| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 21-11-2025 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 28-11-2025 |
| Sl. No. | Item Description |
| 1 | Disconnecting & Taking out LT underground cable(aluminum/copper conductor of size 6 to 70 sqmm any core from trenches including cable cover,tubes if anyetc complete all as specified as directed by Engineer in Charge. |
| 2 | Disconnecting & Taking out LT underground cable(aluminum/copper conductor of size 95 to185 sqmm any core from trenches including cable cover,tubes if anyetc complete all as specified as directed by Engineer in Charge. |
| 3 | Disconnecting & Taking out HT underground cable(aluminum conductor of size 95-120 sqmm any 3 core from trenches including cable cover,tubes if anyetc complete all as specified as directed by Engineer in Charge. |
| 4 | Note for item No 01-03:-Excavation and earth work will be measurel and paid seperately under respective items in this schedule |
| 5 | Dismantling LT Stay assembly, of any size and unserviceable materials removing from the Site(s), complete all as specified as directed by Engineer in Charge.(Note: (a) Unserviceable Stay assembly shall be taken off/dismantled at Ground Level and making good disturbed ground surface.(b)Earthwork for demolition of cement concrete shall be measured and paid separately under relevant Items of this Schedule.) |
| 6 | M & L for Stay assembly complete with all accessories as shown in electrical plate No 1 of MES Schedule Part I dia of stay rod 16mm with and including 7 / 3.15 mm galvanised stay strand complete all as specified as directed by Engineer in Charge.(Note : Loop insulator, excavation & earthwork and cement concrete measured and paid separately under relevant items of this Schedule.) |
| 7 | Dismantling, taking down removing old unserviceable ACSR conductor from existing HT overhead line with its jumper and binding wire complete all as specified as directed by Engineer in Charge. |
| 8 | Supply and fix ACSR conductor for HT OH line incl binding on insulator with binding wire of squirel / weasal or any other as per site requirments and complete all as specified as directed by Engineer in Charge.Note : 3 %of actual pole to pole distance will be added for sag and binding wire for measuement and Payment purpose. |
| 9 | M&L for preparation painting of HT 2 pole structure applying one coat of synthetic aluminum paint on all poles , channels and cross arms, bracket complete all as specified as directed by Engineer in Charge. |
| 10 | Supply and fix in repalacement from existing HT pole 11KV air break gang operated triple pole mechanically operated mounted on insulators and steel frameVertical / Horizontal type ,with operating mechanism worked from ground level for current rating 200 amps all as directed with locking arrangements and godrej lock 7 levers one Nos complete all as specified as directed by Engineer in Charge. |
| 11 | Material and labour for cutting the existing bituminous road / concrete floor and including returning filling and making good using PCC 1:4:8 type D2 to match with the existing surface complete all as specified as directed by Engineer in Charge. |
| 12 | Taking down old unserviceable Cross arms bracing supports clamps back plate fabricated from structural steel section including nuts bolts washers complete all as specified as directed by Engineer in Charge. |
| 13 | Materail and labour for cross arm bracing supports clamps back plate fabricated from structural steel section incl nuts bolts washers welding bending cold and hot drilling holes in any shape or size as indicated or directed inclusive of one primer coat, one under coat and one finishing coat of aluminium paint complete all as specified as directed by Engineer in Charge. |
| 14 | Dismantling of old unserviceable pin /shackle/loop type insulator complete all as specified as directed by Engineer in Charge. |
