Tender For Providing And Fixing Of Shm Light To Remove The Dark Spot In Salempur Majra , Pradhan Enclave,Burari In Ward No-6 Under Civil Line Zone.; 1 Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt ) as required. 2 Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connection etc. as required 3 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Upto 35 sq. mm 4 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. (a) Upto 35 sq. mm 5 Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part Il complete with fitting and cutting, jointing etc. in the existing trench, complete as required. (a) 63 mm dia (OD-63 mm & ID-51 mm nominal) 6 Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-2C*6 sqmm 7 Providing and fiving name board made of MS Sheet 90x60cm, 1mm thick with frame of MS angle 50x50x6mm, two diagonal braces at the back of the sheet of MS flat 40x6mm, total height of the board above ground level 2.40m, length of legs below ground 0.30m embedded in CC block 1:2:4 (1 cement: 2 coarse sand: 4 graded stone aggregate 20mm nominal size) 30x30x45cm including excavation and removal of surplus earth with in 50m lead, applying priming coat of approved steel primer, painting with synthetic enamel paint of approved quality and lettering with enamel paint of approved colour (one side) as per drawing/direction of Engineer-in-Charge. 8 LED FloodLight, powdercoatedpressurediecastaluminum (Systemlumenefficacy>135 lm/Watt)Supplying,installation,Testing&CommissioningofFloodLight,powdercoatedpressuredie cast aluminum body with built in or separatedriver as per the requirement with Driver efficiency >85%,Input voltage:Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 degto 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P.F.≥0.95,IP-66,IK-10,CRI>80,undervoltageandovervoltage protection, EMI-EMCasper CISPR-15,lenses for beam angle 30 deg 120deg as per the application and the project requirement deg., suitable tiltable fitting, life time (LED,Driver & electrical circuitry) of minimum 50000Burning Hours with 70% of initial Lumenmaintained tilllife ends as perLM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K(AsperANSIBin), SDCM(Standard Deviation ColorMatching) <5, Maximumpowerconsumptionshouldnotmore than thespecified rating and Fixture shall be ofrelevant BIS standardcompletein allrespecti/cconnectionswith1.5sqmmFRLS,PVCinsulated copper conductor single core cable and earthing etc. as required withMinimum 5 year OEM warranty.System lumen efficacy>135lm/Watt output . LM79 & LM80 Test reportfromNABLlab foralltestingrequired forLED fixtures as per BISshall be submitted. Shape size and CCT shall beas approved by Engineer-in-Charge as per requirement. (Thermal management:heatsinkofaluminumhousing such that LED junctiontemperature shall not rise above 90°C). 100 watt 9 Fabrication, Supplying, Installation, testing, Commissioning of 12 metres semi high mast System with its accessories ,Mast shaft shall be in one section, hot dip galvanized 4mm thick(Single dip) Inside & out sides & suitable for wind velocity as per IS 875 part3. There shall be in longitudinal seam weld per section and No circumferential weld. It should also Included accessories For semi High Mast head frame 2 point suspension system, 5 X 2.5 sqmm Copper conductor with steel wire rope 5mm dia. (7/19 construction) single drum winch, galvanized lantern carriage arrangement suitable for 4/6 Nos. Flood Light luminaries symmetrically and its control gears boxes and lighting finial, the mast shall have integral type manual tool mounted at the base compartment of its raising and lowering operation with foundation bolts and bolts and Anchor plate and control panel housing suitable RCC (1:2:4) shallow foundation of size 1m(L) x im wide and 2m deep l/c excavation of earth, providing cutting, bending and placing in position, reinforcement of cold twisted bars of 12 mm dia 2100mm long (approx.) 16 nas.and reinforcement of cold twisted bar of 8 mm dia 3700 mm (approx.) 13 nos. (with 150 mm spacing) as required with positioning of foundation bolts and providing DWC HOPE pipe for cable entry & exit as required for the sem high mast considering the safe toil bearing capacity at site as 107/sqm at 2mts. Depth with all material /c 4 Nos SP MСВ, 1 по Double pole 16Amp. MCB etc as rend Logo/Name of manufacturer shall be elther embossed or Rivited plate on the pole. Galvanization as per relevant 15.