| 1 | Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m deep for foundation/cable trench, not exceeding 10 Sqm on plan and getting out in soft/loose soil complete all as specified and as directed. |
| 2 | Returning filling including spreading, levelling and well ramming in layers not exceeding 25cm thick in soil complete all as specified and as directed. |
| 3 | Removal of surplus soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above starting point complete all as specified and as directed. |
| 4 | M&L for sand cushioning with dry clean sand 15cm below cable and 8cm above the cable complete all as specified and as directed. Note : Punned thickness shall be measured for payments. |
| 5 | Supply and laying un-reinforced precast concrete cable cover, class LV, type 1 with peak, size 250mm x 150mm x 40mm complete all as specified and as directed. |
| 6 | Taking out/down old/unserviceable under ground LT cables of any size and connections including pipes etc from trenches/walls/poles of any cross sectional area and keeping serviceable materials in safe custody for reuse and unserviceable materials removing from site as specified and as directed. Note : Excavation and earth work shall be measured and paid separately. |
| 7 | Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated, armoured, nominal cross sectional area of main conductor 10 Sqmm, 4 core stranded aluminium conductor, ISI marked as per IS-7098 (Part-I) 1988 including cable glands, lugs etc to suit the cable size and to be laid in trenches, under floors, through GI pipe complete all as specified and as directed. Note : (1) Pipes shall be measured and paid separately under relevant items.(2) Excavation and earth work shall be measured and paid separately. |
| 8 | Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated, armoured, nominal cross sectional area of main conductor 16 Sqmm, 4 core stranded aluminium conductor, ISI marked as per IS-7098 (Part-I) 1988 including cable glands, lugs etc to suit the cable size and to be laid in trenches, under floors, through GI pipe complete all as specified and as directed. Note : (1) Pipes shall be measured and paid separately under relevant items.(2) Excavation and earth work shall be measured and paid separately. |
| 9 | Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated, armoured, nominal cross sectional area of main conductor 25 Sqmm, 3.5 core stranded aluminium conductor, ISI marked as per IS-7098 (Part-I) 1988 including cable glands, lugs etc to suit the cable size and to be laid in trenches, under floors, through GI pipe complete all as specified and as directed. Note : (1) Pipes shall be measured and paid separately under relevant items.(2) Excavation and earth work shall be measured and paid separately. |
| 10 | Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated, armoured, nominal cross sectional area of main conductor 35 Sqmm, 3.5 core stranded aluminium conductor, ISI marked as per IS-7098 (Part-I) 1988 including cable glands, lugs etc to suit the cable size and to be laid in trenches, under floors, through GI pipe complete all as specified and as directed. Note : (1) Pipes shall be measured and paid separately under relevant items.(2) Excavation and earth work shall be measured and paid separately. |
| 11 | Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated, armoured, nominal cross sectional area of main conductor 50 Sqmm, 3.5 core stranded aluminium conductor, ISI marked as per IS-7098 (Part-I) including cable glands, lugs etc to suit the cable size and to be laid in trenches, under floors, through GI pipe complete all as specified and as directed. Note : (1) Pipes shall be measured and paid separately under relevant items.(2) Excavation and earth work shall be measured and paid separately. |
| 12 | Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated, armoured, nominal cross sectional area of main conductor 70 Sqmm, 3.5 core stranded aluminium conductor, ISI marked as per IS-7098 (Part-I) 1988 including cable glands, lugs etc to suit the cable size and to be laid in trenches, under floors, through GI pipe complete all as specified and as directed. Note : (1) Pipes shall be measured and paid separately under relevant items.(2) Excavation and earth work shall be measured and paid separately. |
