| 1 | Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or water supply pipes lines etc or not exceeding 10 sqm on plan and not exceeding 1.5 m in depth and getting out in soft/ loose soil complete all as specified and as directed. |
| 2 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm in soft/ loose/ hard/ dense soil complete all as specified and as directed. |
| 3 | Removing excavated material (excluding hard rock) not exceeding 50 m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed. |
| 4 | M & L for cement concrete in foundation, filling and mass concrete in M10(Nominal Mix) using 40 mm nominal size graded crushed stone aggregate complete all as specified and as directed. |
| 5 | M & L for cement concrete M15 (Nominal Mix) using 20 mm nominal size graded crushed stone aggregate in lintels upto 1.5 m clear span, cills, steps; seismic and other similar bands, plinth courses, string courses, lacing courses, parapets and railings upto 60 cm in height, copings, kneelers, apex stones, bed plates, kerbs, water troughs, slab staging for water tanks, filling of pressed steel door frame, fixing of hold fasts and the like including weathering, slightly rounded or chamfered angles and throating including necessary formworks complete all as specified and directed. |
| 6 | Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 120 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed. |
| 7 | Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3.5 core, nominal cross sectional area of main conductor 95 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed. |
| 8 | Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 50 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. including taking down old cable complete all as specified and as directed. |
| 9 | Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 35 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed. |
| 10 | Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 4 core, nominal cross sectional area of main conductor 25 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed. |
| 11 | Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 4 core, nominal cross sectional area of main conductor 16 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed. |
| 12 | Supply & laying Sand coarse dry as in cushioning of underground electric cable in trenches, laid to a uniform thickness of 23cm (15cm under the cable & 8cm over the cable) and gently punned down to 18cm thickness complete all as specified and as directed. Note :- Only punned down sand shall be measured. |
| 13 | M&L for bricks, common burnt clay building bricks, sub- class \"B\" designation 75 complete all as specified and directed. |
| 14 | Supplying & laying, in trenches 40 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed. |
| 15 | Supplying & laying in trenches 50 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed. |
| 16 | Supplying & laying in trenches 80 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed. |
| 17 | Supplying & laying in trenches 100 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed. |
| 18 | Supply and fixing 32 mm X 6 mm galvanised mild steel strip for horizontal conductors and down conductors including suitable design of fixing components of galvanised steel as per fig 28 of IS 2309: 1989 complete all as specified and as directed. |
| 19 | Supply and fixing aluminium strip 25 mm X 3.15 mm for horizontal conductors and down conductors including suitable design of fixing components of galvanised steel as per fig 28 of IS 2309: 1989 complete all as specified and as directed. |
| 20 | S&F for cable End termination joint suitable for 1100 voltgrade LT cable, out door type terminal heat shrinkable type joint complete with all jointing material and accessories suitable for 3.5/4 core XLPE LT cable of size 35 sqmm to 70 sqmm complete all as directed. |
| 21 | S&F for cable End termination joint suitable for 1100 voltgrade LT cable, out door type terminal heat shrinkable type joint complete with all jointing material and accessories suitable for 3.5/4 core XLPE LT cable of size 70 sqmm to 120 sqmm complete all as directed. |
| 22 | M&L forstraight through LT joint kit suitable for LT cable, 1100 volt, heat shrinkable type joint complete with all jointing material and accessories suitable for 3.5 corecable of size 35 sqmm to 70 sq mm complete all as directed |
| 23 | M&L for straight through LT joint kit suitable for LT cable, 1100 volt, heat shrinkable type joint complete with all jointing material and accessories suitable for 3.5 corecable of size 70 sqmm to 120 sqmmcomplete all as directed |