| 15 | Supply and fix pin type insulator, porcelain vitreous white brown or green including one galvanised wild steel spindle, two galvanised iron washer and one galvanised iron nut 100 mm height 65mm dia for 1100 volt grade complete all as specified as directed by Engineer in Charge. |
| 16 | Supply and fix of shackle type insulator porcelain vitreous white brown or green 90mm dia and 75mm height including GI strip of 31x3mm size, 12mm dia insulator bolt washer and nut complete all as specified as directed by Engineer in Charge. |
| 17 | M & L for repair/ overhauling of electric panel board including replacement of defective spare/parts such MCCB, MCB, CT, voltmeter, Amp meter, frequency meter, indicator lamps etc including necessary welding to doors, replacement of defective wire, lugs etc and spray painting with one coat of synthetic enamel pait (1st grade quality) complete all as specified as directed by Engineer in Charge.(Note : (i) Spare parts shall be measured and paid seperately as supply only. (ii) The cost of cleaning, painting and replacement of minor spare such as lugs, wire etc shall deemed to be included in the unit quoted rate). |
| 18 | Supply only Digital Voltmeter 0-500 volts with built in selector switch of dial size 96 x 96mm with accuracy class 1.0 including complete all as specified as directed by Engineer in Charge. |
| 19 | Supply only digital ammeter with built in selector switch 0-500 Amps of dial size 96x96mm complete all as specified as directed by Engineer in Charge. |
| 20 | Supply only Neon indicator lamp (RYB) for panle board complete all as specified as directed by Engineer in Charge. |
| 21 | Supply only CT\"s Cast Resin type of ratio 100/5 Amps suitable for electric panel complete all as specified as directed by Engineer in Charge. (Make: AE/L & Tor equivelant of make as per Appx \"B\") |
| 22 | Servicing cleaning painting of oil cooled voltage stablizer of capacity 100-300 KVA including opening, checking and replacing line unserviceable and defective electrical parts and make the stablizer serviceable, minor components like wire, capacitor is including in the cost of repair as directedby Engineer in Charge. |
| 23 | Supply and fixing in repairMultifunction meter of 200A capacity, having voltage indication, Amp indication, p and power indication for bothLL and L-N with connections in existing LT panel/AMFpanel complete all as specified as directed by Engineer in Charge. |
| 24 | Surface cleaning / dressing by removing the roots completely from the earth, shrubs, vegetation, grass, bushes, weeds in soft loose soil , trimming of trees around 1m radius of street light or HT pole, fencing etc from E/M installations complete all as specified as directed by Engineer in Charge. Note:- This item shall be executed for cleaning of surrounding area of various E&M installation. |
| 25 | Supply & laying XLPE insulated, PVC inner sheathed, armoured with galvanised steelstrip or wire, heavy duty, LT underground cable, with aluminium conductor 1100 volt grade of size 6 Sqmm 2 core laid in trenches / duct/ road passing through pipe / duct or fixed on pole and connecting with new lugs and washer bolt tape necessary items and testing etc complete all as specified as directed by Engineer in Charge. |
| 26 | Supply & laying XLPE insulated, PVC inner sheathed, armoured with galvanised steelstrip or wire, heavy duty, LT underground cable, with aluminium conductor 1100 volt grade of size 10 Sqmm 2 core laid in trenches / duct passing through pipe / duct or fixed on pole and connecting and testing etc complete all as specified as directed by Engineer in Charge. |
| 27 | Supply & laying XLPE insulated, PVC inner sheathed, armoured with galvanised steelstrip or wire, heavy duty, LT underground cable, with aluminium conductor 1100 volt grade of size 10 Sqmm 4 core laid in trenches / duct passing through pipe / duct or fixed on pole and connecting and testing etc complete all as specified as directed by Engineer in Charge. |
