| 1 | Sch \"A\" |
| 2 | Supply & fix in replacement sheet metal enclosure indoor type of size 1.35 x 0.9 x 0.2 mtr suitable to fix on wall/floor made out of 2mm thick CRCA sheet having independent compartments suitable for single phase energy meters and MCB provided with front hinged shutters with lockable arrangements and clear glass to visualize the meter reading without opening the compartment with sufficient working space in compartment pre-wired with single core PVC insulated and sheathed FRLS stranded copper conductor wire of suitable size from bus bar to meter compartment6Nos duly crimped withcopper thimbles, duly powder coated complete all as specified and directed and consisting with the following :- (a)Copper Bus bar for 3 phase 4 wire system of 4 x 200 Amps rated insulated copper strip mounted on resin cast insulators in independent compartment having front openable shutter - One set.(b) MCCB, four pole, 415 volts, 100 Amps, 25 KA with adjustable Overload setting - One No.(c) MCB SPN, 32 Amp,10 KA C-Curve - 06 Nos.(d)Multifunction meter(0-600) Volts with inbuilt selector - One set.(e) Indicator Lamps LED in Red in Red/ Yellow/ Blue colour - One Set of Three.Note : Existing meters shall be removed & refixed in panel by contractor and rates are deemed to be inclusive. |
| 3 | Supply & fix in replacement sheet metal enclosure indoor type of size 0.9 x 0.9 x 0.2 mtr suitable to fix on wall/floor made out of 2mm thick CRCA sheet having independent compartments suitable for single phase energy meters and MCB provided with front hinged shutters with lockable arrangements and clear glass to visualize the meter reading without opening the compartment with sufficient working space in compartment prewired with single core PVC insulated and sheathed FRLS stranded copper conductor wire of suitable size from bus bar to meter compartment4Nos duly crimped withcopper thimbles, duly powder coated complete all as specified and directed and consisting with the following :- (a)Copper Bus bar for 3 phase 4 wire system of 4 x 200 Amps rated insulated copper strip mounted on resin cast insulators in independent compartment having front openable shutter - One set.(b) MCCB, four pole, 415 volts, 100 Amps, 25 KA with adjustable Overload setting Ir = (0.8 to 1.0)xIn - One No.(c) MCB TPN, 63 Amp,10 KA C-Curve - 04 Nos.(d)Multifunction meter(0-600) Volts with inbuilt selector - One set.(e) Indicator Lamps LED in Red in Red/ Yellow/ Blue colour - One Set of Three.Note : Existing meters shall be removed & refixed in panel by contractor and rates are deemed to be inclusive. |
| 4 | Supply & fix in replacement sheet metal enclosure indoor type of size 0.9 x 0.9 x 0.2 mtr suitable to fix on wall/floor made out of 2mm thick CRCA sheet having independent compartments suitable for single phase energy meters and MCB provided with front hinged shutters with lockable arrangements and clear glass to visualize the meter reading without opening the compartment with sufficient working space in compartment prewired with single core PVC insulated and sheathed FRLS stranded copper conductor wire of suitable size from bus bar to meter compartment4Nos duly crimped withcopper thimbles, duly powder coated complete all as specified and directed and consisting with the following :- (a)Copper Bus bar for 3 phase 4 wire system of 4 x 200 Amps rated insulated copper strip mounted on resin cast insulators in independent compartment having front openable shutter - One set.(b) MCCB, four pole, 415 volts, 100 Amps, 25 KA with adjustable Overload setting Ir = (0.8 to 1.0)xIn - One No.(c) MCB SPN, 32 Amp,10 KA C-Curve - 04 Nos.(d)Multifunction meter(0-500) Volts with inbuilt selector - One set.(e) Indicator Lamps LED in Red in Red/ Yellow/ Blue colour - One Set of Three.Note : Existing meters shall be removed & refixed in panel by contractor and rates are deemed to be inclusive. |
| 5 | Supply & fix in replacement sheet metal enclosure indoor type of size (0.9x0.45x0.2) mtrsuitable to fix on wall/floor made out of 2mm thick CRCA sheet having independent compartments suitable for single phase energy meters and MCB provided with front hinged shutters with lockable arrangements and clear glass to visualize the meter reading without opening the compartment with sufficient working space in compartment prewired with single core PVC insulated and sheathed FRLS stranded copper conductor wire of suitable size from bus bar to meter compartment02 Nos duly crimped with copper thimbles, duly powder coated complete all as specified and directedand consisting with the following :- (a) Bus bar for 3 phase 4 wire system of 4 x 200 Amps rated insulated copper strip mounted on resin cast insulators in independent compartment having front openable shutter - One set.(b) MCCB, four pole, 415 volts, 100 Amps, 25 KA with adjustable Overload setting Ir = (0.8 to 1.0)xIn- One No.(c) MCB TPN, 63 Amps, 10 KA C-Curve - 02 Nos.(d) Multifunction meter(0-500) Volts with inbuilt selector switch - One set.(e) Indicator Lamps LED in Red in Red/ Yellow/ Blue colour - One Set of Three.Note : Existing meters shall be removed & refixed in panel by contractor and rates are deemed to be inclusive. |
