| 1 | Supply and fixing in replacement, test and commissioning in replacement of LT Panel board from CPRI approved panel manufacturermade out of of 2mm CRCA sheet cubical totally enclosed with frame made out of 50mm x 50mm x 6mmangle iron door front and back openable with locking arrangement indoor type vermin and weatherprooffloormounting type, suitable for 3 phase 4 wire,50 HZ , 415 Volt AC supply with 600A capacity copper bus bar (4 Nos) All MCCB shall be connected with suitable size of copper strip from main bus & with terminate point and complete wiring of panel board with suitable size PVC insulated multistranded copper conductor including lugs/thimbles etc suitable Cable alley with for provn of cable entries at bottom with cable glandsincluding the following :-(a) MCCB 4 pole, 415V,400Amps 50 KA - 02 No (incoming) thermo magnetic adjustable release type,ICS=ICU=100%(b) MCCB 4 pole,415V,250 Amps, 36 KA - 04 Nos (outgoing) thermo magnetic adjustable release type,ICS=ICU=100% ( c) Change over switch front open hand operated 400 Amp - 1 No.(d)Automatic star/Delta starters panel with all accessories mounting suitable for 75 HP-02 Nos.and 40 HP-02 Nos(e) Phase indicating lamps(RYB)-04 set(f) Digital panel meter for Amp,Volt,KWH, power factor and other parameter flush mounting of size 96X96mm-04 set.(g)Suitable CTs for main and for 04 starter panels.Note: before fabrication of panel, the contractor has to take approval from accepting officer on drawing. |
| 2 | Supply and fixing in replacement, commissioning and testing cubical type, factory made, CPRI approved, indoor type, LT panel box of suitable size, made of mild steel sheet of 3.15 mm thick, powder coated, dust & vermin proof, front double doors, compartmentalized, general construction confirming to IS: 8623 (Part 1): 1993, locking arrangements, floor mounted, suitable for 3 phase 4 wire 415 V, 50 Hz with 630 Amps rated copper bus bar (04 nos), including necessary foundation works mounting on angle iron frame made using angle iron 50 mm X 50 mm X 6 mm complete all as specified and as directed and shall be comprising the followings: - INCOMING: - (a) MCCB 400 Amps rated, 50 kA short circuit protection, 415 volts, 50 Hz, four pole, adjustable thermal & fixed magnetic setting- 1 No, (b) MCCB 250 Amps rated, 50 kA short circuit protection, 415 volts, 50 Hz, four pole, adjustable thermal & fixed magnetic setting- 1 No,(c) MCCB 125 Amps rated, 16 kA short circuit protection, 415 volts, 50 Hz, four pole, adjustable thermal & fixed magnetic setting- 2 No, (d) MCCB 63 Amps rated, 10 kA short circuit protection, 415 volts, 50 Hz, four pole, adjustable thermal & fixed magnetic setting- 3 No,(e) Soft starter with all accessories mounting suitable for 75HP- 01 Nos and 30 HP- 02 Nos (f) Ammeter (0 to 630 Amps), digital type with CTs and selector switch – 1 No, (g) Voltmeter (0 to 500 volts), digital type with selector switch, 415 volts, AC- 1No, (h) Indicator lamp RYB set- 4 Set(i) LT panel and soft starter connect and configurate with existing SCADA system |
| 3 | Supply and fixing in repair LED street light luminaire 60 watt made up of pressure die cast aluminium housing with toughened glass and high power LEDsand secondary lenses with IP-66 protection, Efficeincy : 110LM/W, 10 KV SPD included complete including making connections with copper wire 1.0 sqmm complete all as specified and directed. |
| 4 | Supply and fixingin replacement three phase off load change over switch with handle made out of sheet metal enclosure of capacity 400 Amps, 4 pole, side handle, 415 Volts, 50 Hz complete fixing on wall with grouting of base frame and suitable nut bolts all as specified and directed |
| 5 | Supply and fixing XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 3.5 core, 400 Sqmm fixing on wall with suitable saddles or under ground as required at site complete including lugs complete all as specified and directed. |