| 28 | Supply & laying XLPE insulated, PVC inner sheathed, armoured with galvanised steelstrip or wire, heavy duty, LT underground cable, with aluminium conductor 1100 volt grade of size 16 Sqmm 4 core laid in trenches / duct passing through pipe / duct or fixed on pole and connecting and testing etc complete all as specified as directed by Engineer in Charge. |
| 29 | Supply & laying XLPE insulated, PVC inner sheathed, armoured with galvanised steelstrip or wire, heavy duty, LT underground cable, with aluminium conductor 1100 volt grade of size 25 Sqmm 4 core laid in trenches / duct passing through pipe / duct or fixed on pole and connecting and testing etc complete all as specified as directed by Engineer in Charge. |
| 30 | Supply & laying XLPE insulated, PVC inner sheathed, armoured with galvanised steelstrip or wire, heavy duty, LT underground cable, with aluminium conductor 1100 volt grade of size 35 Sqmm 3.5 core laid in trenches / duct passing through pipe / duct or fixed on pole and connecting and testing etc complete all as specified as directed by Engineer in Charge. |
| 31 | Supply & laying XLPE insulated, PVC inner sheathed, armoured with galvanised steelstrip or wire, heavy duty, LT underground cable, with aluminium conductor 1100 volt grade of size 50 Sqmm 3.5 core laid in trenches / duct passing through pipe / duct or fixed on pole and connecting and testing etc complete all as specified as directed by Engineer in Charge. |
| 32 | Supply & laying XLPE insulated, PVC inner sheathed, armoured with galvanised steelstrip or wire, heavy duty, LT underground cable, with aluminium conductor 1100 volt grade of size 70 Sqmm 3.5 core laid in trenches / duct passing through pipe / duct or fixed on pole and connecting and testing etc complete all as specified as directed by Engineer in Charge. |
| 33 | Supply & laying XLPE insulated, PVC inner sheathed, armoured with galvanised steelstrip or wire, heavy duty, LT underground cable, with aluminium conductor 1100 volt grade of size 120 Sqmm 3.5/4 core laid in trenches / duct passing through pipe / duct or fixed on pole and connecting and testing etc complete all as specified as directed by Engineer in Charge. |
| 34 | Supply & laying XLPE insulated, PVC inner sheathed, armoured with galvanised steelor wire heavy duty,HT underground cable(earthened grade) with aluminium conductor 11000 voltgrade of size 95 Sqmm 3 core laid in trenches/duct passing through pipe/duct or fixed on pole and connecting and testing etc complete all as specified as directed by Engineer in Charge. |
| 35 | Supply and fixing in replacementof change over switch board 250 A, 415V on wall/or on angle iron support with nut bolt ad washer including connections complete all as specified as directed by Engineer in Charge. |
| 36 | Supply, jointing, connecting and testing, straight through joint, epoxy based complete with jointing material and all standard accessories suitable for XLPE insulated armoured aluminium conductor cable, LT 1100 Volts, aluminium conductor of 3.5/4 core, 16-35 Sqmm complete all as specified as directed by Engineer in Charge. |
| 37 | Supply, jointing, connecting and testing, straight through joint, epoxy based complete with jointing material and all standard accessories suitable for XLPE insulated armoured aluminium conductor cable, LT 1100 Volts, aluminium conductor of 3.5 core, 50-95 Sqmm complete all as specified as directed by Engineer in Charge. |
| 38 | Supply, jointing, connecting and testing, straight through joint, epoxy based complete with jointing material and all standard accessories suitable for XLPE insulated armoured aluminium conductor cable, LT 1100 Volts, aluminium conductor of 3.5/4 core, 120 to 185 Sqmm complete all as specified as directed by Engineer in Charge. |
| 39 | Supply, jointing, connecting and testing, straight through joint, epoxy based complete with jointing material and all standard accessories suitable for XLPE insulated armoured aluminium conductor cable, LT 1100 Volts, aluminium conductor of 3.5 core,240 to 300 Sqmm complete all as specified as directed by Engineer in Charge. |
