| 1 | Supply, installing, testing and commissioning of LT out door type factory made (CPRI Approved) , Feeder pillar box(KIOSK) of size 750mmX600mmX500mm (over all dimension ) with mild steel angle iron of size 40X40X5mm vertical frameand legs with mild steel flat iron 40X6 mm in horizontal sides of the Panel, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15mm CRCA sheet and 40x40x5 mm thick angle iron frame work,powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside,front & back opening type, with holes for cable entry with cable glands and fixing danger notice plate made of 1.6mm thick mild steel sheet, vitreous enamelled white, of size 20 x 15cm with letter, figures and conventional skull bones in signal red colour and fixed front & back doorpillar box etc with voltage and danger indicated in Hindi and English complete all as specified and directed. With double door shutter and providing suitable locking arrangement. Aluminium bus bar of 700 Amps rating, including color coded insulation as per IS with drill hole 8 way for incoming/outgoing including aluminium lugs, GI bolts, Nuts and washers of suitable size. Installed on Porcelain / synthetic bridge insulators, heavy duty with necessary steel / GI screws, bolts, nuts and washers -08 Nos, including indicator switches with suitable control wiring complete all as specified and as directed. The platform shall be such that it is of a height 45 cm above the nearest road level. complete all as specified and directed including connections of all out going/in coming existing cables of size 25/35/50/95/120/ 150 Sqmm by drawing /digging out cable from |
| 2 | loops in trenches outside the Bldg inclusive of necessary excavation and earth work as required and relaying the cables with retrieved bricks and providing new sand cushioning and crimping suitable size copper lugs for terminal connections of cables, necessary brick foundation with plastering to the Panel boardcomplete all as specified and as directed Engr-in-Charge. Note :- All types of certificates and design verification with switch gears (ACB/MCCB)confirming to IS/IEC 61439/2011 Part - I & II with short circuit test 4000 A with breaking capacity 65KA shall be submitted by the contractor before execution of work. |
| 3 | Supply, installing, testing and commissioning of LT out door type factory made (CPRI Approved), LT feeder pillar box (KIOSK) of size 900mmX600mmX500mm (over all dimension ) with mild steel angle iron of size 40X40X5mm vertical frameand legs with mild steel flat iron 40X6 mm in horizontal sides of the frame, outdoor type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15mm CRCA sheet outerbody, innerside 2.00 mm thick and 40x40x5 mm thick angle iron frame work,powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside,front & back opening type, with drill holes for cable entry including suitable cable glands, andfixing danger notice plate made of 1.6mm thick mild steel sheet, vitreous enameled white, of size 20 x 15cm with letter, figures and conventional skull bones in signal red colour and fixed front & back door pillar box etc with voltage and danger indiated in Hindi and English complete all as specified and directed with double door shutter including suitable locking arrangement with MCCB 4 pole, 415 volts AC grade, 200Amps rating and 25 KA rupturing capacity -01 No(Make : Siemens: / L&T & Equivalent Schneider ) .Aluminium bus bar of 300 Amps ,including color coded insulation as per IS with drilled holes for incoming /out going cable core connection including aluminium lugs ,GI bolts ,Nuts and washers of suitable size installed on Porcelain / syntheticbridge insulators, heavy duty with necessary steel / GIscrews ,bolts, nuts and washers -08 Nos, Porcelain / Bakelite rewirable type fuse carrier of capacity 32 Amps- 10 Nos ,including indicator switches with suitable control wiring complete all |
