.Note:-Necessary excavation,returning filling, removal of soil and straight through joint shall be measured and paid separately under respective item of this schedule. |
| 85 | M & L for PCC earth pit chamber of internal dimension (300x300x300) mm and having wall thickness 100 mm using PCC 1:2:4 type B1 alongwith RCC 1:2:4 type B1 precast cover 50 mm thick reinforced with 8 mm TMT bars both way @100mm c/c including one lifting handle and dismantling of old one complete all as specified and directed. |
| 86 | Supply,laying & fixing double wall corrugated (DWC) pipes ofsize 63 mm outer dia and 50mm inner diamade of high density polythyline (HDPE) conforming to IS 16205(Part-24) in place of old Bricks including all accessories i.e. all type of joints, Sockets, Elbows, bends and End caps etc.. completeallas specified and directed. |
| 87 | Supply and fixing cable jointing kit for 1.1 KV grade cable for straight through joint complete with jointing material heat shrink type and accessories suitable for 3½core XLPE, armoured, Aluminium conductor cable of size 150 to 185 sqmm complete all as specified and as directed. |
| 88 | Supply and fixing cable jointing kit for 1.1 KV grade cable for straight through joint complete with jointing material heat shrink type and accessories suitable for 3½core XLPE, armoured, Aluminium conductor cable of size 70 to 120sqmm complete all as specified and as directed. |
| 89 | Supply and fixing cable jointing kit for 1.1 KV grade cable for straight through joint complete with jointing material heat shrink type and accessories suitable for 3½core XLPE, armoured, Aluminium conductor cable of size 25 to 50 sqmm complete all as specified and as directed. |
| 90 | Supply and fixing cable jointing kit for 1.1 KV grade cable for straight through joint complete with jointing material heat shrink type and accessories suitable for 4core XLPE, armoured, Aluminium conductor cable of size 6 to 16 sqmm complete all as specified and as directed. |
| 91 | S & F LT heat shrinkable type indoor/outdoor end termination cable jointing kit with jointing material and accessories suitable for 1100 volt (Earthed) grade 3½ core XLPE, armoured, Al conductor cable of size 240 to 300 sqmm,complete all as specified and directed. |
| 92 | S & F LT heat shrinkable type indoor/outdoor end termination cable jointing kit with jointing material and accessories suitable for 1100 volt (Earthed) grade 3½ core XLPE, armoured, Al conductor cable of size 150 to 185sqmm,complete all as specified and directed. |
| 93 | S & F LT heat shrinkable type indoor/outdoor end termination cable jointing kit with jointing material and accessories suitable for 1100 volt (Earthed) grade 3½ core XLPE, armoured, Al conductor cable of size 70 to 120 sqmm,complete all as specified and directed. |
| 94 | S & F LT heat shrinkable type indoor/outdoor end termination cable jointing kit with jointing material and accessories suitable for 1100 volt (Earthed) grade 3½ core XLPE, armoured, Al conductor cable of size 25 to 50 sqmm,complete all as specified and directed. |
| 95 | Supply and fixingLT cable sleeves with colour coding (Red, Yellow, Blue and Black ) suitable for 1100 volt grade 3 ½/4 core XLPE, armoured, aluminium conductor of cable size 10 sqmm to 25 sqmm all as specified and directed. |
| 96 | Supply and fixingLT cable sleeves with colour coding (Red, Yellow, Blue and Black ) suitable for 1100 volt grade 3 ½/4 core XLPE, armoured, aluminium conductor of cable size 35 sqmm to 50 sqmm all as specified and directed. |
| 97 | Supply and fixingLT cable sleeves with colour coding (Red, Yellow, Blue and Black ) suitable for 1100 volt grade 3 ½/4 core XLPE, armoured, aluminium conductor of cable size 70 sqmm to 95 sqmm all as specified and directed. |
| 98 | Supply and fixing in repairsingle Core 16 Sq mm multistranded PVC sheathedCopper cable FRLS to connecting the Distribution MCCB in busbar complete all as specified and directed. |
| 99 | Supply and fixing copper Lugs size 16 Sq mm complete all as specified and directed. |
| 100 | Supply and fixingcopper connector for connecting the all link copper cable in Busbar of panel complete all as specified and directed. |
| 101 | M&L for taking out and shifting the allLT Panel , Feeder Pillar Box, Junction Box not in proper ground space for workingand providing PCC (1:3:6) type C2 foundation of size 0.80m X 0.6m X 0.90m depth (0.30m below ground level and 0.60m above ground level ) and connections of all outgoing / incomming existing cable of any size drawing / digging out cable from loops in trenches inclusive of necessary excavation and earthwork as required and relaying the cables and commissioning the panelallasspecified and as directed.Note : No extra cost for PCC, Excavation of Looping cable should be paid to the contractor separately. |
| 102 | (Note : The Scope of Work contained in \"Sch of Credit\" amounting to Rs. 1,01,107.00 (refer Tender Srl Page No 29). The Quoted sum shall be arrived at after deducting the amount of “Sch of Credit” from the total amount of the ‘BoQ’ |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy