| 1 | Material and labour for manufacturing, installation testing and commissioning of synchronization / AMF panel suitable for synchronising 4 Nos DG sets 1010KVA-01 No, 600KVA-01 No, 500KVA-01No & 400KVA-01 No panel, indoor type, double door, cubical type, padestal mounted, of suitable size, CPRI approved having, IP 65, independent compartment for bus bar, incoming feeder and each out going feeders, totally dust and vermin proof with front and rear openings& lockable, factory made, fabricated out of of 3.15 mm thick CRCA Sheet confirming to IS 8623 & MSangle iron section of 50X50X6 mm frame, front operated with locking arrangements suitable for 3 Phase 415 volts 50 Hz, AC supply 415/440, 3 phase, 4 wire AC 50Hz having copper bus bar capacity required to carry current 110% load with three phase and half neutral colour coded, prewired with copper cable of suitable size all as standard practice of manufacturer specifications with the following accessories:- |
| 2 | Incomer DG set 1010KVA:1. 1600A, 4 pole EDO ACB 50KA MP based with O/C & E/F protection - 12. UV Release Coil 240V AC - 13. TNC - Breaker Control switch - 14. Digital MFM with RS-485 EM6400NG - 15. CT - 1600/5A, 15VA - 36. CT shorting link - 87. Phase Indicationg lamp R-Y-B -18. Indicating lamp ON/OFF/TRIP - 39. 6A SP control MCB 10KA C Curve - 510. Terminal block - 4 |
| 3 | Incomer DG set 600KVA:1. 1000A, 4 pole EDO ACB 50KA MP based with O/C & E/F protection - 12. UV Release Coil 240V AC - 13. TNC - Breaker Control switch - 14. Digital MFM with RS-485 EM6400NG - 15. CT - 1000/5A, 15VA - 36. CT shorting link - 87. Phase Indicationg lamp R-Y-B -18. Indicating lamp ON/OFF/TRIP - 39. 6A SP control MCB 10KA C Curve - 510. Terminal block - 4 |
| 4 | DG INCOMER DG - 500KVA:1. 800A, 4 pole EDO ACB 50KA MP based with O/C & E/F protection - 12. UV Release Coil 240V AC - 13. TNC - Breaker Control switch - 14. Digital MFM with RS-485 EM6400NG - 15. CT - 800/5A, 15VA - 36. CT shorting link - 87. Phase Indicationg lamp R-Y-B -18. Indicating lamp ON/OFF/TRIP - 39. 6A SP control MCB 10KA C Curve - 510. Terminal block - 4 |
| 5 | DG INCOMER - 400KVA:1. 800A, 4pole EDO ACB 50KA MP based with O/C & E/F protection - 12. UV Release Coil 240V AC - 13. TNC - Breaker Control switch - 14. Digital MFM with RS-485 EM6400NG - 15. CT - 800/5A, 15VA - 36. CT shorting link - 87. Phase Indicationg lamp R-Y-B -18. Indicating lamp ON/OFF/TRIP - 39. 6A SP control MCB 10KA C Curve - 510. Terminal block - 4 |
| 6 | Bus Coupler - 2000 A 4 pole ACB:1. 2000A 4pole EDO ACB 50KA MP based with O/C, S/C & E/F Protection - 1.02. Breaker control switch with TNC Salzer 1.03. UV release Coil 240V AC L&T 1.04. Indicating lamp ON/OFF/TRIP Esbee 1.05. 6A SP Control MCB 10KA C-Curve L&T 1.06. Terminal Block Elmex 1.0 |
| 7 | INCOMER INTERLOCKING - 1 No1. Electrical Interocking between Mains incomer, DG Incomer & Bus coupler ITE 1.0PLC BASED Synchronising & AUOYO LOAD SHARING1. Aom Ap Synchronising controller CAmAp InteliVision Color display InteliField Bus Gateway2. PLC for Interlocking Delta 1.03. SMPS 24V, 4 Amp GIC 1.04. VMR GIC 1.05. Aux Contactors 2 No 2 NC 230V AC L&T 5.06. Add on Block 2 No 2 NC 230V AC L&T 2.07. 16A DP MCB L&T 3.08. 12/24V, 10 Amp DC Battery Charger PCS 3.09. UPS 650 KVA Microtech 1.010. Cooling Fan 6\" Rexnord 4.011. Space Heater with Thermostat Reputed 4.012. DG start/Stop Push Button Esbee 6.013. Auto/Manual Operated Salzer 3.014. Terminal Block - Lot |
| 8 | OUTGOING 2000A 4 Pole ACB - 1 Nos1. 2000A 4 Pole EDO ACB 50KA MP based with O/C, S/C & E/F Protection L&T 2.02. Indicating lamp ON/OFF/TRIP Esbee 3.03. 6A SP Control MCB 10KA C-Curve L&T 3.0 |
| 9 | GENERAL ITEMS:Steel Fabricated Body made out of 2/1.6 mm Thick CRCA Sheet Steel duly Powder Coated ITE 1.02. Alu. Bus bar 2000A with Support duly Heat shrinkable PVC sleeved, Hindalco Lot3. Hardware & Accessories Reputed Lot4. PVC wiring RR Cabel Lot5. Programming ITE |
| 10 | Supply & fixing Earthing complete with copper earth plate electrode 60cm×60cm× 3.15mm thick buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to20×3mm copper strip as earthing lead, by means of bolts, nuts, check nuts and washers ofbrass or steel all as shown in electrical plate No. 3 connected to earthing test point all asspecified or indicated including testing on completionall as specified & directed .Notes:Quoted rates shall be deemed to be included the following (a) Excavation ,RFR earth workin any type of soil. (b) PCC pit in cement concrete 1:3:6 type C-1, pre cast RCC cover40 mm thick in PCC 1:2:4type B-1, reinforced with 8mm dia TMT bars @ 100mm centre to centre both ways with suitable handle made of 10mm dia round bar.(c) funnelwith wire mesh , watering pipe of GI 20 mm nominal bore light grade and lugs etc. complete all as specified & directed. (d) 32 mm nominal bore medium grade GI protection pipe 5 meter long for protection of earthing lead complete all as specified & directed. (e) Requisite quantity of common salt and charcoal in alternative layers as specified. |
| 11 | M&L earth continuity condcutor or main earthing lead fixed to wall on batten or recess or chasses or burried in ground or drawn in conduit / pipe or fixed to poles or any other indicated situation for loop earthing etc 20 x 3mm copper strip complete all as specified and directed. |
| 12 | Supply, laying or passing through pipe LT, XLPE insulated, galvanised steel stripor wire armoured electric power cable conforming to IS:7098 (Pt-I)-1988, heavy duty with stranded aluminium conductor 1100 Volts grade of size 300 Sqmm 3.5 core with necessary fixing arrangements such as lungs, glands and terminal etc including connecting/testing after taking out unserviceable LT UG cable from trenches/ polecomplete all as specified and directed.NOTE: Excavation, earth work shall be measured and paid for separately. |
| 13 | Schedule of Credit (Minus) Rs.16500.00NOTE: Bidder shall insert credit amount of Rs. 16500.00 as ratein Green field under Col-13. |