| 1 | H. T. SYSTEM 11 KV DOUBLE POLE STRUCTURE Supply, erection, testing and commissioning of 2 pole structure for providing 1 No. 11KV,200A GOS in accordance with IE rules,as per direction and approval of E/I & local authority specification and drawings and comprising of the following. MR. a. 2 Nos. 11 mtr. long MS STEEL poles complete with, pole excavation, MS STEEL foundation, and back filling complete MS steel channel/angle iron etc.b. 1 Set of cross arms, branching, clamps and painting complete with GI nut, bolts & washers as required (for GO & DO), LA connection.c .1 set 11KV Insulator complete with spindles & hardware complete as required. d .1 No. 11KV 400A TP Gang operated Air break switches complete with 25mm dia GI pipe operating machanism, handle & locking arrangement. e. 1 set of 3 nos.11KV single pole drop out fuse complete with barrel fuses, and mounting arrangement. f. 1 set (3 nos.) 11KV lightning arrestor and connecting to all phases. g. 4 No. 150 mm dia 6 meter long GI pipe class \"B\" (for XLPE cable protection) as required. h. 2 Set 50mm dia 3m long GI pipe earting with 25 x 6 mm GI earth strip complete as required (for GO & DO & LA). i 1 nos. 11KV HT danger boards and 2 set of anticlimbing devices. |
| 2 | 11 KV DOUBLE POLE STRUCTURE FOR LINE Supply, erection, testing and commissioning of 2 pole structure for providing 1 No. 11KV,200A GOS in accordance with IE rules,as per direction and approval of E/I & local authority specification and drawings and comprising of the following. MR. a. 2 Nos. 11 mtr. long MS STEEL poles complete with, pole excavation, MS STEEL foundation, and back filling complete MS steel channel/angle iron etc. b .1 set 11KV Insulator complete with spindles & hardware complete as required. c. 4 No. 150 mm dia 6 meter long GI pipe class \"B\" (for XLPE cable protection) as required. d. 2 Set 50mm dia 3m long GI pipe earting with 25 x 6 mm GI earth strip complete as required. e. 1 nos. 11KV HT danger boards and 2 set of anticlimbing devices. |
| 3 | Supply and fixing of 2 metres high cage fabricated with 3mm thick expanded metal fixed on 50mm x 50mm x 6mm angle iron frame having vertical members spaced at 1 to 1.25 mts and horizontal members spaced at 1 mt. The vertical members shall be grouted in floor and horizontal members in the wall to a depth of 300mm with ends forked. The cage shall have 2000mm x 1000mm size one leaf door with locking device having door frame fabricated with 35mm x 35mm x 6mm angle iron and 3mm expanded metal duly fixed with the cage member with hinges etc. The cage shall be painted with red oxide primer and synthetic enamel paint. The job includes all materials, labour, T&P etc. for proper completion of work, as per direction and approval of E/I. MR |
| 4 | HT Panel, (Main) S.I.T.C. of RMU outdoor Type as per latest specification of UP Power Corporations, make GTP approved by UP Power Corporation. Including construction of Plinth and earthing etc. with all material as per Technical Requirment, as per direction and approval of E/I. MR. 11 KV 1 incoming & 4 Outgoing RMU unit 11kv, 630A, 21KA, outdoor, 5way, Motorized right side extensible with configuration of all VCB with temperature, humidity sensors, FRTU, FPI, smart meters & MODEM, RMU containes the breakers-Vacuum and insulated in SF6 gas.with 5 years warranty |
| 5 | 11 KV 1 incoming & 3 Outgoing RMU unit 11kv, 630A, 21KA, outdoor, 4way, Motorized right side extensible with configuration of all VCB with temperature, humidity sensors, FRTU, FPI, smart meters & MODEM, RMU containes the breakers-Vacuum and insulated in SF6 gas. 5 years warranty |