| 4 | as specified and as directed., Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class `B’, old sizebricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for Junction box. The platform shall be such that it is of a height 45 cm above the nearest road level. complete all as specified and directed.Note :- All types of certificates and design verification with switch gears (ACB/MCCB)confirming to IS/IEC 61439/2011 Part - I & II with short circuit test 4000 A with breaking capacity 65KA shall be submitted by the contractor before execution of work. |
| 5 | Supply, installing, testing and commissioning, factory made and tested .LT panel(KIOSK) 1500mm x1200x 600mm size, outdoor type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminum bus bars 600Amps . including color coded insulation as per IS rating installed on porcelain insulators. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15mm CRCA sheet and 40x40x4mm thick angle iron frame work,powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside,front opening type, with holes for cable entry with cable glands,andfixing danger notice plate made of 1.6mm thick mild steel sheet, vitreous enameled white, of size 20 x 15cm with letter, figures and conventional skull bones in signal red colour and fixed front & back door LT panel etc with voltage and danger indiated in Hindi and English with double door shutter and locking arrangement (including provn of 65mm Godrej (Freedom) stranded lock with 2 keys,internal wiring with PVC insulated,stranded copper conductor, FRLS cables, IS-694marked of adequate size but not less than 4 Sqmm.including indicator switches The platform shall be such that it is of a height 45 cm above the nearest road level. complete all as specified and directed including connections of all out going/in coming existing cables of size 25/35/50/95/120/ 150 sqmm by drawing /digging out cable from loops in trenches out side the Bldg inclusive of necessary excavation and earth work as required and relaying the cables with retrieved bricks and providing new sand cushioning and crimping suitable size copper lugs for terminal connections of cables, necessary brick foundation with plastering to |
| 6 | the Panel board,All out going feeders shall be connected by cable through suitable size gland plate / glands.& The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint and taking out of old skelton type panel with control switches complete all as specified and as directed Engr-in-Charge , The scope of work includes the following:- |
| 7 | (I) Incoming :- |
| 8 | (i)MCCB 4 Pole, Tharmal Magnetic adjustable type 400A, Breaking capacity 36 KA, 415 V, 50 Hzwith OL, SC, protection, -01 Nos along with Spreader terminals (Make : Siemens: / L&T & Equivalent Schneider ) |
| 9 | (ii) Digital Amps/volt /PF meter 0-500 volts with selector switch - 01 No (Make: Siemens/ Schneider/ legrand /AE/SELEC) |
| 10 | (iii) Indicator lamp LED type (R, Y, B) complete with fuse -01 Set(Make: Siemens/ Schneider /legrand /AE/SELEC) |
| 11 | (II) Outgoing :- |
| 12 | (i) MCCB 4 Pole, Thermal MagneticBased adjustable type 200A, Breaking capacity 25 KA, 415 V, 50 Hzwith OL, SC, protection, -02 Nos along with Spreader terminals |
| 13 | (ii) MCCB 4 Pole, Thermal MagneticBased adjustable type 100A, Breaking capacity 16 KA, 415 V, 50 Hzwith OL, SC, protection, -02 Nos along with Spreader terminals for location |
| 14 | (iii) MCB TPN 32 Amp 10 KA C-Curve - 1No(Make-Schneider / Legrand L&T ) |
| 15 | NOTE:- All types of certificates and design verification with switch gears (ACB/MCCB)confirming to IS/IEC 61439/2011 Part - I & II with short circuit test 4000 A with breaking capacity 65KA shall be submitted by the contractor before execution of work. |
| 16 | All as per Srl item No 3 here-in-before completebut Size 1500x1200x600 mm and Bus bar 900 Amps rating |
| 17 | (I) Incoming :- |
| 18 | (i)MCCB 4 Pole, Tharmal Magnetic adjustable type 600A, Breaking capacity 36 KA, 415 V, 50 Hzwith OL, SC, protection, -01 Nos along with Spreader terminals (Make : Siemens : / L&T & Equivalent Schneider) |
| 19 | (ii) Digital Amps/volt /PF meter 0-500 volts with selector switch - 01 No (Make: Siemens/Schneider/legrand /AE/SELEC) |
| 20 | (iii) Indicator lamp LED type (R, Y, B) complete with fuse -01 Set(Make: Siemens/ Schneider/legrand /AE/SELEC) |