| 24 | M & L for earthing complete with galvanised steel plate earth electrode 600 mm X 600 mm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to earthing lead of 4.0 mm dia galvanised mild steel wire by means of bolts, nuts, check nuts and washers of galvanised iron from earth plate to test point upto 7.5 metre including all as shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete chamber in cement concrete M15 (Nominal Mix) using 20 mm nominal size coarse aggregate, precast RCC cover slab in cement concrete M15 (Nominal mix) using 20 mm nominal size coarse aggregate of size 40 cm X 40 cm X 5 cm reinforced with 8 mm dia TMT bars @ 150 mm c/c with one handle for lifting made out of 8 mm dia bar, GI funnel, GI wire mesh filter, 20 mm dia GI pipe medium grade for watering, 15 mm dia GI pipe light grade for protection of earthing lead, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil/ strata and testing including taking down old earthing complete all as specified and as directed. |
| 25 | M & L in repair for earthing complete with galvanised steel plate earth electrode 600 mm X 600 mm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to earthing lead of 32 mm X 6 mm galvanised mild steel strip by means of bolts, nuts, check nuts and washers of galvanised iron from earth plate to test point upto 7.5 metre including all as shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete chamber in cement concrete M15 (Nominal Mix) using 20 mm nominal size coarse aggregate, precast RCC cover slab in cement concrete M15 (Nominal mix) using 20 mm nominal size coarse aggregate of size 40 cm X 40 cm X 5 cm reinforced with 8 mm dia TMT bars @ 150 mm c/c with one handle for lifting made out of 8 mm dia bar, GI funnel, GI wire mesh filter, 20 mm dia GI pipe medium grade for watering, 40 mm dia GI pipe medium grade for protection of earthing lead, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil/ strata and testing complete all as specified and as directed. |
| 26 | supply, installation, testing and commissioningof size not less than 2.0m x 1.5m x0.60 m, outdoor cubical type factory made (CPRI approved), single hinged type door for individual MCCBs rubberised gasket, front& back side openable type with locking arrangement (screw type) , fabricated of CRCA sheet 3.15 mm thick supported on 50x 50 x 6 mm angle iron and Tee section frame dust and vermin proof complete with aluminium bus bar 4 Nos, 600 Amps rated capacitymounted on porcelain insulators totally enclosed chamber for protection 3 phase 415 volt with suitable capacity aluminium bus bar and interconnection between MCCB and bus bar will be done by aluminium strip only duly mounted on PCC floor andwith suitable size of bolts, nuts & wahsers.Panel boardshall be powder coated and angle iron frame painted with black synthetic enamel paint over a coat of red oxide primer complete, connecting existing cables with suitable size glands and aluminium lugs to accommodate including dismantling and taking down old unserviceable LT panel board andcomprising of the following :-Incoming :-(a) MCCB, 4 Pole, 400A, 415 V, 35 kA.- 01 No.(b) LCD multifunction meter - 01 No (c) CTs 320/5 A- set of 3(d) Phase indicator lamps (RYB) -set of 3(e) Aluminium bus bar 4 strip -600 amps(f)Internal connection by aluminium strip from MCB/MCCB to busbar and busbar to MCCB/MCB etcOutgoing :-(a) MCCB, 4 Pole, 100 Amp,415 V, 35 kA - 03 Nos(b) MCCB, 4 Pole, 200 A, 415 V, 35 kA - 01 No(c) MCB, TPN, 63 A, 415 V, 16 kA- 01 No |
| 27 | Supply, installation, testing and commissioningof size not less than 2.0m x 1.5m x0.60 m , outdoor cubical type factory made (CPRI approved) ,single hinged type door for individual MCCBs rubberised gasket, front& back side openable type with locking arrangement (screw type) , fabricated of CRCA sheet 3.15 mm thick supported on 50x 50 x 6 mm angle iron and Tee section frame dust and vermin proof complete with aluminium bus bar 4 Nos, 300 Amps rated capacitymounted on porcelain insulators totally enclosed chamber for protection 3 phase 415 volt with suitable capacity aluminium bus bar and interconnection between MCCB and bus bar will be done by aluminium strip only duly mounted on PCC floor andwith suitable size of bolts, nuts & wahsers.Panel boardshall be powder coated and angle iron frame painted with black synthetic enamel paint over a coat of red oxide primer complete, connecting existing cables with suitable size glands and aluminium lugs to accommodate including dismantling and taking down old unserviceable LT panel board and comprising of the following :-Incoming :-(a) MCCB, 4 Pole, 400A, 415 V, 35 kA.- 01 No. (b) Phase indicator lamps (RYB) -set of 3(c) Aluminium bus bar 4 strip of 300 Amps(d)Internal connection by aluminium strip from MCB/MCCB to busbar and busbar to MCCB/MCB etcOutgoing :-(a) MCCB, 4 Pole, 160 A,415 V, 25 kA - 01 No.(b) MCCB, 4 Pole, 125 A,415 V, 25 kA - 03 Nos. |