| 6 | 11 KV 1 incoming & 2 Outgoing RMU unit 11kv, 630A, 21KA, outdoor, 3way, Motorized right side extensible with configuration of all VCB with temperature, humidity sensors, FRTU, FPI, smart meters & MODEM, RMU containes the breakers-Vacuum and insulated in SF6 gas. 5 years warranty |
| 7 | Supply of 11KV grade 3core Brand Stranded Compact Circular Aluminium Conductor, Conductor Screen With Extruded Semi Conducting Compound, XLPE Insulated, Insulation Screening with extruded Semi Conducting Compound in combination with Copper Tape, cores laid up, innersheath of PVC tape, galvanised flat steel strip armoured and overall PVC Sheathed Cable conforming to IS 7098 / (PART-II) 1985 with latest amendments, as per direction and approval of E/I. MR. 240sq.mm 3 core |
| 8 | Laying of one number PVC insulated and PVC sheathed / XLPEpower cable of 11 KV grade of following size in the existing RCC/HUME/ METAL pipe as required, as per direction and approval of E/I. DSR 2022( 8.3.2) Above 120 sq. mm and upto 400 sq. mm |
| 9 | Supplying and making indoor cable end termination with heatshrinkable jointing kit complete with all accessories includinglugs suitable for following size of 3 core, XLPE aluminiumconductor cable of 11 KV grade as required, as per direction and approval of E/I. DSR 2022 (10.4.3). 240sq.mm 3 core/300sq.mm 3 core |
| 10 | Supplying and making outdoor cable end termination with heatshrinkable jointing kit complete with all accessories includinglugs suitable for following size of 3 core, XLPE aluminiumconductor cable of 11 KV grade as required , as per direction and approval of E/I. DRS 2022 (10.5.3). 240sq.mm 3 core/300sq.mm 3 core |
| 11 | TRANSFORMER Providing, erecting, testing & commissioning approved make oil immersed naturally ONAN cooled, double wound, core type outdoor copper wound 11 kV/ 433 Volts Step Down Transformer of following capacities operating on 3 phase, 50 Hz 4 wire & neutral earthed system continuously rated for a full temperature rise in oil following capacities operating on 3 phase, 50 Hz 4 wire & neutral earthed and Off Circuit Tap Changer continuously rated for a full temperature rise in oil not exceeding 40 deg. C at maximum ambient temp. Of 50 deg. C complete with necessary radiator first filling of new transformer oil & standard fitting as below complying with I.S. 1180 LEVEL 2 standards On load tap changing range steps -10% to 5% on H.V in steps of 2.50% .and L.V. for variation should be provided The H.V. shall be connected delta & secondary with star connection. The transformer should have cable-end boxes on H.T. side & on L.T. side suitable for bus duct or cables as per requirement complete with test certificates from manufacturers. Losses As per IS 1180 LEVEL-2. including construction of plinth and doing other arrangements as. 2. Top filter valve 1 Nos. required, as per direction and approval of E/I. MR. 3. Bottom filter-Cum-drain valave 1Nos. 4. Rating and diagram plate 1nos. 5. Earthing Terminals 2Nos. 6. Thermometer pockets 1Nos. 7. Lifting Lugs 2/4 Nos. 8.Air release plug 2/4 Nos. 9. Bi-directional rollers 4Nos. 10.Jacking pads 1Nos.11.Presure relese valve 1Nos. 12. Separate Bare LV neutral 433V 13. Detachable/Fixed type radiators 1Nos. 14. Magnet Oil level gauge. 15. Oil temperature indicator 1Nos. 16. Winding temperature indicator 1Nos. 17. Marshlig Box single window 1No. 18. Double flot buchholz\"s relaywith alarm and trip contact. COPPER WOUND 400KVA 11/.433V. MR |
| 12 | COPPER WOUND 250KVA 11/.433V. MR |