| 6 | M&L Sub main wiring with PVC insulated cable copper conductor FRLS two single core 6 Sqmm drawn through Existing or new PVC rigid non metallic conduit including earth continuity FRLS copper conductor 6 Sqmm PVC insulated with green insulation complete all as specified and directed incluing PVC conduit . |
| 7 | All as per ser item No 05 here-in-before but size 04 Sqmm Copper conductor complete all as specified and directed |
| 8 | Supply and laying XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 6 Sqmm 2 core complete all as specified and directed |
| 9 | Materials and Labour for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4 mm dia galvanised iron or steel wire complete all as specified and directed |
| 10 | Material & labour for Earth continuity conductor or main earthing lead or lightning conductor,25mmx4mm GI strip, fixed to wall on batten with saddles and fixing screws or PVC/Porcelain insulators etc or recessed or chases or burried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing or roof conductors & down conductors etc as required complete all as specified and directed. |
| 11 | Material & labour for Earth continuity conductor or main earthing lead or lightning conductor,32mmx6mm GI strip, fixed to wall on batten with saddles and fixing screws or PVC/Porcelain insulators etc or recessed or chases or burried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing or roof conductors & down conductors etc as required complete all as specified and directed. |
| 12 | Material & labour for soldering/Welding/brazingon both sides (over lapping) to the GI strip of any size as earthing lead including dismantling the old from the existing position/equipment without disturbing the functional requirements of the equipments and reconnecting after repair/welding complete all as specifed and directed. |
| 13 | Materials and Labour for repair of earthing pit as shown on electrical plate No 3 of SSR Part –I (2009), in PCC (1:3:6), type C1, pre-cast RCC (1:2:4) type B1 cover slab 54 cm x 54 cm x 5 cm reinforced with 8 mm dia TMT bars @ 150 mm centre to centre both ways, with one handle for lifting made out of 8 mm dia MS bar including demolition of existing damaged earthing pit and including necessary earthwork in any type of soil, complete all as specified and directed. |
| 14 | S&F in position at various/different locations funnel alongwith wire mesh and replacing existing broken/damaged items complete all as specified & directed. |
| 15 | M& L for earthing complete with & including galvanized MS earth plate of size600 x 600 x 6 mm thick, buried vertically in ground to a depth not less than 2.25 metre below ground level,with top edge of earth plate not less than 1.5 below ground level connected to galvanized earth wire soldered and riveted or connected to earth plate by means of nuts, bolts , check nuts & washers, of galvanizediron or steel all as Shown in electrical plate No. 3 of MES SSR Part- I (2009) and connected to panel board, all as specified and testing on completion including provn of earth wire 4 mmm diaduly protected with and including 15 mm bore medium grade GI pipe upto 7.5 (maximum) metre from electrode to earth point including provnof the earth plate surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of not less than 15 cm in alternate layers of charcoal and salt on all sides of earth plate andGI light grade watering pipe of 20mm bore with funnel with wire mesh including all necessary excavation& earth work in any type of soil, returning filling in, removal of surplus soil to a distance 50 metre, PCC 1:3:6type C-1 as inearth chamber, 50 mm thick RCC cover using cementconcrete 1:2:4 type B-0 reinforced with & including 8 mm dia mild steel TMT bar @ 100 mm c/c Both way with suitable handle for lifting arrangement & including form work and MS frame using MS angle of size 40mm x 40mm x 6mmcomplete all as specified & directed. NOTES:- (i) On testing, after completion of Job, if desired earth resistance is not obtained, the earthing shall be redone by the contractor without any extra cost to the department. |
