| 1 | Material and labour for taking down the unserviceable flood light of 150 to 200 watts installed at a height of 12 metres on the hangar building, including arranging and utilizing all necessary tools, plants, safety gear, and equipment for safe and proper removal, and completing the work in all respects as specified and directed. |
| 2 | Supply and fixing in replacement of unserviceable flood light, 200 Watts, delivering 20,000 lumens with a system wattage of 135, CCT 5700/4000K, suitable for mounting with eye bolt hook, IP‑65 protection, and operating voltage range of 120V to 270V, installed at a height of 12 metres on the building, complete all as specified and as directed by the Engineer‑in‑Charge. Make: Philips BY515P LED200S 5700 NB PSU GR or equivalent of Havells / Crompton. |
| 3 | Taking down unserviceable sub‑main wiring of sizes 2.5, 4.0, and 6.0 sqmm (3 runs) from Distribution Board to Switch Board/ fittings height of 12 metre hanger, including removal of associated PVC casing capping and PVC conduit fixed on wall/surface of any size, and making good the disturbed surfaces where required, complete all as specified and directed by the Engineer‑in‑Charge. |
| 4 | Material and labour for sub‑main wiring in proper colour coding with 1100V grade, 1.5 sqmm, two single‑core PVC insulated FRLS unsheathed cables with multi‑stranded copper conductor conforming to IS‑694 Part‑II, ISI marked, FRLS grade, including and laid in PVC conduit/casing capping (25mm, medium grade, as per existing type) with all accessories, concealed or fixed on surface/wall/ceiling/floor/roof as required, along with flush metal boxes of suitable hylum sheet/modules and frames, and including one run of 1.5 sqmm PVC insulated, 1100V grade, FRLS, multi‑stranded unsheathed copper conductor in green colour as continuous earth wire connected to common earth dolly, complete all as specified and as directed. Make: |
| 5 | All as per item No. 4 hereinbefore but using 2.5 sqmm size cable, complete all as specified and directed by the Engineer‑in‑Charge. |
| 6 | All as per item No. 4 hereinbefore but using 4.0 sqmm size cable, complete all as specified and directed by the Engineer‑in‑Charge. |
| 7 | All as per item No. 4 hereinbefore but using 6.0 sqmm size cable, complete all as specified and directed by the Engineer‑in‑Charge. |
| 8 | Taking down copper/aluminium point wiring (light,fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc and making good disturbed surfaces of walls, floors, etc. |
| 9 | Supply and fix piano type flush switch, single pole, one way, 6 Amp, complete all as specified and directed. |
| 10 | Supply and fix piano type flush switch, single pole, one way, 16 Amp, complete all as specified and directed. |
| 11 | Supply and fix socket outlet, 5 pin, 6 Amp, complete all as specified and directed. |
| 12 | Supply and fix socket outlet, 5 pin, 16 Amp, complete all as specified and directed. |
| 13 | Supply and fix switch socket combination, 2‑in‑1, 6 Amp, flush type, 5 pin, 230 Volts, complete all as specified and directed. |
| 14 | Supply and fix switch socket combination, 2‑in‑1, 3 pin, 6 Amp and 16 Amp, flush type, universal shuttered, complete all as specified and directed. |
| 15 | Supply and fix LED light fitting, 1 × 16W, 220V AC, decorative box type, with driver and holder, including LED tube light, and connecting up with three‑core flexible copper conductor cable of suitable size from ceiling rose, complete all as specified and directed. |
| 16 | Supply and fix modular fan step regulator, 1 to 5 steps, 120 Watt - 2 modulecomplete all as specified and directed. |
| 17 | Taking down old unserviceable MCB Distribution Board of any size, including cutting and chasing/civil works involved and making good the disturbed surfaces, complete all as specified and directed. |
| 18 | Supply and fix MCB Distribution Board (DB), SPN, double door, IP‑42, 4‑way, with earth terminal and neutral bus bar for 4 circuits, suitable for concealed/surface mounting in walls, including making incoming and outgoing electrical connections with lugs/thimbles, and carrying out necessary minor civil works such as cutting, chasing, painting, and making good disturbed surfaces, complete all as specified and directed. |
| 19 | All as per item No. 18 hereinbefore but using 8 way complete all as specified and as directed. |
| 20 | Taking down old unserviceable MCB of any size complete all as specified and directed. |
| 21 | Supply and fixing miniature circuit breaker (MCB) SP 6 To 32 AMP, 240 Volts, 10kA, ‘C’ curve, of the following poles and current carrying capacity, installed in MCB distribution board (DB), complete with necessary connections, testing, and commissioning, all as specified and directed by the Engineer-in-Charge. |
| 22 | All as per item No 21 here-in-before but SPN 40 to 63 AMP. |
| 23 | Taking down old unserviceable earthing complete all as specified and as directed. |
| 24 | Material and labour for earthing complete with galvanised steel earth plate electrode 60cm×60cm× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less\"than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion complete all as specified and as directed. |