| 40 | Supply, jointing, connecting and testing, straight through joint, epoxy based complete with jointing material and all standard accessories suitable for XLPE insulated armoured aluminium conductor cable, LT 1100 Volts, aluminium conductor of 3.5/4 core,400- 630 Sqmm complete all as specified as directed by Engineer in Charge. |
| 41 | Excavation in trenches not exc 1.5 m wide and n.exc 1.5m in depthfor foundation / fixing pole / laying cable and pipe line etc or for man hole etc not exc 10 sqm on plan and getting out in soft / loose soil complete all as specified as directed by Engineer in Charge. |
| 42 | Returning filling in including spreading leveling, watering and well ramming in layers not exc 25 cm thick using suitable excavated soft / loose soil complete all as specified as directed by Engineer in Charge. |
| 43 | Removing excavated soil to a distance exc 50 m but n.exc 100 m and depositing where directed at a level n.exc 1.5m above the starting point complete all as specified as directed by Engineer in Charge. |
| 44 | M&L for providing dry river sand 18mm thick as in sand cushioning to under ground PVCcable including punning down of sand in layer complete all as specified as directed by Engineer in Charge. (Note: for measurement purpose any punned thickness of sand will be considered.) |
| 45 | Supply & laying ISI marked & conforming toIS- 5820- 1970 unreinforcedprecast concrete cable coverClass LV , Type I, flatsize 250 mm X 150 mm X40 mm in trenches as protection toLT UG cable complete all as specified as directed by Engineer in Charge. |
| 46 | Laying only PCC cable cover for LT/HT UG cable, of any description retrieved from item No 1 to 3, complete all as specified as directed by Engineer in Charge. |
| 47 | supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable ofsize 50 to 95 sqmm complete all as specified as directed by Engineer in Charge. |
| 48 | supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable ofsize 50 to 95 sqmm complete all as specified as directed by Engineer in Charge. |
| 49 | supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable ofsize 50 to 95 sqmm complete all as specified as directed by Engineer in Charge. |
| 50 | Supply, fix in repair digitalprogrammable Time Switch 24 HOURSof supply voltage 220-240 Volts AC, 50/60 HZ complete all as specified as directed by Engineer in Charge.Make :-GIC,selec,hager or equivalent as approved by GE. |
| 51 | S&F in repair 7 Watt LED spike LightIP 67 water proof enclosure, off white color, fixed in position & connecting complete all as specified as directed by Engineer in Charge. Make Havells/Crompton/Philips |
| 52 | Supply and fix in repair MCCB 40-63 Amp, three Pole, breaking capacity 10-16KA, 415 V - 50 Hz, fixed in existing panel & connecting complete all as specified as directed by Engineer in Charge. |
| 53 | Supply and fix in repair MCCB 100 Amp, Three Pole, breaking capacity 16 -25KA, 415 V - 50 Hz, with adjustable thermal and magnetic settingfixed in existing panel & connecting complete all as specified as directed by Engineer in Charge. |
| 54 | Supply and fix in repair MCCB 125 Amp, Three Pole, breaking capacity 16-25 KA, 415 V - 50 Hz, with adjustable thermal and magnetic settingfixed in existing panel & connecting complete all as specified as directed by Engineer in Charge. |
| 55 | Supply and fix in repair MCCB 160 Amp, Four Pole, breaking capacity 25-36KA, 415 V - 50 Hz, fixed in existing panel & connecting complete all as specified as directed by Engineer in Charge. |
| 56 | Supply and fix in repair MCCB 200 Amp, Four Pole, breaking capacity 35 /36 KA, 415 V - 50 Hz,with adjustable thermal and magnetic setting fixed in existing panel & connecting complete all as specified as directed by Engineer in Charge. |
| 57 | Supply and fix in repair MCCB 400 Amp, Four Pole, breaking capacity 35 KA, 415 V - 50 Hz,with adjustable thermal and magnetic setting fixed in existing panel & connecting complete all as specified as directed by Engineer in Charge.Make:- Havells/C&S/ABB |