| 28 | Supply, install,testingand commissioning outdoor type LT panel/feeder panel ofsize 0.6mx0.6mx0.45m , CPRI approvedfactory made totally encloseddust and vermin proof , double steef shutter in front and single leaf shutter in rear side made of 3.15 mm thick CRCA sheet, duly fabricated and having proper locking arrangement in both ront and rear door painted with powder coated paint and aluminium bus bar 300 amps suitable for 500 volts, 50 Hz , 3 phase 4 wire system and comprising with and including following accesories and mounted on PCC platform all around the panel board including taking down of old feeder pillarcomplete and comprising of the following items:- Incoming :-(a) MCCB, 4 Pole, 200A, 415 V, 25 kA.- 01 No. (b) Aluminium bus bar 4 strip of 300 amps(c)Internal connection by aluminium strip from MCB/MCCB to busbar and busbar to MCCB/MCB etc |
| 29 | S&F in repair MCCBmicroprocessor release conforms to IS/IEC 60947-2Ics 100% Icu ETM with in- built Earth fault protection adjustable overload 40-100% adjustable short circuit 2-12 Ir, relaese range 160-400Amp in Frame 3, 4 Polebreaking capacity Icu at 415 volt AC , 36 KA , including fixingto the existing panel board matching withthe existing slots, including any alteration required and with extention links properly connected to the bus bar complete all as directed. |
| 30 | M & L for carrying out any repair woks to panel board LT with clearingany dent /deformation to panel cover,replacing/providing bolts,nuts with welding worketc.including making up with the existing colour paint of any type and size of panel complete all as specified and directed. |
| 31 | Supply, fixing and testing indication lampswith showing red, yellow and green in colour of 22.5mm dia to monitor on panel board suitable for 240V AC supply as existing at site all as specified and directed. |
| 32 | Supply and fixing, testing and commissioning digital electronic ammeter of cap as existing rangwith in built selector switch suitable for415V panel flush pattern square type with adopter or as existing including wiring complete all as specified and directed. |
| 33 | Supply, fixing, testing and commissioning of digital electronic voltmeter of cap as existing range with in built selector switch suitable for415V panel flush pattern square type with adopter or as per existing including wiring complete all as specified and directed. |
| 34 | S&F Multifunction meters 3 phase voltage, current, frequency with communication accuracy class 1 (0.5 optional) 2 output, contact for trip LED display use on LT/HT system testing complete all as directed. |
| 35 | S&F in repair 3 Pole power contactors type ML-04 with AC3 rating of 70 Amps and AC1 rating of 100 Amps- 02 Nos complete all as specified and directed. |
| 36 | M&L for reshifting of LT panel from one location to another along with removing from ground,dismantling of PCC and transportation from one side to another complete all as specified and as directed. |
| 37 | M&L for Aluminium Painting with one coats on 9mtr LT pole and one coat ofsythetic enemal paint upto 1.5meter above the ground level with black andyellow colour alternatively25 cm intervel from bottom of pole and the coping along with painting of channel and angle ontubular Poles complete all as specified and as directed. |
| 38 | M & L for numbering on PCC or tubular pole,writing neatly on the poles 1.5 meter above ground levelwith letters andtwo to three numbers complete all as specified and directed. |
| 39 | S&F of MCCBThermal Magnetic release conforms to IS/IEC 60947-2Ics 100% Icu ETM with in- built Earth fault protection adjustable overload 80-100%Fixed short circuit 10 Ir, rated current 160Amp in Frame 2, 4 Polebreaking capacity Icu at 415 volt AC , 25 KA complete all as specified and as directed. |
| 40 | S&F of MCCBThermal Magnetic release conforms to IS/IEC 60947-2Ics 100% Icu ETM with in- built Earth fault protection adjustable overload 80-100%Fixed short circuit 10 Ir, rated current 200Amp in Frame 2, 4 Polebreaking capacity Icu at 415 volt AC , 25 KA complete all as specified and dorected. |
| 41 | S&F of MCCB thermal Magnetic release conforms to IS/IEC 60947-2Ics 100% Icu ETM with in- built Earth fault protection adjustable overload 80-100%Fixed short circuit 10 Ir, rated current 250Amp in Frame 2, 4 Polebreaking capacity Icu at 415 volt AC , 25 KA complete all as specified and directed. |
| 42 | S&F of MCCBThermal Magnetic release conforms to IS/IEC 60947-2Ics 100% Icu ETM with in- built Earth fault protection adjustable overload 80-100%Fixed short circuit 10 Ir, rated current 63-100Amp in Frame 1, 4 Polebreaking capacity Icu at 415 volt AC , 25 KA complete all as specified and directed. |
| 43 | S&F MCB TPN 63 Amp \"C\" series 10KA 415 volts complete all as specified and as directed. |