| 1 | Supply , laying,jointing, testing and commissioningin replacement of LT underground cable, 1100 volts grade, XLPE insulated and PVC sheathed, armoured heavy duty with multistrand aluminium conductors IS-7098, laid in trenches /fixed on wall /floor /road /culverts /pole or encased cable of size 95 sqmm 3.5 core, including taking out old us cable complete all as specified. |
| 2 | All as per item No 1.00 (here-in-before) but 35 Sqmm 3.5 core. |
| 3 | Excavation in trenches not exc 1.5m wide and not exc 1.5m in depth for laying of cable etc, and for foundation of poles, stays etc. not exc 10sqm on plan and getting out in soft / loose soil complete all as specified and directed. |
| 4 | Supply and laying double wall corrugated pipe (DWC) in replacement conforming to IS 19430 Part - I of size 120mm outer dia and 103.5 mm inner dia complete all as specified and as directed |
| 5 | Supply and laying double wall corrugated pipe (DWC) in replacement conforming to IS 19430 Part - I of size 50mm outer dia and 38 mm inner dia complete all as specified and as directed |
| 6 | M&L for returning filling in approved excavated soil including spreading levelling and well ramming in layers n.exc 25cm thick complete all as specified and directed. |
| 7 | M&L for removing surplus soil to a distance not exceeding 50 m & depositing at a level not exceeding 1.5 m above the starting point complete all as specified and directed. |
| 8 | Demolition of path /concrete in ground floors and pavings (below or above ground level) .complete all as specified and as directed. Note : The rate inclusive of taking down and refixing of any type of cheqered tiles, interlocking tiles complete as per existing for good make. |
| 9 | M/L for cement concrete type B-2, 1:2:4 (40mm graded aggregate) complete all as specified and as directed. |
| 10 | Boring of hole under road/pavement/hard standing or any other situation by mannual means and suitable for passing of GI pipe 100 mm bore and making good both ends all specified and directed |
| 11 | Supply, installation, commissioning and testing of LT Panel out door type,LT 415 Volts, 50 Hz , 3-phase, 4 wire supply, size of LT panel not less than 1.5 m high x 2.5 m width x 0.7 m depth CPRI approved/tested, factory assembled ,out door type,weather and vermin proof (Protection Class IP-54) made out of3.15 mm (for external) and 2.00 mm (for internal) thickMS Sheet CRCA sheet with both side (front and back) hinged, double door opening for external, rubber lining, locking arrangement, painted internally and externally with powder coating of grey shade (RAL-7032) as per seven tank process completemounted on angle iron 65mm x 65mm x 6 mm legs 45 cm high above GL and 15 cmembedded in ground with and including blocks of PCC 1:2:4 type C1 of block size 30x30x30 cm comprising of the following. (a) Bus bar chamber having 4 nos air insulated Aluminium strip bus bars of rating not less than the 1.5 times the rated capacity of theincomer ACB/MCCB, bus bar must be colour coded heat shrinkable as well as outgoings shall have aluminium four pole(bus bar) of current carrying capacity not less than 1.5 times the rated capacity of individual MCCBs.:- Contd/-............ |
| 12 | (a) INCOMING :- (i)MCCB 4 pole , LT 415 Volts, 50 Hz ACgradeof 400Amps rating36 KArupturingcapacitiy with Adjustable Thermal and Fixed Magnetic setting - 01 No. (ii) Voltmeter 0-500 V digital type with 3 way rotary selector switch - 01 No (iii) Ammeter 0-400 Amp digital type with 3 way rotary selector switch - 01 No(iv) Indicating lamp one set of three (v) CT of suitable size class-1 ISI marked - 01 Set of three (b) OUTGOINGS (i) MCCB4 pole, 415 Volts, 50 Hz AC,250 Amps 25 KA rupturingcapacitiy with Adjustable Thermal and Fixed Magnetic setting -3 Noc. (ii) MCCB4 pole, 415 Volts, 50 Hz AC, 63Amps 25 KA rupturingcapacitiy - 2 No. Note:(i) All incoming and outgoing feeder shall be connected by cable through suitable size glands & thimples.(ii) The various feeders shall be indicated by 50mm size letters in synthetic enamel white paint (iii) All MCCB should be connected to Bus bar directly through expended links |