| 58 | S&F in replacement of 4 Pole 250 Amp power contactor,AC 3 rating, fixed in existing panel & connecting complete all as specified as directed by Engineer in Charge.Make : - SIEMENS/LARSEN & TUBRO/LEGRAND/ SCHNEIDER/HAVELLS India LTD/C & S ELECTRIC LIMITED (C&S) / CROMPTON GREAVES/GE/ABB/HPC |
| 59 | S&F in replacement of 4 Pole 60-80 Amp power contactor,AC 3 rating, fixed in existing panel & connecting complete all as specified as directed by Engineer in Charge.Make : - SIEMENS/LARSEN & TUBRO/LEGRAND/ SCHNEIDER/HAVELLS India LTD/C & S ELECTRIC LIMITED (C&S) / CROMPTON GREAVES/GE/ABB/HPC |
| 60 | S&F in replacement of 4 Pole 32 to 40 Amp power contactor,AC 3 rating, fixed in existing panel & connecting complete all as specified as directed by Engineer in Charge.Make : - SIEMENS/LARSEN & TUBRO/LEGRAND/ SCHNEIDER/HAVELLS India LTD/C & S ELECTRIC LIMITED (C&S) / CROMPTON GREAVES/GE/ABB/HPC |
| 61 | S&F in replacement of 4 Pole 9-12Amp power contactor,AC 3 rating, fixed in existing panel & connecting complete all as specified as directed by Engineer in Charge.Make : - SIEMENS/LARSEN & TUBRO/LEGRAND/ SCHNEIDER/HAVELLS India LTD/C & S ELECTRIC LIMITED (C&S) / CROMPTON GREAVES/GE/ABB/HPC |
| 62 | Supply and fixing in replacement ofBollard light 9W,CCT-3000K height 0.6mwith bolts or with PCC Foundationcomplete all as specified as directed by Engineer in Charge. Make Bajaj cat no BGBOL 1000 9W LED WW or Equivalent |
| 63 | Supply and fixing in replacement ofBollard light 9W,CCT-3000K height 1mwith bolts or with PCC Foundation complete all as specified as directed by Engineer in Charge. Make bajaj cat no BGBOL 1000 9W LED WW or Equivalent |
| 64 | Material and Labour forServicing and cleaning of solar panels of street light checking out connections the existing solar street light complete all as specified as directed by Engineer in Charge. |
| 65 | M&L for repair/ maintenance of APFC capacitor bank panel board upto 150 KVAR with 5/6 stage by checking of fault, weakness of capacitor and removing of fault including replacement of spare items complete including testing for proper automatic functioning complete all as specified as directed by Engineer in Charge.Note:- (a)Spare items required for repair/ maint shall be measured seperately under respective items.(b) Cost of minor parts such as nut, bolt, washers, screw etc are deemed to be included in quoted rate. |
| 66 | supply only in repalcement of dry type cylindrical capacitior of rating 10-12 KVAr, 440volt suitable for APFC panel complete all as specified as directed by Engineer in Charge. |
| 67 | supply only in repalcement ofdry type cylindrical capacitiocylindrical capacitior of rating 5-6 KVAr, 415 volt suitable for APFC panel complete all as specified as directed by Engineer in Charge. |
| 68 | Supply only in replacement of power factor controller 30-525 volts (mean voltage), 230 volts (supply voltage), 50 Hz, 6 step, 3 phase complete all as specified as directed by Engineer in Charge.Make: Epcos/ L&T/ Siemens |
| 69 | Suplly only in repair selector switch complete all as specified as directed by Engineer in Charge. |
| 70 | supply only in repair push button on/off green or red colour complete all as specified as directed by Engineer in Charge. |
| 71 | servicing and repair of High mast panel including cleaning of panel checking and repairing of wiring , greasing and testing of motor and wire , changing of burnt auxilary contacts,change of capacitorconnections of cable etc complete all as specified as directed by Engineer in Charge. |
| 72 | supply only for repalcement of capacitor 3pole, upto 10mfd 440volt 50Hz suitable for APFC panel complete all as specified as directed by Engineer in Charge. |
