Tender For Improvement Of Main Electrical Panels & Cables At Mrs.G.L.M.Hospital; 1 Supplying, Installation, testing and commissioning of earth pit of minimum dia. 150 mm size 3 mtr. Deep in hard rock soil, through machine or by any suitable means. Earth electrode consisting of 3 mtr. Long and 80 mm Dia. Size G.I electrode surrounded by highly conductive black fill compound chemical 2 bags (25 kg each) with necessary masonry encloser for 300 mm x 300 mm size GI earth pit cover complete as required. 2 Providing and fixing 25mmX5mm G.I. stripon surface or in recess for connections etc as reqd. 3 Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-3.5C*35 sqmm 4 Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-3.5C*50 sqmm 5 Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-3.5C*70 sqmm 6 Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-3.5C*95 sqmm 7 Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-3.5C*300 sqmm 8 Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-3.5C*400 SQMM 9 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. Upto 35 sq. mm 10 Above 35 sq. mm and upto 95 sq. mm 11 Above 185 sq. mm and upto 400 sq. mm 12 Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Upto 35 sq. mm (clamped with 1mm thick saddle) 13 Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) 14 Above 185 sq. mm and upto 400 sq. mm (clamped with40x3mm MS flat clamp) 15 Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. Upto 35 sq. mm (clamped with 1mm thick saddle) 16 Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mmMS flat clamp) 17 Above 185 sq. mm and upto 400 sq. mm (clamped with40x3mm MS flat clamp) 18 Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc.as required. 150 mm width X 50 mm depth X 1.6 mm thickness 19 300 mm width X 50 mm depth X 1.6 mm thickness 20 Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray bends (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 150 mm width X 50 mm depth X 1.6 mm thickness 21 300 mm width X 50 mm depth X 1.6 mm thickness 22 Wiring for light point /fan point /exhaust fan point /call ball point with 1.5sq.mm FRLS PVC installed copper conductor single core cable in surface / recessed PVC conduit, with piano type switch phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5sq.mm. FRLS PVC installed copper conductor single core cable etc as required. Group C 23 Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase ACsupply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum ) 24 Supplying, Installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency5%, Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range -5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P.F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), ofmnimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) 18- 22 Watt 25 SITC of metal clad, powder coated, compartmentalized cubical panel board as per CPWD electrical specifications including insulated aluminum bus bars, supports, interconnection, erection of switchgears with depth 30 cm to 60 cm and making provisions for termination of incoming/ outgoing cables/ bus ducting and making foundation etc as required. (Suitable for 630 Amp TP & N) 26 Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminalspreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required 27 © 630 A,50KA,FPMCCB 28 Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminalspreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required