| 13 | Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated, armoured, nominal cross sectional area of main conductor 95 Sqmm, 3.5 core stranded aluminium conductor, ISI marked as per IS-7098 (Part-I) including cable glands, lugs etc to suit the cable size and to be laid in trenches, under floors, through GI pipe complete all as specified and as directed. Note : (1) Pipes shall be measured and paid separately under relevant items.(2) Excavation and earth work shall be measured and paid separately. |
| 14 | Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated, armoured, nominal cross sectional area of main conductor 120 Sqmm, 3.5 core stranded aluminium conductor, ISI marked as per IS-7098 (Part-I)including cable glands, lugs etc to suit the cable size and to be laid in trenches, under floors, through GI pipe complete all as specified and as directed. Note : (1) Pipes shall be measured and paid separately under relevant items.(2) Excavation and earth work shall be measured and paid separately. |
| 15 | Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated, armoured, nominal cross sectional area of main conductor 185 Sqmm, 3.5 core stranded aluminium conductor, ISI marked as per IS-7098 (Part-I)including cable glands, lugs etc to suit the cable size and to be laid in trenches, under floors, through GI pipe complete all as specified and as directed. Note : (1) Pipes shall be measured and paid separately under relevant items.(2) Excavation and earth work shall be measured and paid separately. |
| 16 | Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated, armoured, nominal cross sectional area of main conductor 240 Sqmm, 3.5 core stranded aluminium conductor, ISI marked as per IS-7098 (Part-I)including cable glands, lugs etc to suit the cable size and to be laid in trenches, under floors, through GI pipe complete all as specified and as directed. Note : (1) Pipes shall be measured and paid separately under relevant items.(2) Excavation and earth work shall be measured and paid separately. |
| 17 | Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated, armoured, nominal cross sectional area of main conductor 400 Sqmm, 3.5 core stranded aluminium conductor, ISI marked as per IS-7098 (Part-I) 1988 including cable glands, lugs etc to suit the cable size and to be laid in trenches, under floors, through GI pipe complete all as specified and as directed. Note : (1) Pipes shall be measured and paid separately under relevant items.(2) Excavation and earth work shall be measured and paid separately. |
| 18 | Boring of holes horizontal for laying not less than 40mm pipe (minimum depth 0.75 mtr from top level) under the road pavement, hard standing using trenchless technology complete all as specified and as directed.Note : cost of accessories required for making hole/bore deemed to be included in the quoted rate. |
| 19 | M&L for 40 mm bore, steel tubes, galvanised, light grade with all fittings, laid in floor /road crossing /drain etc as in protection of UG cable including taking down old unserviceable complete all as specified and as directed. |
| 20 | M&L for 80 mm bore, steel tubes, galvanised, light grade with all fittings, laid in floor / road crossing /drain etc as in protection of UG cable including taking down old unserviceable complete all as specified and as directed. |
| 21 | M&L for 100 mm bore, steel tubes, galvanised, light grade with all fittings, laid in floor / road crossing /drain etc as in protection of UG cable including taking down old unserviceable complete all as specified and as directed. |
| 22 | Supply, jointing and testing XLPE cable straight through joints including jointing materials and accessories complete, cold shrinkable outdoor cable joint kit suitable for XLPE 1100 Volts (Earthed) cable of size 6 Sqmm to 16 Sqmm 2/3.5/4 Core complete all as specified and as directed. |
| 23 | Supply, jointing and testing XLPE cable straight through joints including jointing materials and accessories complete, cold shrinkable outdoor cable joint kit suitable for XLPE 1100 Volts (Earthed) cable of size 25 Sqmm to 50 Sqmm 2/3.5/4 Core complete all as specified and as directed. |
| 24 | Supply, jointing and testing XLPE cable straight through joints including jointing materials and accessories complete, cold shrinkable outdoor cable joint kit suitable for XLPE 1100 Volts (Earthed) cable of size 70 Sqmm to 120 Sqmm 2/3.5/4 Core complete all as specified and as directed. |
| 25 | Supply, jointing and testing XLPE cable end termination joints including jointing materials and accessories complete, cold shrinkable outdoor cable joint kit suitable for XLPE 1100 Volts (Earthed) cable of size 35 Sqmm to 95 Sqmm 4 core complete all as specified and asdirected. |