| 21 | (II) Outgoing :- |
| 22 | (i) MCCB 4 Pole, Thermal MagneticBased adjustable type 250 A, Breaking capacity 25 KA, 415 V, 50 Hzwith OL, SC, protection, -1 Nos along with Spreader terminals |
| 23 | (ii) MCCB 4 Pole, Thermal MagneticBased adjustable type 200A, Breaking capacity 25KA, 415 V, 50 Hzwith OL, SC, protection, -2 Nos along with Spreader terminals |
| 24 | (iii) MCCB 4 Pole, Thermal MagneticBased adjustable type 100A, Breaking capacity 16 KA, 415 V, 50 Hzwith OL, SC, protection, -2 Nos along with Spreader terminals |
| 25 | (iv) MCB TPN 40 Amp 10 KA C-Curve - 2 No(Make-Schneider / Legrand L&T ) |
| 26 | NOTE:- all types of certificates and design verification with switch gears (ACB/MCCB)confirming to IS/IEC 61439/2011 Part - I & II with short circuit test 4000 A with breaking capacity 65KA shall be submitted by the contractor before execution of work. |
| 27 | All as per Srl item No 3 here-in-before Completebut Size 1600 x1000x600 mm and Busbar 950 Amps rating |
| 28 | (I) Incoming :- |
| 29 | (i)MCCB 4 Pole, Tharmal Magnetic adjustable type 630A, Breaking capacity 36 KA, 415 V, 50 Hzwith OL, SC, protection, -01 Nos along with Spreader terminals (Make : Siemens: / L&T & Equivalent Schneider ) |
| 30 | (ii) Digital Amps/volt /PF meter 0-500 volts with selector switch - 01 No (Make: Siemens/Schneider/legrand /AE/SELEC) |
| 31 | (iii) Indicator lamp LED type (R, Y, B) complete with fuse -01 Set(Make: Siemens/Schneider/legrand /AE/SELEC) |
| 32 | (II) Outgoing :- |
| 33 | (i) MCCB 4 Pole, Thermal MagneticBased adjustable type 250 A, Breaking capacity 25 KA, 415 V, 50 Hzwith OL, SC, protection, -01 Nos along with Spreader terminals |
| 34 | (ii) MCCB 4 Pole, Thermal MagneticBased adjustable type 200 A, Breaking capacity 25 KA, 415 V, 50 Hzwith OL, SC, protection, -01 Nos along with Spreader terminals |
| 35 | (iii) MCCB 4 Pole, Thermal MagneticBased adjustable type 100A, Breaking capacity 16 KA, 415 V, 50 Hzwith OL, SC, protection, -04 Nos along with Spreader terminals |
| 36 | (iv) MCB TPN 40 Amp 10 KA C-Curve - 02 Nos(Make-Schneider / Legrand L&T ) |
| 37 | NOTE:- all types of certificates and design verification with switch gears (ACB/MCCB)confirming to IS/IEC 61439/2011 Part - I & II with short circuit test 4000 A with breaking capacity 65KA shall be submitted by the contractor before execution of work. |
| 38 | All as per Srl item No 3 here-in-before Completebut Size 1500 x1200x600 mm and Busbar 900 Amps rating |
| 39 | (I) Incoming :- |
| 40 | (i)MCCB 4 Pole, Tharmal Magnetic 600A, Breaking capacity 36 KA, 415 V, 50 Hzwith OL, SC, protection, -01 Nos along with Spreader terminals (Make : Siemens: / L&T & Equivalent Schneider ) |
| 41 | (ii) Digital Amps/volt /PF meter 0-500 volts with selector switch - 01 No (Make: Siemens/Schneider/legrand /AE/SELEC) |
| 42 | (iii) Indicator lamp LED type (R, Y, B) complete with fuse -01 Set(Make: Siemens/Schneider/legrand /AE/SELEC) |
| 43 | (II) Outgoing :- |
| 44 | (i) MCCB 4 Pole, Thermal MagneticBased adjustable type 200 A, Breaking capacity 25 KA, 415 V, 50 Hzwith OL, SC, protection, -2 Nos along with Spreader terminals |
| 45 | (ii) MCCB 4 Pole, Thermal MagneticBased adjustable type160A, Breaking capacity 16 KA, 415 V, 50 Hzwith OL, SC, protection, -01 Nos along with Spreader terminals |
| 46 | (ii) MCCB 4 Pole, Thermal MagneticBased adjustable type 100A, Breaking capacity 16 KA, 415 V, 50 Hzwith OL, SC, protection, -01 Nos along with Spreader terminals |
| 47 | (iii) MCB TPN 63 Amp 10 KA C-Curve - 2 Nos(Make-Schneider / Legrand L&T ) |
| 48 | (iv) MCB TPN 40 Amp 10 KA C-Curve - 2 Nos(Make-Schneider / Legrand L&T ) |
| 49 | NOTE:- All types of certificates and design verification with switch gears (ACB/MCCB)confirming to IS/IEC 61439/2011 Part - I & II with short circuit test 4000 A with breaking capacity 65KA shall be submitted by the contractor before execution of work. |