| 73 | Supply and fix in repair dangerplate size 250mmx200mm mild steel ,1.6mm thick and vitreous enamelled white ,with letters,figures and conventional skull, and cross bones in signal red colur on front sideby means of screws bolts or clamps written 11000Volt ,and Danger in bold by red color in English and hindi language as per IS 2551-1982 complete all as specified as directed by Engineer in Charge. |
| 74 | Supply and fix in repair dangerplate size 150mmx200mm mild steel ,1.6mm thick and vitreous enamelled white ,with letters,figures and conventional skull, and cross bones in signal red colur on front sideby means of screws bolts or clamps written 11000Volt ,and Danger in bold by red color in English and hindi language as per IS 2551-1982 complete all as specified as directed by Engineer in Charge. |
| 75 | Servicing and repair of search lights mounted mounted on roof of guard tower including cleaning, welding, change of cable, repairing of moving handle greasing rotating parts etc complete all as specified as directed by Engineer in Charge.Note: cost of driver replaement will be paid seperatel |
| 76 | Supply and fix in replacement of LED Post-Top lantern,20 watt energy saving, environmental friendly, long life aesthtically designed with symmentrical light distribution, spun aluminium landscape luminaire with high power LEDs as light source ,suitable for pole size and making complete all as specified as directed by Engineer in Charge. |
| 77 | Supply and fix in replacement ofLED Post-Top lantern,40 Watt energy saving, environmental friendly, long life aesthtically designed with symmentrical light distribution, spun aluminium landscape luminaire with high power LEDs as light source ,suitable for pole size and making arrangements ,pcc work , electric connections complete all as specified as directed by Engineer in Charge. |
| 78 | S&F in replacement of LED Street Light fitting 35 Watt, system efficiency not less than 100 lumen / watt, IP65/66 protection,consisting of high / low voltage cut off, maintenance free isolated Electronic driver circuits, Low THD, PMMA grade high quality Transmittance lens, Epoxy powder coated Die Cast Aluminium housing with weather proof gasket for lamp & driver compartment, Heat resistance toughened glass fitted in cast aluminium housing with SS screws,fixed on existing bracket & connecting complete all as specified as directed by Engineer in Charge. Make wipro cat part no LR02-331-XXX57-XX OR equivalent of crompton/philips/wipro/syska/C&S electric/HPL electric & power Ltd/HELONIX TECHNOLIES. |
| 79 | S&F in replacement of LED Street Light fitting 45 Watt, system efficiency not less than 100 lumen / watt, IP65/66 protection,consisting of high / low voltage cut off, maintenance free isolated Electronic driver circuits, Low THD, PMMA grade high quality Transmittance lens, Epoxy powder coated Die Cast Aluminium housing with weather proof gasket for lamp & driver compartment, Heat resistance toughened glass fitted in cast aluminium housing with SS screws,fixed on existing bracket & connecting complete all as specified as directed by Engineer in Charge. Make wipro cat part no LR02-331-XXX57-XX OR equivalent of crompton/philips/wipro/syska/C&S electric/HPL electric & power Ltd/HELONIX TECHNOLIES. |
| 80 | S&F in replacement of LED Street Light fitting 70 Watt, system efficiency not less than 100 lumen / watt, IP 66 protection, IK 07 impact resistance, consisting of high / low voltage cut off, maintenance free isolated Electronic driver circuits, Low THD, PMMA grade high quality Transmittance lens, Epoxy powder coated Die Cast Aluminium housing with weather proof gasket for lamp & driver compartment, Heat resistance toughened glass fitted in cast aluminium housing with SS screws,fixed on existing bracket & connecting complete all as specified as directed by Engineer in Charge. |