| 26 | Supply, jointing and testing XLPE cable end termination joints including jointing materials and accessories complete, cold shrinkable outdoor cable joint kit suitable for XLPE 1100 Volts (Earthed) cable of size 120 Sqmm to 240 Sqmm 4 core complete all as specified and asdirected. |
| 27 | S&F for precast RCC cable route indicator with embrossing mark as \"HT /LT CABLE \"duly painted with approved colour of size 75cm x 15cm x 7.5cm all as specifed and directed by Engr-in-Charge. |
| 28 | Dismantling /uprootingof LT unserviceable pre-stressed concrete /steel poles of any size and shape and including taking out dismantled portion of poles embedded in ground after necessary demolition ofconcrete foundation and making good disturbed ground surface properly and disposal thereof complete all as specified and as directed.Note:- Earth work for taking out poles shall be measured and paid separately under relevant item of this Schedule. |
| 29 | M&L for steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9.0 metres long) including two coats of aluminium paintover a coat of primer except the planting depth which shall be painted withblack bituminous paintincluding writing pole number using suitable paintcomplete all as specified and as directed.Note : excavation and earth work, PCC fillingshall be measured and paid separately. |
| 30 | M&L for cement concrete (1:4:8) type D-2 (using 40 mm graded stone aggregate) as in pole foundation, filling and mass concrete complete all as specified and as directed. |
| 31 | M&L for cement concrete (1:3:6) type C-1 (using 20 mm graded stone aggregate) as in sub base of floor complete all as specified and as directed. |
| 32 | M&L for cement concrete (1:2:4) type B-1 using 20 mm graded stone aggregate as in coping of pole including necessary form work for fair finish surfaces complete all as specified and as directed |
| 33 | Dismantling LT stay assembly, of any size andremoving from the site(s) complete all as specified and as directed. |
| 34 | M&L for stay assembly comprising of 7/8 SWG galvanised stay of standard wire of required length fixed to pole with and including galvanised flat iron clamps, bolts, nuts and washers etc including galvanised steel 14 mm dia, 400 mm long stay bow and GI stay plate of size 300 x 300 x 6 mm thick, thimble MS clamp made out of 50 x 6mm and loop insulators porcelain brown all as shown in EP No.1 of SSR part - I including all accessories and excavation, earth work and PCC work complete all as specified and as directed. |
| 35 | Dismantling cross-arms of M.S. channel or angle sections etc. complete and stackingaside serviceable materials for re-use with in 50m and removing unserviceable materials from site of workcomplete all as specified and as directed. |
| 36 | M&L for cross arms bracing supports clamps and back plates fabricated from structural steel sections including nuts, bolts & washers, welding, bending, cold or hot drilling holes for bolts in any shape or size as indicated or directed and including one coat of aluminium paint over one coat of red oxide zinc chrome primer, complete all as specified and as directed. |
| 37 | Dismantling of insulators of any type from LT poles of any size and type and setting aside complete all as specified and as directed. |
| 38 | M&L for pin type, polymer insulator suitable for 1100 volts with 100 mm height, 65 mm dia inclgalvanised steel pin and nut complete all as specified and as directed. |
| 39 | M&L for shackle type, polymer insulator suitable for 1100 volts grade complete with 100mmheight and 115 mm dia, size of straps 31mm x 5mm and 14mm dia, overhead distribution lines, complete with galvanised steelhardware and fittings, all as specified and as directed. |
| 40 | Dismantling/taking down old aluminium steel reinforced (ACSR) conductor of any size any type from LT overhead line including all jumper, cross arms, clamps, bolts, nuts etc and keeping serviceable materials in safe custody for reuse in the work complete all as specified and as direc |
| 41 | Supply, fixing and stringing of aluminium conductor steel reinforced (ACSR) conductor of size (a) Squireel 6/1 x 2.11, (b) Weasel 6/1 x 2.59, (c) Rabbit 6/1 x 3.25 as suitable conforming to IS - 398 part- 4 of 1994 including binding, straining in LT over head line including all jumper connection and binding on insulator with new wire/aluminium tape complete all as specified and as directed. |