| 13 | All as per item No 11 here-in-before, size of LT panel not less than 1.0 m high x 1.5 m width x 0.5 m depth but incommer & outgoing as per the following:- (a) INCOMING :- (i)MCCB 4 pole , LT 415 Volts, 50 Hz ACgradeof 250Amps rating36 KA- 01 No. (ii) Voltmeter 0-500 V digital type with 3 way rotary selector switch - 01 No (iii) Ammeter 0-400 Amp digital type with 3 way rotary selector switch - 01 No(iv) Indicating lamp one set of three (v) CT of suitable size class-1 ISI marked - 01 Set of three (b) OUTGOINGS (i) MCCB4 pole, 415 Volts, 50 Hz AC, 63 Amps 36 KA -4 Nos. (ii) MCBTPN, 415 Volts, 50 Hz AC, 63 Amps 10 KA -1 No1. |
| 14 | M&L for earthing complete in replacement with galvanized earth plate electrode 60cmx60cmx6mm thick burried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of plate not less than 1.5 m deep below normal ground level and connected to and including galvanized iron earth streep 25x4 mm by welding thimbles, etc as shown in electrical plate No 3 of SSR Part-I and connection to main switch board/Test point/panel/equipment and testing on completion including excavation and earth work in any type of soil, returning filling in, and removal of surplus spoil to a distance not exc 50 metre, charcoal and salt in alternate layer 15 cm thick all around the earth plate electrode, MS funnel with wire mesh, GI pipe medium grade 20 mm bore for watering and 40mm bore upto 7.50 metre long GI pipe light grade for earth wire protection fixed with poles/wall with two clamps, made from MS flat 25 mmx3mm, welding,PCCchamber (1:3:6) type C1, 40mm thick precast RCC cover 1:2:4 type B1 shall be provided on CI frame etc complete including taking down existing u/s earthing all as specified & as directed. |
| 15 | Supply , fixing, installing and commissioningof octagonal Hot-Dip Galvanised street light pole7 mtr long , Top dia 70mm (A/F) Bottom dia 130mm (A/F) sheet thickness 3mm and base plate dimensions 200x200x12, foundation bolts M19x600 and 1 mtr arm for lighting bracket, 1100 volts grade,including cost of nuts and bolts and all accessories ( including provisions of camera, Wi Fiunit, speaker etc at later stage)as supplied by themanufature including cost foundation accessories etc, the foundation bolts as per manufactureer design should be hot dipped galvanised pole complete with door locking arrangement, Terminal plate consisting of 2 nos10A, 4 pole natural links including connection etc with suitable connecting arrangement for 2 nos, cost of RCC 1:1.5:3 for foundation of size 0.7m x0.7mx1.8m with minimum 8 nos 12 mm dia longitudinal MS reinforcement rods with rings of 8 mm dia not more than 200mm cement concrete for fixing the pole with labour and material required to complete the job cat ref JIL9010C, Material specification mast & pole shaft : BSEN 10025, ASTM A572, IS 5986, Foundation - IS 2062/E250A, Base Plate IS-2062, Galvanization IS:4759/2629 and ASTM A123Make: Bajaj, Crompton complete all as specified and directed . |
| 16 | Supply and fixingin replacement to LED street light fitting 90 watt 230 Volt ACout door type with high pressure die cast aluminium hosing and heat resistant toughtened glass complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP65/66 protection complete all as specified and directed.Make:Halonix Cat Ref No HLSLD-E1-90-CWDL-R01 or equivalent of Havells/Phillips |
| 17 | S&F FRLS PVC insulated and PVC sheathed 1.5 sqmm 3 core multistranded copper conductor cable from for street light including PVC wire connectors for making connection complete all as specified and directed. |