| 16 | All as per ser item No 14 here-in-before but using galvanised iron strip 25x4mm as earthing lead complete all as specified and directed. |
| 17 | All as per ser item No 14 here-in-before but using galvanised iron strip 32x6mm as earthing lead complete all as specified and directed. |
| 18 | Excavation in trenches in soft/loose soil not exceeding 1.5 m wide and not exc. 1.5 mtr deep for laying of cables and getting out in soft/loose soil compete all as specified and directed. |
| 19 | M&L filling dry and clean sand in trenches for cable 8 cm deep below and 15 cm above for cable cushioning complete all as specified and directed . |
| 20 | M&L Old size sub class ‘B’ bricks laid flat in trenches over the cable with the length of brick perpendicular to the direction of cable length, adjacent/abutting each other complete all as specified and directed. |
| 21 | Returning filling including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick in trenches compete all as specified and directed. |
| 22 | Removal of surplus soil obtained from excavation to a distance not exceeding 50 mtr and depositing where directed ata level not exceeding 1.5 mtr above the starting point compete all as specified and directed. |
| 23 | Supply, laying, jointing, testing and commissioning in replacement of cable XLPE insulated , armoured heavy duty electric cable with aluminium conductor, 1100 volts grade,laid in trenches, fixed by means of MS saddles on or fixed on poles including connection with proper lugs for the following size including taking out old one complete all as specified and directed :- |
| 24 | 25 Sqmm 3.5 Core |
| 25 | 35 Sqmm 3.5 Core |
| 26 | 50 Sqmm 3.5 Core |
| 27 | Supply and fixing in replacment GI pipe light grade 40 mm bore for cable protection fixed to poles/along wall/floor/under road/across the drain or nallah including taking up old GI pipe complete all as specified and directed |
| 28 | All as per ser item No 23 here-in-before but size 50 mm dia complete all as specified and directed |
| 29 | All as per ser item No 23 here-in-before but size 80 mm dia complete all as specified and directed |
| 30 | M&L in replacement of SP MCB 6 to 32Amps, 240 v, 50 Hz AC Made from moulded self extinguishing thermostat plastic and suitable for \"C\" curve, 10KA breaking capacity and terminal box suitable upto 35 sqmm cable complete all as specified and directed conforming to IS 8828, IEC 60898 . |
| 31 | M&L in replacement of MCB Single Pole & Neutral MCB 6 to 32 Amps, 240 v, 50 Hz AC Made from moulded self extinguishing thermostat plastic and suitable for \"C\" curve, 10KA breaking capacity and terminal box suitable upto 35 sqmm cable complete all as specified and directed conforming to IS 8828, IEC 60898. |
| 32 | S& F in replacement offactory made Pantone 7541C shade powder coated distribution board SPN 4 way fabricated of CRCA sheet with metal door (IP-43 protection) bar, Neutral bar, standard DIN rail, earth bar and cable ties for cable management, top and bottom removable gland plates with knockouts and suitable for one SP MCB as a incomer and 3 SP MCBs as outgoing complete all as specified and directed conforming to IS: 8623 along end box for above DB. |
| 33 | M&L in factory made Pantone 7541C shade powder coated distribution board SP & N 12 way fabricated of CRCA sheet with metal door (IP-43 protection) bar, Neutral bar, standard DIN rail, earth bar and cable ties for cable management, top and bottom removable gland plates with knockouts and suitable for one DP MCB as a incomer and 10 SP MCBs as outgoing complete all as specified and directed conforming to IS: 8623 along end box for above DB |
| 34 | M&L in factory made Pantone 7541C shade powder coated distribution board SP & N 8 way fabricated of CRCA sheet with metal door (IP-43 protection) bar, Neutral bar, standard DIN rail, earth bar and cable ties for cable management, top and bottom removable gland plates with knockouts and suitable for one DP MCB as a incomer and 6 SP MCBs as outgoing complete all as specified and directed conforming to IS: 8623 along end box for above DB |
| 35 | M & L in factory made Pantone 7541C shade powder coated distribution board 4 way TPN DB Double door with metal double door (IP-43 protection) fabricated of CRCA sheet and fixed on wall and suitable for universal mounting and including 200 Amps bus bar, Neutral bar, Standard din rail,earth bar and cable ties for cable management, top and bottom removable gland plates with provn for MCB TPN and RCCB as incomer and 12 SP MCBs outgoing complete all as specified and directed conforming to IS :8623 along with cable end box for above DB |
