| 1 | Maintenance of Station Battery Banks as per specification. |
| 2 | Monthly Maintenance on flooded type battery banks of voltage upto 48V and VRLA Battery upto 110V. |
| 3 | Monthly Maintenance on 110V flooded type battery banks |
| 4 | Annual Curative discharge and charge on VRLA Battery Banks of voltage more than 48V & up to 110V. (Including hourly recording of all cell voltages) |
| 5 | Annual Curative discharge and charge on flooded type Battery Banks of voltage upto 110V. (Including hourly recording of Specific gravity, cell voltage and temperature.) |
| 6 | Supply, installation, testing and commissioning of 110V,10ASCR Controlled FloatBattery Chargeras per the detailed specification. |
| 7 | Supply, installation, testing and commissioning of12V,26Ah VRLA Battery for RMU control supply as per the detailed specification. |
| 8 | Supply and installation of Power contactor inAMF panel for DG set |
| 9 | Maintenance of Earth Pits and measurement of Earth Pit Resistance as per the specification. (Refer Sec VI (MNC), Clause No.2). |
| 10 | Supply and replacing following earth pit chamber parts after removing and disposing off old/damaged part as per drawing No. IGC/ESD/5060/1008/1. |
| 11 | RCC Top cover alone |
| 12 | RCC ring Collar alone |
| 13 | RCC ring with cover |
| 14 | Installation of Following Sizes of Copper Earthing Conductor on Walls, Floors, Built in Trenches including supply of GI spacer and clamps, fixing fasteners etc as per detailed specification. .(Note: Copper conductor will be issued free of cost by the department).(Refer Sec VI, Clause No.12.5). |
| 15 | 95 Sqmm multi Stranded tinned copper conductor |
| 16 | End Termination of the following sizes of annealed, tinned, stranded Copper conductor including supply of copper crimping lugs etc. (Refer Sec VI, Clause No.12.6). |
| 17 | 95 Sqmm stranded tinned Copper conductor |
| 18 | AMC forDiesel Engines sets of various capacities of different make installed atIGCAR as followsas per the scope of work. |
| 19 | AMC for 650kVA Diesel Engine set of Kirloskar make installed at PDC-XII SS at IGCAR as per the scope of work. |
| 20 | AMC for 250kVA Diesel Engine set of Kirloskar make installed at DWR SS at IGCAR as per the scope of work. |
| 21 | AMC for 250kVA Diesel Engine set of Kirloskar make installed at RCL SS at IGCAR as per the scope of work. |
| 22 | AMC for 180kVA Diesel Engine set of Cummins make installed at PDC-IX SS at IGCAR as per the scope of work |
| 23 | AMC for 62.5kVA Diesel Engine set of Cummins make installed at KKM Gate at IGCAR as per the scope of work. |
| 24 | AMC for 25kVA Diesel Engine set of Kirloskar make installed at UGC-CSR at IGCAR as per the scope of work. |
| 25 | AMC for 10kVA Mobile Diesel Engine set of Ashok leyland make installed at at IGCAR as per the scope of work. |
| 26 | Charges for carrying out B check in the following DG setslocated at IGCAR as per the scope of work |
| 27 | Charges for carrying out 250kVA Diesel Engine set B-Check including supply ofspares for B-Check (Engine oil 40 ltrs,fuel filters,lube oil filter, air cleaner element and required hoses etc.) as per the detailed scope of work. |
| 28 | Charges for carrying out 180kVA Diesel Engine set B-Check includingsupply of spares for B-Check (Engine oil 40 ltrs,fuel filters,lube oil filter, air cleaner element and required hoses etc.) as per the detailed scope of work. |
| 29 | Charges for carrying out 62.5kVA Diesel Engine set B-Check including supply ofspares for B-Check (Engine oil 15 ltrs,fuel filters,lube oil filter, air cleaner element and required hoses etc.) as per the detailed scope of work. |
| 30 | Charges for 25kVA Diesel Engine set B-Check includingspares for B-Check (Engine oil 10 ltrs,fuel filters,lube oil filter, air cleaner element and required hoses etc.) as per the detailed scope of work. |
| 31 | Charges for 10kVA Diesel Engine set B-Check includingspares for B-Check (Engine oil 10 ltrs,fuel filters,lube oil filter, air cleaner element and required hoses etc.) as per the detailed scope of work. |
| 32 | Cleaning of DG Sets and Their AMF Panels including supply of consumables(Banian waste) as per detailed specification |
| 33 | Servicing / Repairing of Self starter motor of DG Set as per detailed specification including Transportation charges. |
| 34 | Top up of Diesel to the DG Set diesel tanks From the Diesel drums using manual Pump including shifting of Pumps. |
| 35 | Assisting in Protective Relay Calibration work.Cleaning of relay housing and tightness checking |
| 36 | Assisting in replacement/modification of relay/multifunction meters and its associated wiring. |