| 6 | Excavation in trenches not exc 1.5 mtr wide and not exc 1.5 mtr in depth for foundation, laying of HDPE pipe. and getting out in hard soil , complete all as specified and as directed . |
| 7 | Removing excavated material n exc. 50m and depositing where directed at a level n exc. 1.5 mabove the starting point |
| 8 | Returning & filling in, including spreading, levelling, watering & well ramming in layers not exc 25 cm as in soil complete all as specified & directed . |
| 9 | Supply and fixing HDPE Pipe of size 50 mm bore, complete all as specified and directed. |
| 10 | M&L for replacementof Earthing completely using Copper Bonded Rod of diameter more than 15mm and length of 10 feet below ground level .The material shall be low carbon high tensile copper bonded rods with 99.9 % of copper on the surface. pit shall be filled with highly conductive and eco friendly ground enhancing compound as per IEC 62561- 7 shall be not less than 30Kg per pit & PCC 1:3:6 Earth Pitchamber of size 310mm×300×170mm(W×L×H) with Cast iron covercomplete all as specified and directed |
| 11 | S&F in replacement Earth continuity conductor or main earthing lead of size 25× 4mm GI fixed to wall using insulated earth strip atevery 2 feet ditsance earthing strip shouldbe fixed from6th to ground floor and necessary termination with nuts and bolts complete all as specified and directed |
| 12 | Demolition of Exisiting concrete supporting block ofpumps and motor excedding 15cm of thickness aboveand below ground level all specfied and directed by Engineer-in-charge |
| 13 | M&L cement concrete 1:2:4, type B-2 (using 40 mm graded stone aggregate) as in support of Base frame with MSbolts placed in concrete andhardstanding finishing even and fair without using extra cement all as specified. Note: Location of bolts and size of bolts should macht the previous one |
| 14 | M& L for Disconnectingcentrifugal pump from motor, suction and delivery pipe line of any Make, model and taking down packingfor removing and insertion of new shaft sleeves or remove Bearing using bearing puller gear and fix new bearingsand greasing all parts, coupling pump to motor and check for proper shaft alignments such that no vibration produce during opertionof following capacity pumps, complete all as specfied and as directed by Engineer-in-charge. |
| 15 | Pump coupled with 75 HP motor (Bearing Size 6309-ZZ & 3309) |
| 16 | Pump coupled with 60 HP motor(Bearing Size 6308 ZZ & 3308) |
| 17 | Pump coupled with 50/40 HP motor(Bearing Size 6307 ZZ & 3307) |
| 18 | Pump coupled with 30/20 HP motor(Bearing Size 6306 ZZ & 3306) |
| 19 | M& L for Disconnecting motor frompump of any Make, model andremove Bearing using bearing puller gear and fix new bearingsat DE /NDE including necessary greasing ,check for proper shaft alignments such that no vibratiobn produce during opertion of following capacity Motors. |
| 20 | Pump coupled with 75 HP motor (Bearing size 6313-ZZ & 6312ZZ ) |
| 21 | Pump coupled with 60 HP motor (Bearing size 6312 ZZ & 6311ZZ ) |
| 22 | Pump coupled with 40 HP motor (Bearing size 6311 ZZ & 6308ZZ ) |
| 23 | Pump coupled with 15 HP motor(Bearing size 6307 ZZ & 6309ZZ ) |
| 24 | Pump coupled with 20 HP motor (Bearing size 6309 ZZ & 6308ZZ ) |
| 25 | S&F in repair AC-3type contactorwith control voltage of 230V AC with integrated auxillary or Add on block contacts with 1 or 2 No and NC including connection of control wiringto contactorand testing ofstarter after repairing . |
| 26 | Contactor rating of 115A |
| 27 | Contactor rating of 75A |
| 28 | Contactor rating of 65A |
| 29 | Contactor rating of 40A |
| 30 | Contactor rating of 32A |
| 31 | Contactor rating of 22A |
| 32 | Contactor rating of 18A |
