| 1 | Taking down existing energy meters carefully from existing meter box after disconnecting the power supply by deploying of skilled manpower, carefully opening connection from terminals and depositing in E/M stores for safe custody. Also ensure proper database w.r.t. locations of meters alongwith it\"s final readings before effecting disconnectionof the meters & being removed from wall and providing the same to MES for final settlement for all the meters complete all as directed. |
| 2 | Supply , installation, testing and comission of Smart energy prepaid Meter confirming to IS-16444: 2015 (Reaffirmed 2020) and as ammended time to time, AC whole current,single phase, 2 wires Smart Energy Meter of rating 240 Volt, 5/10-60 Amps,50 Hz , Class 1, enclosed in polycarbonate box complete as specified in CEA notification. The meter shall communicate with Head End System (HES) on any of the communication technologies mentioned in IS-16444 Part-I . The selection of communication technology should be as per the site conditions and as per design consideration of AMI Implementing agency to meet the performance. The smart meters should be based on RF Mesh communication technology or Cellular communication technology and carry minimum 5 years warranty from the date of activation complete all as directed. |
| 3 | Supply , installation, testing and comission of Smart energy prepaid Meterconfirming to IS-16444: 2015 (Reaffirmed 2020) and as ammended time to time, AC whole current, three phase, 4 wires Smart Energy Meter of rating 415 Volt, 10-100 Amps,50 Hz , Class 1, enclosed in polycarbonate box complete as specified in CEA notification. The meter shall communicate with Head End System (HES) on any of the communication technologies mentioned in IS-16444 Part-I. The slection of communication technology should be as per the site conditions and as per design consideration of AMI Implementing agency to meet the performance. The smart meters should be based on RF Mesh communication technology or Cellular communication technology and carry minimum 5 years warranty complete all as directed. |
| 4 | Supply , installation, testing and comission of Smart energy Meter(IS-16444), AC whole current,three phase, 4 wires, CT operated Smart Energy Meter ofClass 0.5 S ,415 V, 50 Hz, 1b 5Acomplete all as specified. The meter shall communicate with Head End System (HES) on any of the communication technologies mentioned in IS-16444 Part-I in a secure manner . The selection of communication technology should be as per the site conditions and as per design consideration of AMI Implementing agency to meet the performance. The smart meter should be based on RF Mesh communication technology or Cellular communication technology.The meter shall be provided with transparent polycarbonate ABS thermoplastic box with sealing arrangements of suitable size as per the requirement of OEM of Electric meter. The cost of meter should include the supply of current transformer, Rated burden 15 VA, Accuracy class 0.5 S, frequency 50 Hz and voltage class 660V effectively earthed and CT ratio suitable as (60/5 to 1000/5) complete all as directed.Note for serial item No. 02 to 04: (i)Bidder shall procure meter from three different manufacturer having minimum quantity of any one make shall not beless than 30% of total meter.(ii) Smart energy prepaid meter shall meet minimum specification criteria as per perticular specification , scope of work and technical specification.(iii) Bidder shall provide replacement warranty of 5 years from the date of activation of smart energy meter for any type of defect / fault/ error in reading / non functioning of smart feature.(iv) The smart energy meter shall not have built in soft keys for recharging through token system. (v) The cost of SIM deemed to be included in the quoted rate. |
| 5 | Recurring Monthly Sim charges (GPRS/Internet and SMS charges) to be paid to existing AMISP in the station , post commissioning and activation of smart energy meter for 06 month period or till time of succesful integration with existing AMISP. Note :(i) The meter SIM shall be capable to communicate with existing AMISP in the station and shall be integrated with existing HES and MDM network in the station.(ii) Recurring monthly payment may be claimed by contractor monthly basis. |
| 6 | Material and labour for sub main wiring with two single core 6.0 Sqmm FRLS, ISI marked PVC insulated multi stranded, unsheathed copper conductor cable and one single core unsheathed FRLS , ISI marked, PVC insulated multistranded copper conductor cable of size 6.0 Sqmm green colour as earth lead including PVC conduit/ flexible conduit or casing capping of suitable size lugs /ferrel for connection includingtaking down old existing unserviceable one complete all as directed.Note:Two run of 6.0 Sqmm cable ,one runof earth wire of 6.0 Sqmmand one run of PVC conduit/ flexible conduit or casing capping shall be measured as one length. |
| 7 | Material and labour for sub main wiring with four single core 6.0 Sqmm FRLS, ISI marked PVC insulated multi stranded, unsheathed copper conductor cable and one single core unsheathed FRLS , ISI marked, PVC insulated multistranded copper conductor cable of size 6.0 Sqmm green colour as earth lead including PVC conduit/ flexible conduit or casing capping of suitable size lugs /ferrel for connection includingtaking down old existing unserviceable one complete all as directed.Note:Four run of 6.0 Sqmm cable ,one runof earth wire of 6.0 Sqmmand one run of PVC conduit/ flexible conduit or casing capping shall be measured as one length. |