| 13 | MAIN L.T PANEL/FEEDER PILLAR SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be outdoor, free standing, floor mounting, sheet metal clad, cubicle, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required including construction of plinth and doing other arrangements as required, as per direction and approval of E/I. MR. MAIN L.T PANEL. MR. INCOMING. 1 Nos. 500 Amp FP MCCB 36KA having S/C, E/F O/C protectionR,Y,B Phase indication Lamp with control MCBOn, Off, Trip Status Indication with control MCBMultifunction Meter. BUSBARS. 1 Nos. 600 Amp FP busbars of aluminium alloy as per SLD. OUTGOING. 8 Nos. 100 Amp FP MCCB 36 kA, On, Off, Trip Status Indication with control MCB. 1 Nos. 100 Amp FP MCCB 36 kA, On, Off, Trip Status Indication with control MCB. RELAYS AS PER SLD |
| 14 | METER PANEL. MR. INCOMING. 1 Nos. 100 Amp FP MCCB 36KA having S/C, E/F O/C protectionR,Y,B Phase indication Lamp with control MCBOn, Off, Trip Status Indication with control MCBMultifunction Meter. BUSBARS 1 Nos. 125 Amp FP busbars of aluminium alloy as per SLD. OUTGOING. 30 Nos. 63 Amp DP MCB 10 Ka. 28Nos. 1-Phase Energy Meter. RELAYS AS PER SLD |
| 15 | METER PANEL. MR INCOMING 1 Nos. 100 Amp FP MCCB 36KA having S/C, E/F O/C protectionR,Y,B Phase indication Lamp with control MCBOn, Off, Trip Status Indication with control MCB Multifunction Meter. BUSBARS. 1 Nos. 125 Amp FP busbars of aluminium alloy as per SLD. OUTGOING. 24 Nos. 63 Amp DP MCB 10 Ka. 20Nos. 1-Phase Energy Meter. RELAYS AS PER SLD |
| 16 | MAIN L.T . MR. INCOMING. 1 Nos. 800 Amp FP MCCB 36KA having S/C, E/F O/C protectionR,Y,B Phase indication Lamp with control MCBOn, Off, Trip Status Indication with control MCBMultifunction Meter. BUSBARS. 1 Nos. 1000 Amp FP busbars of aluminium alloy as per SLD. OUTGOING. 7 Nos. 250 Amp FP MCCB 36 kA, On, Off, Trip Status Indication with control MCB. 2 Nos. 63 Amp FP MCCB 36 kA, On, Off, Trip Status Indication with control MCB. RELAYS AS PER SLD |
| 17 | FEEDER PILLAR . MR. 1 Nos. 250 Amp FP MCCB 25KA having S/C, E/F O/C protectionR,Y,B Phase indication Lamp with control MCBOn, Off, Trip Status Indication with control MCBMultifunction Meter. BUSBARS. 1 Nos. 320 Amp FP busbars of aluminium alloy as per SLD. OUTGOING. 15 Nos. 63 Amp FP MCB 10 Ka. RELAYS AS PER SLD |
| 18 | FEEDER PILLAR. MR. INCOMING. 1 Nos. 250 Amp FP MCCB 25KA having S/C, E/F O/C protectionR,Y,B Phase indication Lamp with control MCBOn, Off, Trip Status Indication with control MCBMultifunction Meter. BUSBARS. 1 Nos. 320 Amp FP busbars of aluminium alloy as per SLD. OUTGOING. 19 Nos. 63 Amp FP MCB 10 Ka. RELAYS AS PER SLD |
| 19 | FEEDER PILLAR. MR. INCOMING. 1 Nos. 250 Amp FP MCCB 25KA having S/C, E/F O/C protectionR,Y,B Phase indication Lamp with control MCBOn, Off, Trip Status Indication with control MCBMultifunction Meter. BUSBARS. 1 Nos. 320 Amp FP busbars of aluminium alloy as per SLD. OUTGOING. 20 Nos. 63 Amp FP MCB 10 Ka. RELAYS AS PER SLD |
| 20 | EXTERNAL LIGHT FEEEDER PILLAR. MR. SITC of compartmentalised design, dust tight & vermin proof made out of 14 gauge M.S. sheet, stove powder coated L.T panel complete as required with following incomming & outgoing as per detail below and including construction of plinth and doing other arrangements as required, as per direction and approval of E/I. INCOMER. 1 Nos. 63 AMP FP MCCB . 1 Nos. 100 AMP FP DUSK-DOWN TIMER WITH CONTACTOR. BUSBARS. 1 Nos. 100 Amp TPN busbars of aluminium alloy as per SLD. OUTGOING. 8 Nos. 32 Amp DP MCB. INSTRUMENTS. 18 Nos. 1 Phase energy meter. 1 Nos. 0 to 500 Volt digital voltmeter with Voltmeter Selector Switch & Protective SP MCB (96mm square). 1 No. 0 to 100 Amp digital Ammeter .1 Sets of phase indicating lights (RYB) with protection fuses . 1 Sets breaker \"ON\" & \"OFF\" indicating lamp. 1 Sets auto trip indicating lamp . |