| 33 | S&F in repair Thermal over load relay with adjustablesetting with integrated auxillary or Add on block contacts with 1 or 2 No and NC including connection of control wiringto OLR and testing ofstarter after repairing . |
| 34 | OLR of capacity I Min of 45 to I max 65A |
| 35 | OLR of capacity I Min of 34 to I max 50A |
| 36 | OLR of capacity I Min of 20 to I max 32A |
| 37 | OLR of capacity I Min of 12 to I max 18A |
| 38 | OLR of capacity I Min of 08 to I max 12A |
| 39 | S&F in replacement self lubricated asbestoes non metallic and non graphite gland packing white colour of sizes 8 to 12 mm complete all as specified and directed Make : Champion or techno and commercial equivalent |
| 40 | M&L for replacement of MSjaw coupling type-L withspider made of synthetic rubber or gear coupled type of suitable for 75 HP motor |
| 41 | M&L for replacement of MSjaw coupling type-L withspider made of synthetic rubber or gear coupled type of suitable for 60 HP motor |
| 42 | M&L for replacement of MSjaw coupling type-L withspider made of synthetic rubber or gear coupled type of suitable for 40 HP motor |
| 43 | M&L for replacement of MSjaw coupling type-L withspider made of synthetic rubber or gear coupled type of suitable for 15/20 HP motor |
| 44 | 26. M&L for Disconnecting motor power cables of various sizes from electrical motor of different capacities and decoupling from thepump sets,removing and taking down carefully and transporting to authorised workshop ,Dismantaling stator and rotor carefully andrewinding stator assembly with supper enamelled copper windingwire of suitable gauge matching to existing gaugeand cleaning of slots ,core with carbon tetra chloride solution and apply two coats of insulation varnish and keep stator assembly in heating chamber to improve insulation strength ,reassemble motor completey and transporation to site ,coupling pump to motor and check for proper shaft alignments such that no vibratiobn produce during opertioncoupling to pump with exact allinment ,connect power cables to motor and testing of following capacity motor |
| 45 | 75HP |
| 46 | 60 HP |
| 47 | 40 HP |
| 48 | 20/15 HP |
| 49 | S&F in repair and replacemnt of MCCBof following capacity including disconnecting the cable, replacement of burntout lugs, spreaders of suitable size including nuts and bolts andfixing to existing panelincluding necessary alternation to existing busbar and panel all as specfied and directed by Enginner-in-charge :- |
| 50 | MCCB of 630A,Breaking capacity 50KA,4P with adjustable thermal magnetic setting Ics=Icu=100% |
| 51 | MCCB of 400A,Breaking capacity 50KA,4P with adjustable thermal magnetic setting Ics=Icu=100% |
| 52 | MCCB of 320/350A,Breaking capacity 50KA,4P with adjustable thermal magnetic setting Ics=Icu=100% |
| 53 | MCCB of 250 A,Breaking capacity 36KA,4P with adjustable thermal magnetic setting Ics=Icu=100% |
| 54 | MCCB of 200 A,Breaking capacity 36KA,4P with adjustable thermal magnetic setting Ics=Icu=100% |
| 55 | MCCB of 125 A,Breaking capacity 16KA,3P fixed type |
| 56 | MCCB of25A to 100A,Breaking capacity 16 KA , 3P fixed type |
| 57 | MCCB of 250 A,Breaking capacity 36KA,3P with adjustable thermal magnetic setting Ics=Icu=100% |
| 58 | MCCB of 200A,Breaking capacity 36KA,3Pwith adjustable thermal magnetic setting Ics=Icu=100% |
| 59 | S&F in repair and replacemnt ofburnout aluminiumspreaders incoming or outgoingof followingsize including nuts and bolts all as specfied and directed by Enginner-in-charge |
| 60 | 250A 4P |
| 61 | 250A 3P |
| 62 | 400A 3P |
| 63 | S & F in repair pressure gauge 150mm dia range 0-10Kg /Sqcm. Note: quoted rated should includingfor providingof adopter /Ferrule/check nut etc required for fixing pressure guage and necessary alterations including necessary welding to MS or CI pipe fortaping if required. |