| 42 | Restringing of old aluminium conductor steel reinforced (ACSR) or AAAC conductor of any size and make on LT 9 m long poles alongwith earth wire, including replacement of binding wire and aluminium taps reconnection, street light connections, service connections and binding to insulators with suitable size of new binding wire including prunning of tree branches 2 mtr all around OH LT line by means of pulley, rope etc complete all as specified and as directed.Note : 04 Nos of ACSR or AAAC conductor shall be measured as one unit length. |
| 43 | S&F for PVC/fiber separator for LT over head line, 1100 volts, conductor 3/4 wire system, suitable for 2 conductor, in spanwithout damaging the over head line including taking down old separator complete all as specified and as directed. |
| 44 | S&F for PVC/fiber separator for LT over head line, 1100 volts, conductor 3/4 wire system, suitable for 4 conductor, in spanwithout damaging the over head line including taking down old separator complete all as specified and as directed. |
| 45 | S&F in repairs 1100 volts grade, heavy duty, cable PVC insulated, aluminium conductor, stranded of size 10 Sqmm x 2 core,served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm dia GI suspension wire, one twin core cable flat or circular etc complete all as specified and as directed. |
| 46 | S&F in repairs 1100 volts grade, heavy duty, cable PVC insulated, aluminium conductor, stranded of size 6 Sqmm x 2 core,served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm dia GI suspension wire, one twin core cable flat or circular etc complete all as specified and as directed. |
| 47 | S&F for PVC conduit pipe 20mm dia with fixing arrangement with flat iron with nut bolts on pole complete all as specified and as directed. |
| 48 | S&F in repairs non transparent SMC kiosks pole box 3/4 wirejunction box made engineering plastic one piece mouldingof size 310 x 210 x 120mm with connector bus bar 4 strips mounting on DMC unbrakable insulator with kitkat 20 A MCBcomplete fixedto street light pole with suitable sizeofmild steel/ flat iron clamps, nuts and bolts complete all as specified and as directed. |
| 49 | S&F in repairs non transparent SMC kiosks pole box 2 wirejunction box made engineering plastic one piece mouldingof size 200 x 150 x 100mm with connector bus bar 2 strips mounting on DMC unbrakable insulator with kitkat 20 A MCBcomplete fixedto street light pole with suitable sizeofmild steel/ flat iron clamps, nuts and bolts complete all as specified and as directed. |
| 50 | S&F in replacement of synthetic insulating mat of size 2.0mx1.0mx19mm at substations and other installations complete all as specified and as directed. |
| 51 | S&F in repair of MCCB, 4 pole, 415 Volts with adjustable thermal & adjustable magnetic setting, 400 Amps of breaking capacity 36 KA complete all as specified and as directed. |
| 52 | S&F in repair of MCCB, 4 pole, 415 V with adjustable thermal & adjustable magnetic setting, 630 Amps of breaking capacity 36 KA complete all as specified and as directed. |
| 53 | S&F in repair of MCCB, 4 pole, 415 V with adjustable thermal & adjustable magnetic setting, 250 Amps of breaking capacity 25 KA complete all as specified and as directed. |
| 54 | S&F in repair of MCCB, 4 pole, 415 V with adjustable thermal & adjustable magnetic setting, 200 Amps of breaking capacity 25 KA complete all as specified and as directed. |
| 55 | S&F in repair of MCCB, 4 pole, 415 V with adjustable thermal & adjustable magnetic setting, 160 Amps of breaking capacity 25 KA complete all as specified and as directed. |
| 56 | S&F in repair of MCCB, 4 pole, 415 V with adjustable thermal & adjustable magnetic setting, 125 Amps of breaking capacity 25 KA complete all as specified and as directed. |
| 57 | M&L for Off load change over switch 400 A with enclosure rated voltage 415V-AC 50 Hz, type FP fixed on wall with nut and bolt including taking down complete all as specified and directed. |
| 58 | M&L for Off load change over switch 250 A with enclosure rated voltage 415V-AC 50 Hz, type FP fixed on wall with nut and bolt including taking down complete all as specified and directed. |
| 59 | M&L for Off load change over switch 100 A with enclosure rated voltage 415V-AC 50 Hz, type FP fixed on wall with nut and bolt including taking down complete all as specified and directed. |
| 60 | M&L for Off load change over switch 63 A with enclosure rated voltage 415V-AC 50 Hz, type FP fixed on wall with nut and bolt including taking down complete all as specified and directed. |
