| 1 | Sub Head-I (Servicing of DEA sets) :: Carrying out \" B\" Check General Servicing of following capacity of diesel Engine Alternator sets of different makesandmodelsunder various exchanges / BTS including replacement of completeold lubricant oil, fuel filter, lubricant oil filter i/cTransportation charges, Tools and plants, testing etc complete as required at site. (Lubricant oil and filters shall be as per the manufacturer\"s recommendation).(Kirloskar/ M&M/Escorts/ Eicher/Ashok Leyland/ Greaves etc). [a] 12.5/15 KVA |
| 2 | [b]above 15 KVA and up to 20 KVA |
| 3 | [c] above 20 KVA and up to 32.5 KVA |
| 4 | [d] above 32.5 KVA up to 45KVA |
| 5 | [e] above 45 KVA and upto 62.5 KVA |
| 6 | Sub Head-II ( Repairing Works of DEA Sets) ::Replacement of faulty / defective spare parts / components/ accessories of existingDG sets i/c dismantling / disconnecting the faulty /defective ones, fixing and connection of new ones, testing and commissioningetc. complete as required.( Make- Recommended by manufacturer/ BSNL makes only)[a] 1x25 sqmm flexible Multi corecu conductor PVC insulated Battery Leads (Flexible) of length not less than 0.6 Meters with two nos terminals . |
| 7 | [b] Flexible wire braided fuel pipe of 19 mm dia for the connection of fuel line connection ( inlet and outlet ) complete as required at site. |
| 8 | [c] Banjo bolts with washer |
| 9 | [d] Suitable size belt |
| 10 | Providing ofmaintenance free NewLead acid Batteriesof following types / rating complete with first fill of electrolyte & first charging i/ctesting and commissioning at site complete as reqd.[a] 88Ah, 12 volt maintenance free Battery (M/s Exide FXPO-XP880or Equivalent of BSNl approved. Make) |
| 11 | [b] 130 Ah, 12 volt maintenance free Battery (M/s Exide FXPO-XP1300 or Equivalent of BSNLapproved Make) |
| 12 | [c] 150 Ah, 12 volt maintenance free Battery (M/s Exide FXPO-XP1500 or Equivalent of BSNLapproved. Make) |
| 13 | Repairing of following items of EA set i/creplacement of faulty parts, making connection, testing etc complete as reqd. [a] Starting Self12v up to 25 KVA |
| 14 | [b] Starting Self12V, 32.5 to 62.5 KVA |
| 15 | [c] ChargingAlternator |
| 16 | [d] Repairing and Cleaning of Engine Radiator up to 62.5 KVA EA Set etc complete as required. |
| 17 | Repairing and servicing of FIP i/c replacement of faulty components , tresting , calibration etc. complete as reqd.[a] Up to 25 KVA EA Set |
| 18 | [b] From 30 KVA to 62.5 KVA EA Set |
| 19 | Re-winding of alternatorwith \"H\" class insulated copper wire and \"H\" class insulated material (Paper, Varnish ,appoxi base hardner) i/c replacement of diodes, petty repairing , testing, dismantling and realignment,transportation upto work shop, loading /unloadingetc. complete as required. (Note: The dismantled burnt copper winding will be the property of the firm, so the rates to be quoted accordingly)[a] Up to 25 KVA EA Set |
| 20 | [b] From 30 KVA to 62.5 KVA EA Set |
| 21 | S/F of following capacity ratingfour poleon Loadchange over switchinsteel enclosurecapable ofworking 415/500 V,AC 23 Dutyi/c drilling hole on the board, making connection, earthing the body etc. as reqd. Make: HPL SOCOMAC or SS make)[a] 63 Amp Four pole on load |
| 22 | [b] 125 AmpFour pole on load |
| 23 | Supplying & fixing of three Phase AVRsuitable for voltage regulation in DG setupto 62.5 KVA Capacity EA seti/c testing etc. complete as reqd. |
| 24 | Shifting of following capacity DG set from one site to another i/c dismantling , loading / unloading and installation of DG set at new location etc. complete as reqd . ( Upto 30 Km distance )[a]Upto 25 KVA DG set |
| 25 | [b] Above 25 KVA to 62.5 KVA EA Set |
| 26 | [c] Extra per Km. charges for distance more than 30 Km |
| 27 | SH-III ( Buy back of old Lead acid batteries) :: Less (Buy back ) price for 12 Volt old existing unsevicable battery irrespective of make and model available at site. [a] AH capacity up to 110 AH |
| 28 | AH Capacity Above110 AH & up to 130 AH |
| 29 | AH capacity Above 130 AH & Upto 150 AH |
| 30 | SH-IV ( Visit Charges) :: Visit charges to attend fault of DEA Set on call basis/ complaint basis on behalf of written Job order from SDE(E) concerned for different TE /BTS sites under jurisdiction including attending the minor faults involving no material and submit detailed report for major fault to the Engineering -In-charge i/c fare charges to visit the site from HQ etc complete as reqd.Note:- (1) Visit Charges are not payable, if cost of work executed at particular site is beyond Rs 5000/-. (2). The Charges shall be paid only subject to submission of detailed site visit report in Job Order along with bill for sites where servicing / major repairing work not carried out by agency. (3). Charges shall be paid proportionately to attend the complaints e.g. 3 Sites for visit up to 30 KM\"s on a route, 2 Sites for visit more than 30 KM & Up to 60 KM on a route and 1 Site for visit beyond 60 KM from HQ . (4) Visit charges shall be allowed only once during the currency of contract/once in a year whichever is earlier for a particular sites/site as applicable. |