| 37 | Wiring for Numerical relays with 1.5sqmm 1100V grade FRLS insulated copper conductor wires in PCCpanelsincluding termination of copper wires at either end by crimping,testing and commissioningas per the detailed scope of work [Note:supply of Wires, PVC Sleeves/Ferrules, Copper Crimping Lugs are in department scope] |
| 38 | Maintenance of Motor Control centres/Distribution Centres, LT panels / TPN switch Fuse Units (Refer Sec VI (MNC), Clause No.17.2). |
| 39 | AMF panel with 2 Nos. Of ACB or Contactor and Cubical Switchboards having number of vertical sections up to 7 |
| 40 | Shifting of Electrical equipments/Oil drums of various sizes including loading and unloading.(Refer Sec VI (MNC), Clause No.31). |
| 41 | Equipment weighing upto 100 kg within a distance of 500 mtrs. |
| 42 | Equipment weighing upto 100 kgs for a distance more than 500 mtrs and upto a distance of 5 kms.(Refer Sec VI (MNC), Clause No.31) |
| 43 | Heavy Electrical equipment (more than 500 kg and upto 5 Tons) within a distance of 1 kM |
| 44 | Heavy Electrical equipment (more than 500 kg and upto 5 Tons) within a distance of 5 kM |
| 45 | Shifting of Tr. Oil/Diesel with drums. (210Litres) |
| 46 | Supply, cleaning the floor, proper pasting and installation of 2.0 mm thickness, Max useable voltage 3.3kV, AC Proof voltage 10kV for 3 minutes, AC dielectric strength 30kV RMS Insulating Mat confirming to IS:15652 |
| 47 | Supply and painting One coat on metallic surfaces of electrical equipment and other required surface at all levels with primer and following paint (Asian or approved brand, colour and manufacturer) to give an even shade including preparation of the surfaces, scaffolding complete all as per specifications and as directed by the Engineer-in-Charge. (Refer Sec VI (MNC), Clause No.3). |
| 48 | Synthetic Enamel Paint |
| 49 | Supply and installation of Name platesmade up of Acrylic sheets with various sizeswith description engraved on itas follows |
| 50 | 300 x50mm Acrylic sheet |
| 51 | 400 x100mm Acrylic sheet |
| 52 | 300 x150mm Acrylic sheet |
| 53 | 100 x50mm Acrylic sheet |
| 54 | Supply and Installation of MS Brackets, Supports, Frame work, Clamps, Base Channels, etc. fabricated out of angle / Channel / Rods etc. The rate quoted shall include the cost of fabrication / welding, cleaning and painting/ galvanising as follows including supply of required, fasteners, nuts, washers, etc.(Refer Sec VI, Clause No.11). |
| 55 | MS fabrication 1 coat primer & 2 coats synthetic enamel paint |
| 56 | GI: MS fabrication With hot dipped galvanising. |
| 57 | Supply and installation of GI Perforated sheet(4mm holes 3mm thick) with fabrication for providing in PCC Panel |
| 58 | Operating the dewatering pump for dewatering cable trenches and related activities. |
| 59 | Clearing light jungle area, bulb weeds, grass including removal all unwanted plants, branches, twigs, wild growth etc.complete, and disposing the same 100 meters away manually or burning them without disturbing other areas etc., complete all as directed by the Engineer-in-Charge. Contractor must inform the Engineer-in-charge and prior permission shall be obtained from him for burning the wild growth.(Refer Sec VI (MNC), Clause No.7.3). |
| 60 | Cleaning the spare cub-boards / Tool-racks, shifting of equipments and spares with in the sub-station, re-arranging /positioning the spares and equipments and segregation of materials, cleaning of spares, minor house keeping works as per the detailed specification. (using 1 electrican and 3 helpers for one day.) |
| 61 | Operation of Distilled water plant& storing ofwater in 10 Ltrs. cans |
| 62 | Loading, Transportation, Unloading at site, installation, Testing and Commissioning of 1100 Volts Grade PVC/HRPVC/XLPE insulated, Stranded Aluminium/copper conductor cables of following sizes in built-in trenches, on walls, poles and through embedded pipes including supply of GI spacer, clamps etc and as per the detailed specification (Note: Cable will be issued free of cost by the department).(Refer Sec VI, Clause No.3) |
| 63 | 0 3/3.5/4core X Upto 25 sqmm |
| 64 | End Termination of the following sizes of Aluminium Conductor PVC Insulated and sheathed armoured UG Cable using Single Compression, Heavy Duty, Gland connecting the cable to the equipment such as Switches/Panel Boards etc. using Comet or equivalent make Aluminium crimping lugs as directed by Engineer-in-Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for fixing cable gland. (Refer Sec VI, Clause No.10.1). |
| 65 | 4C x 2.5 Sq.mm including cable gland earthing |