| 61 | S&F in repairs LED street light fitting of capacity 90W, with pressure die cast housing , toughened glass and individual LEDs with secondary optics and IP 66 protection and impact resistance complete AC 120-300V, 50Hz with lumen 9900 with CCT 5700 and PF >0.95, surge protection >5KV and THD <10%, including with necessary brackets /pipes/clamps & nuts& bolts for holding the street light fitting and twin core aluminum cable of 2.5 Sqmm as required in existing location complete all as specified and as directed. |
| 62 | S&F in repairs LED street light fitting of capacity 70/75W, with pressure die cast housing , toughened glass and individual LEDs with secondary optics and IP 66 protection and impact resistance complete AC 120-300V, 50Hz with lumen 7920 with CCT 5700 and PF >0.95, surge protection >5KV and THD <10%, including with necessary brackets /pipes/clamps & nuts& bolts for holding the street light fitting and twin core aluminum cable of 2.5 Sqmm as required in existing location complete all as specified and as directed. . Note (i) necessary excavation, PCC work, bracket, connecting wire will be measured and paid separately under relevant items |
| 63 | S&F in repairs LED street light fitting of capacity 60W, with pressure die cast housing , toughened glass and individual LEDs with secondary optics and IP 66 protection and impact resistance complete AC 120-300V, 50Hz with lumen 6600 with CCT 5700 and PF >0.95, surge protection >5KV and THD <10%, including with necessary brackets /pipes/clamps & nuts& bolts for holding the street light fitting and twin core aluminum cable of 2.5 Sqmm as required in existing location complete all as specified and as directed. . Note: (i) necessary excavation, PCC work, bracket, connecting wire will be measured and paid separately under relevant items) |
| 64 | S&F in repairs LED street light fitting of capacity 45/50W, with pressure die cast housing , toughened glass and individual LEDs with secondary optics and IP 66 protection and impact resistance of IK07, including with necessary brackets /pipes/clamps & nuts& bolts for holding the street light fitting and twin core aluminum cable of 2.5 Sqmm as required in existing location complete all as specified and as directed. . Note: (i) necessary excavation, PCC work, bracket, connecting wire will be measured and paid separately under relevant items) |
| 65 | S&F in repairs integral compact wide beam high performance LED flood light luminaire with IP 66 protection, tampered protective toughened glass cover, thermal shock impact resistance cover, epoxy black powder coated finish, high purity , 200WLED of luminous efficiency greater than >120 Lm/watt with built in control gear including connecting up with 2.5 Sqmm multistranded Aluminium/Copper conductor cables of suitable length withfixed to pole/wall, etc and testing complete all as specified and directed. |
| 66 | S&F in repairs integral compact wide beam high performance LED flood light luminaire with IP 66 protection, tampered protective toughened glass cover, thermal shock impact resistance cover, epoxy black powder coated finish, high purity , 120WLED of luminous efficiency greater than >120 Lm/watt with built in control gear including connecting up with 2.5 Sqmm multistranded Aluminium/Copper conductor cables of suitable length withfixed to pole/wall, etc and testing complete all as specified and directed. |
| 67 | Surface dressing of installation/sub station area by removing of grass, creepers, etc. from roof of the building, in fencing and surrounding area of installation building complete all as specified and as directed. |
| 68 | Attending and rectifying day-to-day faults and breakdowns in Low Tension (LT) and High Tension (HT) overhead ACSR conductor lines or underground power cables, LT/HT Switch gear system at any height on poles or towers, street lighting system faults including replacement of lights, work covers locating faults, repair/replacement of damaged portions, reconnection, jointing, testing, and restoration of supply all complete as specified and as directed. NOTE :- (I) Necessary T&P and Transport required for attending and rectifying complaints should be provided by the contractor under this item only. (II) New Material Issued from Store will be recorded as per procedure and old material recovered from site will be deposited at MES store. |
| 69 | Pruning branches of tree not exceeding 10mm girth including cutting of trunk branches and stacking of serviceable material and disposal of unserviceable materials to a distance not exceeding 50 m and clearing complete all as specified and as directed. |