| 50 | M&Lof plate earthing for sub station equipments complete with galvanisedmild steel plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground vertically (in earth pit not less than3.5m below normal ground level) with the top edge of the earth plate at a depth not less than 2.75m below normal ground level,the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides and incl GI earth strip 32 x 6 mm bolted (with GI nuts, bolts & check nuts) and riveted to earth plate at one end and connected to metallic bodies of LT equipments etc at the other, earth strip encased in and including 40mm boreGIlight grade pipe with all fittings from top of electrode to body of equipment fixed with and including 25 x 3mm flat iron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI pipe medium grade from bottom of earth pit to top of electrode complete with earth pit in PCC 1:2:4 type B-O using 12 mm graded crushed stone aggregateexcavation & earth work and RCCcover complete all specified and shown in electrical plate No 5 of SSR Pt-I. |
| 51 | Supply, laying, jointing, testing and commissioning LT underground cables, 1100 volts grade, XLPE insulated and PVC sheathed, heavy duty armoured, with multistranded aluminium conductors, IS-7098 (marked, laid in trenches / ducts / fixed on poles / walls / laid under roads / paths / drain / culverts or encased in GI pipe complete all as specified and directed. Cables of the following sizes:-(Note;- (i) Rate quotted includes terminal Lugs /road cutting/ wall cutting/ floor cuttingand making good damged portion matching with existing surface with all existing finishes.(ii)Excavation andearth work, sand cushioning, brick cover and protection pipe etc. shall be measured and paid for separately.) |
| 52 | 10 Sqmm 4 core |
| 53 | 25 Sqmm 4core |
| 54 | 35 Sqmm 3.5 core |
| 55 | 50 Sqmm 3.5 core |
| 56 | 70 Sqmm 3.5 core |
| 57 | 95 Sqmm 3.5 core |
| 58 | 120 Sqmm 3.5 core |
| 59 | 150Sqmm 3.5 core |
| 60 | 185 Sqmm 3.5 core |
| 61 | 240 Sqmm 3.5 core |
| 62 | 300 Sqmm 3.5 core |
| 63 | M&L for boring of holes under road , pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed. |
| 64 | Supplying and fixing STRAIGHT THROUGH cable jointing Kit for 1100 V grade cable forcomplete with jointing material ( heat shrink type) and accessories suitable XLPE armoured aluminium conductor cable and testing aftre jointing complete all as specified and directed the following size :- |
| 65 | for cable of size 25 sqmm x 04 core to 50 sqmm x 3.5 core |
| 66 | for cable of size 70 sqmm x 3.5 core to 95 sq mm x 3.5 core |
| 67 | for cable of size 120 sqmm x 3.5 core to 150 sq mm x 3.5 core |
| 68 | for cable of size 185 sqmm x 3.5 core to 240 sq mm x 3.5 core |
| 69 | M&L Cutting of worn-out / burnt aluminium cable terminal lugs from the LT cable , crimping of new aluminium cable core and fixing with transformer/ Panel MCCB terminal/ FPB/ JB/ pole/DBs/ stud including cutting/ dressing of cable, disconnecting under ground / OH line cable conductor , cutting down worn-out portion and refixing with suitable lugs complete, includingunder ground cables of any type and size for repairs including taking out underground cable loop from ground and making connections of restoration of electric supply complete all as specified and directed Engr-in-Charge . Note:-Excavation, earth work , taking out cable protection covers, and sand cushion and relaying the same shall be deemed included in the unit rate quoted by Contractor. |
| 70 | S&F pole mounting type junction box factory made of size 350x250x150mm of FRP sheet duly powder coated with front openable hinged door, locking arrangements, with 4 Nos aluminium bus bars 40 Amps ratingmounted on porcelain insulator, cable glands and lugsconsistingDP 6 Amps \"C\" series(Make of MCB :Legrand / C&S / ABB) ,mounted on MCB rail -01 no. including mild steel flat iron clamp made out of 40x4mm FI, nuts, bolts and washers duly painted with two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified Engr-in- Charge. |
| 71 | Supply& fixing 1.5 Sqmm three core (nominal area) PVC insulated and PVC sheathed multi stranded unarmoured Copper conductor cable LT 1100 volt grade FRLS drawn throughpolefor connecting to street light and pole JBs with cable terminal(MAKE:HAVELLS, FINOLEX, MESCAB, KEI) pole wirings connecting up with streetlight feeder(Junction box) complete all as Specified and directed Engr -in -Charge |