| 21 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Voltsgrade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protectedwith burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc., as per direction and approval of E/I. SOR 2018 Sl no. 501. 6 sq. mm 2 core, SOR 2018 Sl no. 501.a |
| 22 | 10 sq. mm 2 core, SOR 2018 Sl no. 501.b |
| 23 | 16 sq. mm 4 core, SOR 2018 Sl no. 501.i |
| 24 | 70 sq. mm 3-1/2 core, SOR 2018 Sl no. 501.m |
| 25 | 240 sq. mm 3-1/2 core, SOR 2018 Sl no. 501.r |
| 26 | 300 sq. mm 3-1/2 core, SOR 2018 Sl no. 501.s |
| 27 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required,as per direction and approval of E/I. 6 sq. mm 2 core. DSR 2022 (9.1.1) |
| 28 | 10 sq. mm 2 core. DSR 2022 (9.1.2) |
| 29 | 16 sq. mm 4 core. DSR 2022 (9.1.33) |
| 30 | 70 sq. mm 3-1/2 core. DSR 2022 (9.1.23) |
| 31 | 240 sq. mm 3-1/2 core. DSR 2022 (9.1.29) |
| 32 | 300 sq. mm 3-1/2 core. DSR 2022 (9.1.30) |
| 33 | Supply and fixing danger board fabricated from 10 gauge M.S. Sheet as per I.E. Rules, as per direction and approval of E/I. MR |
| 34 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required, as per direction and approval of E/I. DSR 2022 (5.2) |
| 35 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required, as per direction and approval of E/I. DSR 2022 (5.4) |
| 36 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required, as per direction and approval of E/I. DSR 2022 (5.6) |
| 37 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm), as per direction and approval of E/I. DSR 2022 (5.8) |
| 38 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm),as per direction and approval of E/I. DSR 2022 (5.9) |
| 39 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut,bolt, spring, washer excavation and re-filling etc. as required, as per direction and approval of E/I. DSR 2022 (5.10) |
| 40 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required, as per direction and approval of E/I. DSR 2022 (5.11) |
| 41 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required, as per direction and approval of E/I. DSR 2022 (5.16) |
| 42 | Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required, as per direction and approval of E/I. DSR 2022 (14.14.4) . 300 mm dia |
| 43 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required, as per direction and approval of E/I. 160 mm dia (OD-160 mm & ID-135 mm nominal). DSR 2022 (14.16.4) |
| 44 | Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand ) with R.C.C. top slab with 1:1.5:3 mix (1 cement : 1.5 coarse sand (zone- III) : 3 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand (zone- III) : 8 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design, as per direction and approval of E/I. MR |
| 45 | OUTDOOR LANDSCAPE LIGHTING Supplying and making straight through joint with cast resin compound including ferrules and other jointing materials, for following size of PVC insulated and PVC shethed/XLPE aluminium conductor cable of 1.1 KV grade as required , as per direction and approval of E/I. DSR 2022 9.3. 70 sq. mm 3-1/2 core. DSR 2022 (9.3.20) |
| 46 | 240 sq. mm 3-1/2 core. DSR 2022 (9.3.26) |
| 47 | 300 sq. mm 3-1/2 core. DSR 2022 (9.3.27) |
| 48 | Supplying and making straight through cable jointing with cast resin compound including ferrule and other jointing materials, for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required , as per direction and approval of E/I. DSR 2022 10.3. 240sq.mm 3 core. DSR 2022 (10.3.3) Please Enable Macros to View BoQ information |