| 36 | M & L for replacement TPN MCB 40TO 63 Amps, 240 v, 50 Hz AC Made from moulded self extinguishing thermostat plastic and suitable for \"C\" curve, 10KA breaking capacity and terminal box suitable upto 35 sqmm cable complete all as specified and directed conforming to IS 8828 of 1996, IEC 60898 of 2002 |
| 37 | M&L for repair and replacement of three Phase Electronic kWh Energy Meter of rating 10-60 Amps, Class 1.0, 240V, 50Hz, LED type display compete all as specified and directed. |
| 38 | M&L for repair and replacement of single Phase Electronic kWh Energy Meter of rating 5-30 Amps, Class 1.0, 3X 240V, 50Hz, LED type display compete all as specified and directed. |
| 39 | M&L for LT fedder piller box out door type made out of MS sheet CRCA of sheet 3.0 mm thick 90x45x60 cm size with aluminium busbar 4 No\"s 400 Amp long suitable for 440 volts and mounted on LT protection insulator, Front opening door two leaf braced with continue hinges mounted on 4 Nos angle iron of 50x50x6 mm,60 cm long duly included with boxand grouted in PCC block of size 30x30x15 cm in concrete 1:3:6 and top of box MS sheet duly in step types with protection of 20mm on all sides weather/vermen proof with high quality rubber bedding on panel door, cable entry arrangements at bottom including earthing terminals 2 No\"s at both sides, cable gland connecting to busbar and painted with red stove enamelled powder coated paint two coats over red oxide primer complete all as specified and directed |
| 40 | Supply and fixing in replacement of MCCB of current rating 400 Amps, 4 pole, 415 volts AC, 36 KA rupturing capacity with adjustable thermal type release including taking down old unserviceable MCCBs complete all as specified and directed. |
| 41 | Supply and fixing in replacement of MCCB of current rating 315 Amps, 4 pole, 415 volts AC, 36 KA rupturing capacity with adjustable thermal type release including taking down old unserviceable MCCBs complete all as specified and directed. |
| 42 | Supply and fixing in replacement of MCCB of current rating 250 Amps, 4 pole, 415 volts AC, 36 KA rupturing capacity with adjustable thermal type release including taking down old unserviceable MCCBs complete all as specified and directed. |
| 43 | Supply and fixing in replacement of MCCB of current rating 200 Amps, 4 pole, 415 volts AC, 36 KA rupturing capacity with adjustable thermal type release including taking down old unserviceable MCCBs complete all as specified and directed. |
| 44 | Supply and fixing in replacement of MCCB of current rating 125 Amps, 4 pole, 415 volts AC, 25 KA rupturing capacity with adjustable thermal type release including taking down old unserviceable MCCBs complete all as specified and directed. |
| 45 | Supply and fixing in replacement of MCCB of current rating 100 Amps, 4 pole, 415 volts AC, 16 KA rupturing capacity with adjustable thermal type release including taking down old unserviceable MCCBs complete all as specified and directed. |
| 46 | Supply and fixing in replacement of MCCB of current rating 63 Amps, 4 pole, 415 volts AC, 16 KA rupturing capacity with adjustable thermal type release including taking down old unserviceable MCCBs complete all as specified and directed. |
| 47 | Supply, installation, testing & Commissioning of OEM built outdoor 40kVAr APFC panel in replacement of suitable size, having Circuit Breaker, Capacitor duty Contactor, Super heavy duty Power Capacitors, APFC Relay shall be of same OEM make.APFC Panel shall be OEM make, machine pressed, dust and vermin proof, indoor type, coated with 11 tank power coating process to provide better protection against corrosion. The APFC panel will be fabricated out of 14/16 SWG CRCA sheet steel, free floor standing.APFC panel should have Insulated bus bar pan assembly made from copper of suitably rated capacity. The capacitors shall be encapsulated in an aluminium can. All vital components of APFC panel i.e. capacitors, contactors, APFC relay should be of same OEM make. Advanced Range PF Regulator / micro-processor based APFC relay having 8/12 steps with LCD Display with a built in RS 485 communication port. The capacitor duty contactors shall be used for switching \"on\" and switching \"off\" operations in capacitor banks. Also, the Capacitor used should be of Super Heavy Duty MPP type with Penta safety, Capacitors used should be ISI mark and having BIS certification. Step size of capacitors for 100KVAR would be =2 (15 kVAr) + 1 (5 kVAr) + 1 (3 kVAr) + 2 (1 kVAr) |
| 48 | Boring of holes under road, pavement, hard standing by trenchless technique and necessary T&P for passing of LT/HT cables. complete all as specified and directed. |