| 18 | Supply , laying,jointing, testing and commissioningof size 10 sqmm 4 core LT underground cable , 1100 volts grade, XLPE insulated and PVC sheathed, armoured heavy duty with multistrand aluminium conductors IS-7098, laid in trenches /fixed on wall /floor /road /culverts /pole or encased in GI pipe complete all as specified and directed. |
| 19 | Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine for laying under ground pipe upto 40mm dia complete all as specified and directed. |
| 20 | Material and labourfor 16 mtr long High galvanised mast (in two sections ) 360mm Bottom 150mm top 4/3 mm section thickness PCD 460 mm with base plate of 560x25 mm light suitable for 9 lantern symmetrically fitted along with their control gear and having two point suspension system with stainless steel wire rope of 6mm dia 97/19 guage and double drum winch with luminaire mounting arm, pulley assembly, aviation obstruction light, lightning arrester spike including RCC foundation as per height complete all as specified and directed Note :- The scope includes raising & lowering system (R&L), trailing cable, power tool, feeder pillar for switching operation of luminaries, lightning finial and aviation obstruction light. The R & L system will comprise of double drum winch, SS wire rope not less than 6mm, head frame and lantern carriage. The Job also includes RCC foundation work as per manufacturer’s instructions suitable for 16 mtr long High mast light complete all as specified and directed. |
| 21 | Supply and laying and testing cable XLPE insullated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor,1100 Volts, grade cross sectional area 25 sqmm 4 core including taking down unserviceable cable complete all as specified and directed. |
| 22 | S&F LED flood light fitting of capacity 200W for high mast light, efficacy >110LPW (or nearest higher Cap), 240 Volts, energy saving, environmental friendly, long life, exclusive innovative, die cast aluminium IP66 flood light suitable for highlighting architectural facade and general purpose lighting complete with accessories, pre-wired upto a terminal block and mounting attachment complete all as specified and directed. |
| 23 | Supply of outdoor stand mounted feeder pillar 32 A TPN MCB incomer,single dial time switch, 25A TP contactor for the automatic switching of luminaries, power tool control with 2 Nos 9A contractors and raise lower push button, incoming 35 Sqmm and outgoing 16 & 2.5 Sqmm terminals (type STD4) complete all as Spd & directed |
| 24 | S&F 4 mm dia MS wire 75x75mm mesh, made upto into mattress or cages appx 2.0 mtr height and fixed with flate iron/angle by welding in position and directed including complete all as specified and directed. Note:- MS angle, MS flate, Nuts, Bolts and washer will be measured and paid sepretly. |
| 25 | M & L for two coats of synthetic enamel paint of silver colour on steel surfaces over a coat of red oxide primer including preparation of surfaces complete all as specified. |
| 26 | M&L for copper conductor UN armoured cable XLPE Insulated and PVCInnersheathed of size 8 core 2.5 Sqmm complete all as specified and directed. |
| 27 | Supply, installation, commissioning and testing in replacement of MCCB 63 Amp (fixed on existing panel) 415 volt, 4 pole, 25 KA breaking capacity with adjustable current range for overload protection and thermal release complete with spreader terminals (legs) and with proper lugs complete all as specified and as directed. |
| 28 | Material and labour for cement concrete type D-2,1:4:8 (using 40 mm graded crushed stone aggregate)for sub floors, sub-bases, floors, foundation and paving etc complete all as specified and directed . |
| 29 | M&L for MS work of angles for post and struts of fencing around transformer plinth etc drilling holes, flate iron fillet for securing wire mess by welding to angle iron frame and framed work as in door/ gate of angle and wire mess. Door to be fixed by 03 Nos 100mm long hinges and one sliding door bolt of 300mm long for locking arrangement complete all as specified including. |