| 70 | Pruning branches of tree not exceeding 15mm girth including cutting of trunk branches and stacking of serviceable material and disposal of unserviceable materials to a distance not exceeding 50 m and clearing complete all as specified and as directed. |
| 71 | Pruning branches of tree not exceeding 20mm girth including cutting of trunk branches and stacking of serviceable material and disposal of unserviceable materials to a distance not exceeding 50 m and clearing complete all as specified and as directed. |
| 72 | Pruning branches of tree not exceeding 25mm girth including cutting of trunk branches and stacking of serviceable material and disposal of unserviceable materials to a distance not exceeding 50 m and clearing complete all as specified and as directed. |
| 73 | Pruning branches of tree not exceeding 30mm girth including cutting of trunk branches and stacking of serviceable material and disposal of unserviceable materials to a distance not exceeding 50 m and clearing complete all as specified and as directed. |
| 74 | Supply & fixing flexible LED tricolor strip lightlength18mtrs high surge with stand capability uoto 3.5 kv, 96 LEDs per meter, 8w/mtr, 220V-240V, 50 Hz with IP 65 complete all as specified and directed. |
| 75 | Supply only Megger Insulation Tester, Digital/Analog display with 5 Test range; 250 V, 500 V,1000 V. 2500 V, 5000 V. 1 GΏ, 1/4 mA, 5 kV digital insulation tester, Guard terminal to shunt surface leakage , selectable DC or AC volts including frequency , CAT III 600 V safety rating complete all as specified and directed Make : WACO or equivalent |
| 76 | Supply only 11-33 KV Highly insulated FRP Earth Discharge Rod , Length 5ft , Voltage range 11-33 Kv , Handle Material Rubber complete all as specifed and directed . Make : Kusam Meco or equivalent |
| 77 | Supply only Digital Clamp Meter with specification 6000 counts, High Precision with Ncv, Vfc, in rush current , Low Z, temperature. All as directed and specified. Make Fluke 301 b or equivalent |
| 78 | S&F in repairs, LED post top lantern of 40 WattMAPLE Decorative Post top for 360° indirect light with IP 65 protection. Resistant to impact and corrosion. Glare-free and better uniformity including providing and connection with 1.5Sqmm copper conductor, multistranded copper conductor cable of required length complete all as specified andas directed. (Make : Havell\"s/ Philips/CG). |
| 79 | S&F in repairs decorative gate light 20W made up of high grade unbreakable polycarbonate material suitable for retrofit LED lamp B22 Base, including providing and connection with 2.5 Sqmm aluminium conductor, cable of required length and taking down old unserviceable fitting of any make and size complete all as specified and as directed.Make - Havells /Philips/Bajaj/Wipro/Century. |
| 80 | S&F 10W LED Bollard MAYA I Pressure die cast powder coated housing with PC diffuser. Efficient high output LED with IP65 protectionMake -Havells / CG/Bajaj/Magik complete all as specified and directed . |
| 81 | M&L for scrapping the existing surfaces of the LT/HT poles of anyheight (painting length) with emery paper, removing the dust and rustproperly and applying 2 coats of aluminum paint over complete pole and stickering the pole with glow sign round the electrical pole at three places of 10cm width andnumbering with paint not less than 4 letters with glow sign material at the bottom of pole and nomenclature shall be given by Engineer-in-Charge complete all as specified and as directed. |
| 82 | Taking down old unserviceable sign board and S&F new retro reflective sign board of size 4x3 feet, fixed both sides on stainless steel board made out of aluminium composite panel (ACP) sheet, 3mm thick, fixed on SS-304 series hollow tubular section, 38mm dia. The board shall be provided with reflective tape of quality high intensity chequered type blue colour, letter / symbol shall be written in white colour writing of approved shape. The sign board shall be supported on 2 Nos. post of 60mm dia stainless steel pipe, 304 series, 3.0m long with round moulded design on top duly embedded in ground of size 450x450x600mm in PCC 1:2:4 type B-2 (using 40mm graded stone aggregate) including necessary excavation & earthwork etc. complete all as directed by Engineer-in-Charge.Note: The sample of sign board is to be approved by Engr-in-Charge as per ground requirement before procurement by Contractor. |