| 25 | Material and labour for earthing complete with galvanised steel plate electrodes of size 600x600x6mm thick burried directly in ground with earth pit not less than 2.25 meter deep below normal ground level with top edge of plate not less than 1.5 meter below normal ground level connected to galvanised 25x4 mmearth lead by means of nuts bolts check nuts GI washers earth wire protected by galvanised iron pipe 15mm bore (Medium grade) for watering charcoal or coke and salt in alternate layers necessary earth work in soft/loose soil complete all as shown in electrical plate No 5 of SSR Part I including testing on completion all as specified and directed. |
| 26 | Taking down old unserviceable GI wire of any size complete all as specified and as directed. |
| 27 | Supply and fixing earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4mm dia galvanised iron or steel wire complete all as specified and directed |
| 28 | Taking down old unserviceable PVC conduit / Casing Caping complete all as specified and as directed. |
| 29 | Supply and fixing of rigid non-metallic PVC conduit / casing capping, exclusive of boxes (junction / terminal), but inclusive of all accessories such as tees, bends, elbows, reducers, bell mouth tube ends, couplers, lock nuts, saddles, pipe hooks, etc. The wiring shall be laid in a neat and disciplined manner, ensuring that loose casing capping and PVC conduit are properly fixed in position 25mm, complete all as specified and directed by the Engineer-in-Charge. Make: Richa/Anchor/Polycab |
| 30 | Taking down unserviceable spare parts like Fan blades, oscillation mechanism, gear box set, motor assy, fan blade guard grill, bushings, capacitor, burnt wiring, control switch, base plate etc complete all as specified and directed. |
| 31 | Servicing of pedestal fan shall be carried out complete, including thorough cleaning, lubrication, testing, and replacement of unserviceable parts as required. The servicing shall cover inspection and rectification of fan blades (if cracked, bent, or worn out), front and rear guards (grill), and the oscillation mechanism including oscillating knob, gear box set, and lever/pinion gear. The motor assembly shall be checked, cleaned, and repaired, including replacement of motor bearings or bushings, rewinding (if burnt or weak), straightening/replacement of shaft, and replacement of capacitor in case of low speed or failure to start. The electrical system shall be overhauled, including checking and replacement of power cord/plug top, ON/OFF switch or speed control switch, and internal wiring set. The stand and base components such as height adjustment pipe and locking knob, base plate/weight stand, and all nuts, bolts, screws, and washers shall be inspected and replaced if found defective. Additional accessories such as rubber grommets/cushions for vibration control and lubricating oil/grease for shaft and gears shall be provided as necessary complete all as specified and directed by the Engineer-in-Charge. |
| 32 | Taking down unserviceable SPN enclosure complete all as specified and directed. |
| 33 | Supply and fixing Single pole and neutral enclosure with a two pin and earth plug and socket with 10-20 Amps complete with one single pole MCB. Make: Havells / Legrand / Indoasian. |
| 34 | Taking down unserviceable aviation light complete all as specified and directed. |
| 35 | Supply and fixing aviation light at 12 metre height hanger complete all as specified and as directed. |
| 36 | Material and labour for welding work required at 12 mtr height hanger. |
| 37 | Taking down old unserviceable test point of any size complete all as specified. |
| 38 | Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw complete all as specified and directed. |
| 39 | Taking down old unserviceable GI pipe from floor, wall etc of any size complete all as specified. |
| 40 | Supply, laying, 50 MM bore galvanized steel water tubing, medium grade, with all necessary fittings, laid in trenches or fixed to wall with suitable clamps for crossing the cable/strip etc complete all as specified and directed. |
| 41 | Supply and fixing in replacement of CI cover for existing size earthing pit complete all as specified and as directed. |
| 42 | Demolition of existing concrete in ground floors and pavings, not exceeding 15 cm thickness (below or above ground level), and removal of debris to a distance of 50 m from the starting point, complete all as specified and directed. |
| 43 | Excavation in trenches not exc. 1.5 Mtr wide and not exc 1.50 Mtr in depth for foundation etc. and getting out in soft/loose soil complete all as specified and as directed. |
| 44 | Excavation in trenches exc. 1.5 Mtr wide and not exc 3.0 Mtr in depth for foundation etc. and getting out in soft/loose soil complete all as specified and as directed. |
| 45 | Returning, filling in, including spreading, levelling, watering, and well ramming of excavated soil in layers not exceeding 25 cm thickness each, ensuring proper compaction, all around cables/ pipes or other underground installations. |
| 46 | Removing excavated material to a distance not exceeding 50 metres and depositing or spreading where directed, at a level not exceeding 1.5 metres above the starting point complete all as specified and directed. |
| 47 | Material and labour for PCC 1:4:8 type D2, 40mm graded aggregate complete all as specified and as directed. |
| 48 | Material and labour for PCC 1:3:6 type C1, 20mm graded aggregate complete all as specified and as directed. |