| 72 | S&Fservice main distribution (SMC JUNCTION BOX ) box minimum inside size 395 x 235 x 150 mm with Bus bar 200 amps 4 pole for distribution of multiple nos of service connection, (ISI marked )weather and moisture-proof, nuts and bolted bus bar system, 200 Amps capacity and fixing on pole/wall with suitable FI clamp nuts and bolt complete all as specified and directed. (Make : Mahendra/ Sintex and equivalent ) |
| 73 | Excavation in trenches in soft/loose soil n.exc 1.5m wide and n. exc 1.5m depth for laying of cable, errection of poles, stay andpipe line,and getting out complete all as specified and directed |
| 74 | Returning & filling including spreading, leveling watering and well ramming in layers n. exc 25 cm thick in any type of soil complete all as specified. |
| 75 | Removal of excavated soil to a distance n. exc 50 m above the starting point complete all as specified. |
| 76 | M&Lfly ash old size bricks, straight or curved on plan , laid flat with width equal to length of brick , laid dry over electric cable for protection all as specified. |
| 77 | M & L for local sand coushioning with dry and clean over and under the cable for protection of cable , 80 mm sand laid before laying the cable 150 mm sand after laying the cable and then punned. After punning thickness of sand cushioning shall be 18 cm and filling the sand in cable duct of inside the sub station building complete all as specified and directed. Note :- Only punned thickness of sand shall be measured for payment. |
| 78 | Material and labour for GI tubing light grade 100 mm bore for passing through cables, laid in treanches, under the floor, along the wall or along the pole with necessary clamps, nuts, bolts and washers etc. and making good disturbed surface of wall, floor etc complete all as specified and directed . |
| 79 | Material and labour for GI tubing light grade 80 mm bore for passing through cables, laid in treanches, under the floor, along the wall or along the pole with necessary clamps, nuts, bolts and washers etc. and making good disturbed surface of wall, floor etc complete all as specified and directed . |
| 80 | Material and labour for GI tubing light grade 50 mm bore for passing through cables, laid in treanches, under the floor, along the wall or along the pole with necessary clamps, nuts, bolts and washers etc. and making good disturbed surface of wall, floor etc complete all as specified and directed . |
| 81 | Material and labour for GI tubing light grade 40 mm bore for passing through cables, laid in treanches, under the floor, along the wall or along the pole with necessary clamps, nuts, bolts and washers etc. and making good disturbed surface of wall, floor etc complete all as specified and directed . |
| 82 | M&L for auguring of hole suitable for passing 40mm to 100mmbore pipe in true horizontal position under road, PCC paths etc., by means of mechanical ring/ auger after doing ultrasound to prevent any damage to existing cables pipe line specified and directed coming in the route not exceeding 1.5 m in depth below existing surface level of road and not excd 30M in length complete all as specified. Note: Pipe shall be measured and paid separately under appropriate items and any damage to existing cables of anytype shall be made good by the Bidder without any extra cost to department. |
| 83 | Supplying & fixingin repair LED street light fitting 70 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 66 protection complete. complete all as specified and directed. Make Polycab/Bajaj/Phillips |
| 84 | Dismantling old existing ACSR conductor of any type/size complete all as specified and directed. |
| 85 | Dismantling old existing MS cross arms of any type/shape complete all as specified and directed. |
| 86 | Dismantling old existing Insulators of any type/shape complete all as specified and directed. |
| 87 | Dismantling old existing LT stay complete all as specified and directed. |