| 1 | Designing, providing, constructing, hydraulic testing, commissioning and giving satisfactory trials of STP for inlet Sewage parameters BOD=300, COD=600, TSS=600, TKN 55, pH= 6.5 to 7.5 based on SBR technology consisting of Inlet Chamber, Screen Chamber, Grit- Detritus Tanks and Biological CASP Basins, Chlorine Contact Tank, Chlorinator with Chlorinator shed & tonner Shed, Chemical Storage & Dosing shed with dosing Equipments, Sludge Sump, Gravity Sludge Thickener cum Sludge dewatering system equipment, sludge storage shed, necessary piping work with required valves, gates, storm water drains and rain water harvesting system, bypass drains, roads & pathways, landscaping, Compound wall with gates, Administration Block cum Laboratory, Laboratory Equipments, Tools and Plants, Spare Parts, ESR (200 KL) and Tanker Filling points, Metering Room, Guard Cabin etc. complete as turnkey job with all involved civil, electrical, instrumentation and mechanical works inclusive of following items, units as per detailed specification for civil, electrical, instrumentation and mechanical components with all duties and taxes, etc. complete to achieve BOD < 10 ppm, COD < 100 ppm, TSS < 10 ppm, to get reusable quality of water for industrial / agricultural purposes. outlet parameters shall also include TN < 10 ppm, Nh3N < 2 ppm and TP < 1 ppm) with full automation including PLC-SCADA, OCMS and Instrumentation, reuse arrangement (storage - OHSR and pumps) and treated effluent disposal line for treated water 1 KM as per specifications. This includesOn line monitoring of Sewage Treatment Plant through Artificial Intelligence including online monitoring system (analyser at Inlet and outlet), DO analysers and Hydrostatic level sensor, DLT, Other necessary instrumentation like flow meter, pressure gauge and accessories to run the complete system in automation. |
| 5 | Design, construction, execution, testing and commissioning of pumping station including but not limited to all relevant civil, electrical, mechanical (including Pumps, motor, valves/gates, screen conveyor, EOT/HOT Crane, suction / delivery or any other piping required etc.), including electro magnetic flowmetre etc. along with ancillary civil works as required as per detailed scope of work and employer\"s requirment as per Tender Document. |