| 64 | Supply and laying in replacement of copper unamoured power cable of size 25sqmmfrom motor starter panel to motor including HDPE pipe in ground/walls with all fittings complete all as directed. |
| 65 | Supply and laying in replacement of copper unamoured power cable of size 35sqmmfrom motor starter panel to motor including HDPE pipein ground/walls with all fittings complete all as directed. |
| 66 | Supply and laying in replacement of copper unamoured power cable of size 50 sqmmfrom motor starter panel to motor including HDPE pipein ground/walls with all fittings complete all as directed. |
| 67 | Material and labour for bacteriological and chemical analysis of water sample at govt approved lab (Iso 9001:2008)including collecting sample from pumphouse using labedownedsample jar and testing every month all directed and specfied by Enginner-in-charge |
| 68 | Supply and Lay in repair LTXLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 4 Core x 10 Sqmm complete all as specified and directed.Note : 1. The cost of Al thimbles/lugs and cable gland etc is including in the quoted rate and no extra payment will be made for it. 2. The excavation, earth work, sand cushioning and brick protection etc will be measured and paid separately under respective items. |
| 69 | S & F in repair looping box of size 130mm x 130mmx77mm weather proof IP66/67including connector blocks four way having suitable size bolt to connect upto 6sqmm x 2 core cable two Nos with the help of suitable gland, thimble nuts, washers supports by flat aluminium clamps not less than 25 mm x 3mm with suitable size nuts, bolts and washers inside and outside looping box including fixing with electric pole and taking out old one of any type complete as directed. Make : Hansel , Cat ref : KF3535G. or equivalent make as approved by Engr-in-charge. |
| 70 | Scrapping of paint complete pump and motor, base frame and accessories complete including making new synthetic enamel paint of two coats over a coat of red oxide primer of motor of capacity 15 HP to 75 HP complete all as specified and directed. |
| 71 | Supply and fixing in repair fabrication of Iron frames size and thickness as per existing on site including nut bolts, washers , two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed. |
| 72 | Supply and fixing in repair rubber vibration pads heavy dutyfor base frame as per sample suitable for the following size of pumpsets:- |
| 73 | 50 to 75 HP |
| 74 | 30 to 40 HP |
| 75 | 15 to 25 HP |
| 76 | Cutting cast iron pipes/DI pipes and reducing to required length before laying in position forinsertion of new tees, branches, for the following sizes :- |
| 77 | 150 mm bore |
| 78 | 200 mm bore |
| 79 | 300 mm bore |
| 80 | Supply and fixing in repair DI/CI Bends (any type, radius and angle) tapers any type, (straight, bend, increasing, decreasing or double socket etc.) Tee pieces single branch. \"Y\" junction, double branch, cross (all sockets or socket and spigot) collars, caps and plugs complete any type of fittings up to 150 mm bore |
| 81 | Supply and fixing in repair DI/CI Bends (any type, radius and angle) tapers any type, (straight, bend, increasing, decreasing or double socket etc.) Tee pieces single branch. \"Y\" junction, double branch, cross (all sockets or socket and spigot) collars, caps and plugs complete any type of fittings 200 mm to 300 mm bore. |
| 82 | Supply and laying in replacement of spigot and socket ductile iron water tubing having cement mortar lining on inner surface and one coat of bituminous paint over exposed surface ISI marked, IS No. 8329:2000, including rubber joint of suitable size, class K-9 laid on wall/roof/floor/trenches with proper alignment as per site requirement and carryout testing against leakage before filling the trenches etc complete all as specified and directed. |
| 83 | 150 mm bore |
| 84 | 200mm bore |
| 85 | 300mm bore |