Tender For Provision Of Of One (01) High Mast Light At Residential Complex At Diber Haldwani.; 1 Contract Details 2 Supply& erection ,testing and commissioning of galvanised 16M high mast pole in two section suitable for 47 m/sec wind speed along with head frame, luminaires carriage suitable for 08 luminaires in symmetrical arrangement alongwith raising lowering system comprising double drum winch, 5mm diameter SS wire rope, trailing cable, connector,LED type single dome aviation obstruction light with polycorbonate enclosure type BGAV302 , integral power tool motor,manual handle, junction box, lightning finial , Wiring material from Junction box to individual luminaire & MCB in base compartment ,foundation bolts manufactured from special steel along with nuts, washers, anchor plate and common template including outdoor stand mounted feeder pillar with 32A TPN MCB incomer, single dial time switch, 25A TP contactor for the automatic switching of luminaries, power tool control with 2 no 9A contactors and raise lower push button, Incoming 25 sq. mm and out going 16 & 2.5 sq. mm terminals incuding construction of foundation with M20 grade concrete for the highmast considering the safe soil bearing capacity at site as 10 T/sqmtr at 2 metre depth with all materials and labour alongwith erection of the high mast with the help of suitable tools and plants, wiring of luminaires with all wiring materials like PVC insulated PVC sheathed flexible cable of suitable copper conductor cores of 1.5 sq. mm, lugs, MCB and all labour(the cost of wiring material from Junction box to individual luminaire & MCB in base compartment are included in qouted rate) . Note:-Foundation for 16 mtr High mast pole as per manufacture design and recommendation. 3 S&F LED Flood light fitting 200 Watt, with surge protection 4KV inbuilt in driver and minimum 10 KV separate, IP66 having Pressure dia cast aluminum housing with heat resistant toughened glass, individual LED lenses complete making connection with suitable in size of wire. (i) The driver should be potted ant vibration type system lumen efficiency should be 140 lumen/Watt. Make: Bajaj cat part no.PRAZE F 280L WH NB-A5 TG SD or equivalent of havells/ crompton. 4 Supply, installation, commissioning and testing LT panel board cubical outdoortype floor mounted, factory made 3.15mm MS sheet, conforming to IP-54, with front and back hinges door with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof and painted powder coated including 200 Amp rated Aluminium bus bar 3 phase 4 wire system and wiring with suitable size of copper cablecomprising and suitable foundation & following accessories :- Incoming (a) MCCB 63 Amps 16 KA4 pole 415 volt with TMR fixed type -01 nos (b) Digital Voltmeter 0-500Vwith selector switch-01 No (c ) Digital Ammeter0-200A CT ratio type with selector switch and 3 Nos of CTs 100/5 (d) Phase indicator lamp LED typeRYB-01 set . Outgoing- (a) MCB TPN 32 Amps -2 NOS (b) Sparespace for MCB TPN 40 Amp -01 No (c) MCB SPN 32 Amps -1 NOS (d) PCC foundation ( 1:2:4) grading(1.5x1.5x0.5) CUM (e) Supply and fix time switches 415V three phase of 20 amps rating with contactor fitted inside steel enclosure.Nos- 1 (Note:Cable glands should be provided for all incoming /outgoing connections.) 5 Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25.0 sq mm 4 core complete all as specified and directed. Make ; Havells/gloster/polycab 6 Material & Labour of Earthing complete with copperearth plate electrode 60×60cm.× 3.15mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to copper earth strip 20X 3 mm as earth lead in 40 mm dia GI light grade protection pipe including charcoal, salt,bolts, nuts, check nuts and washers of copper all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion 7 Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtr depth for taking out/for laying under ground cables/pipes etc and getting out any type soil all as dircted 8 Returning filling in including spreading, levelling, watering and well ramming in layers n-exc 25 cm 9 Removing excavated soil to a distance n-exc 50 mtr and depositing where directed at a level n-exc 1.5 mtr above the starting point 10 Supply and laying common burnt clay building bricks sub class B designation 75 old size bricks for cable protection 11 Supply and spreading fine river sand in trenches for cushioning of under ground cable/filling cable ducts all as directedby Engr-in-Charge at site Note : - Only punned thickness shall be measured for payment purpose 12 M&L Boring of holes (manually) under road , hard standing without damaging the surface for 50 mm bore GI Pipe. NOTE:- (i) Depth of hole shall be 1 Metre below the top surface of Road / hard standing. 13 M&L for GI tubing 50 mm dia light grade with all necessary fittings laid in trenches flxed to walls, poles, under road/floor etc for cable protection complete allas specified and directed.