| 8 | M&L for Sub main wiring with two run single core 1.5 Sqmm FRLSH copper conductor cable PVC insulated, unsheathed, 1100 V including 20 mm diaconcealed on wall/ceiling inISI markedwith all accessories such as Tees, elbows, junction boxes etc, as required fixed on wall alongwith one run of1.5 Sqmm single core PVC FRLSH insulated unsheathed copper conductor cable as continuous earth wire and connecting to main switch board / distribution board and testing on completion complete all as specified and directed.Note : Two runs of 1.5 sqmm and one run of 1.5 sqmm cable and one run of PVC conduit shall be measured as one RM. |
| 9 | M&L for concealed point wiring with PVC insulated unsheathed multistranded FRLS copper conductor in PVC conduitwith cable 1.5 Sqmm size 1100 volts grade conforming to IS:694 and terminate to flush box of required size suitable for mounting modular switches and sockets including single core multi stranded FRLS copper conductor 1.5 Sqmm PVC insulated cable as earth wire connected to earth and common earth dollydrawn in same concealed conduit for one light controlled by one, one way switch complete all as specified and directed. |
| 10 | S&F 35/36 watt, (2\" x2\") Recessed/Surface Mounted square luminaire made of CRCA & with single piece molded polycarbonate diffuser. The diffuser shall be so designed that it deos not protude below the luminaire/ceiling & is able to give more volumetric light & higher vertical illumination. The luminaire shall be so desiged that it emits light from the inner side walls of the luminaires & shall be hollow from centre.The hollow portion of the luminair should an option to be covered with customizable backplate or un-cut grid ceiling tile.Luminaire shall deliver minimum system lumens of 3910lumens with a system luminous efficacy ≥135 lm/W, system wattages ≤ 34W & integral module with lumen efficacy of ≥140lm/W and viewing angle of 120°to ensure better uniformity.Itshould have CCT of 5700KCRI ≥ 80,SDCMs. The life shall be L70850@ 50K Hrs. The luminaire driver shall have THD≤10% @ full load,PF ≥ 0.90@ full load, internal surge protection of 2KV,operating voltage range of 140V-270V.The luminaire shall have serviceability of Class B. The luminire shall be IP20 compliant. The fixture design should be with flicker free operation having ripple ≤ 5% the LED driver should comply to IEC61000.3.2,2009 for Harmonics, IEC61347-2-13, 2006 IN Conjuction WITH IEC61347-1 ED 2.0, 2007 for Electrical safety, CISPR 15/EN 55015 (9 khZ TO 30MHz) for RFI, EMI/EMC, IEC 62384 for driver performance test. The luminaire driver shall have efficiency of ≥85%. The luminaire driver shall be of the same make /manufacturer/ brand as that of LED luminaires. The luminaire & driver shall have BIS registration & the bidder shall submit the BIS certificate along with technical BID. The LED luminaire manufacturer should have in-house NABL accredited lab to conduct type test, factory acceptance test before dispatch of material,LM79 test & IK test.The bidder shall submit the NABL accreditation of LED luminaire manufacturer alone with technical bid. The bidder shall submit the type test of luminaires & LM79 test reports issued by NABL accredited lab before supply of material complete all as specified and directed. |
| 11 | S&F Bldg security light fittings high-quality group control enabled integrated LED Building security Light withsystem wattage not exceeding 20W with a nominal system efficacy of 135 lumen/watt. The LED used shall have CCT of 5700K, SDCM ≤ 5 and CRI≥70. The housing should be made of LM6/ADC12 Alloy, non-corrosive Single Piece pressure die-cast aluminum, to withstand extreme environments. The spigot shall be part of “Single Piece Pressure Die-cast housing” & shall not be bolted to the luminaire housing to ensure robust design. The name of the brand should be embossed/engraved & should not be mentioned using sticker/screen printing. It should have corrosion resistant powder coating to pass NSS of 500 Hrs. The luminaire LED shall have declared Lifetime of 75K hours@L70. The product should be designed for continuous operation (10-12 Hrs. per day). The Ingress protection should be minimum IP66 & impact resistance shall be IK10.Control gear compartments shall be Top maintainable without accessing/opening the optical compartment. The Luminaire should have a minimum 20 KV/10KA SPD duly bolted in the Luminaire. The SPD should be able to sustain a minimum 15 hits of 10KA rating i.e. Total of 45 hits across all the three modes as per IEEE 62.41.2. The luminaire should be of Class B Serviceability. The LED used in the luminaire shall be SMD type only & shall be from either Lumileds, Osram, Nichia, Cree & APT Electronics make or equivalent. The Driver should be asphalt potted & should be a BIS approved driver. The driver shall have operating voltage of 120V to 270V, PF≥0.95 @ full load, THD≤10% @ full load. The driver should be capable of withstand voltage stress of 440V for 8 Hrs., should have an auto shutdown @ 325V(±15V) and have an auto recovery feature. The driver shall comply to IEC61547 & IEC 61000-3-2.The luminaire driver & it’s SPD shall be of the same make/manufacturer as that of LED luminaires.Luminaire manufacturer must have In-house NABL accredited lab to conduct LM79, Type test as per IS10322 & \"FAT\" before dispatch as per IS 10322. The contractor must submit the NABL accreditation certificate for Luminaire manufacturer along with sample approval. The LED Luminaire & it\"s driver both should be BIS registered. contractor shall submit the following reports before supply of material for approvals: LM79 issued by NABL accredited lab, LM80 issued by LED manufacturer, Type Test report for luminaire as issued by NABL accredited lab, RoHS compliance issued by LED luminaire manufacturer, BIS certificate for LED Luminaire & Driver and including 1.2m long 32mm dia GI pipe light grade bend to shape and fixed using two nos clamps fabricated using MS Flat iron 40x5mm including necessary nut bolts and washers and making electrical connection using 1.5sqmm, 3 core multi-stranded copper conductor PVC insulated and over all PVC sheathed cable form light fitting complete all as specified and directed |