| 81 | S&F in replacement of LED Street Light fitting 90 Watt, system efficiency not less than 100 lumen / watt, IP 66 protection, IK 07 impact resistance, consisting of high / low voltage cut off, maintenance free isolated Electronic driver circuits, Low THD, PMMA grade high quality Transmittance lens, Epoxy powder coated Die Cast Aluminium housing with weather proof gasket for lamp & driver compartment, Heat resistance toughened glass fitted in cast aluminium housing with SS screws,fixed on existing bracket & connecting complete all as specified as directed by Engineer in Charge. |
| 82 | S&F in replacement ofLED flood Light fitting 100 Watt, system efficiency not less than 100 lumen / watt, IP 66 protection, IK 07 impact resistance, consisting of high / low voltage cut off, maintenance free isolated Electronic driver circuits, Low THD, PMMA grade high quality Transmittance lens, Epoxy powder coated Die Cast Aluminium housing with weather proof gasket for lamp & driver compartment, Heat resistance toughened glass fitted in cast aluminium housing with SS screws fixed on existing bracket & connecting, complete all as specified as directed by Engineer in Charge. |
| 83 | S&F in replacement ofLED flood Light fitting 200-210 Watt, system efficiency not less than 100 lumen / watt, IP 66 protection, IK 07 impact resistance, consisting of high / low voltage cut off, maintenance free isolated Electronic driver circuits, Low THD, PMMA grade high quality Transmittance lens, Epoxy powder coated Die Cast Aluminium housing with weather proof gasket for lamp & driver compartment, Heat resistance toughened glass fitted in cast aluminium housing with SS screws fixed on existing bracket & connecting, complete all as specified as directed by Engineer in Charge. |
| 84 | Supply and fix in repair bracket made outof 40mm GI pipe medium grade of length1.5mtr and bend to shape for fixing of street light fitting including three Nos of FI 32x6mm clamps with suitable nuts and bolts complete all as specified as directed by Engineer in Charge. |
| 85 | Taking out and refixing of interlocking tiles from groundcomplete all as specified as directed by Engineer in Charge. |
| 86 | M&L for demolition of cement Concrete in ground floors and pavings etcn exc 15 cm thickness (below or above ground level) complete all as specified as directed by Engineer in Charge. |
| 87 | M&L Cement concrete type B- 2, 1:2:4 (40mm graded aggregate) for 100 mm thicknes complete all as specified as directed by Engineer in Charge. |
| 88 | M&L Cement concrete type B- 2, 1:3:6(40mm graded aggregate)complete all as specified as directed by Engineer in Charge. |
| 89 | Supply & fix inreplacement round, 2 core cable, PVC insulated and PVC sheathed, Aluminium conductor of size 2.5 Sqmm,for electric connection from feeder / looping box / street light over head line to street light fitting complete all as specified as directed by Engineer in Charge. |
| 90 | S&F in repair Sheet moulding compound (SMC) junction box of size 240 mm x 130 mm x 110mm, comprising three phase aluminumbus bar and one No MCB SP, 06 Amps C type, fixed on pole with mild steel clamps, nuts and bolts complete all as specified as directed by Engineer in Charge. |
| 91 | Supply and fix / laid in wall/trenches Road 50 mm bore galvanised steel water tubing,light grade for laying cable of suitable size complet including taking down old pipe complete all asspecified and as directed by Engineer-in-Charge. |
| 92 | Supply and fix in replacement MCBs SPN40 -63Amps, 415 volts with ‘C’ curve, fixed in sheet metal board complete all as specified as directed by Engineer in Charge. |
| 93 | Supply and fix in replacement MCBssingle pole & neutral , 6 to 32 Amps, 230 volts with ‘C’ curve, fixed in sheet metal board complete all as specified as directed by Engineer in Charge. |
| 94 | Supply and fix in replacement MCBssingle pole , 6 to 32 Amps, 230 volts with ‘C’ curve, fixed in junction box/sheet metal board complete all as specified as directed by Engineer in Charge. |
| 95 | Supply and fix in replacement MCBstriple pole , 6-32Amps, 415 volts with ‘C’ curve, fixed in sheet metal board complete all as specified as directed by Engineer in Charge. |
| 96 | Supply and fix in replacement MCBstriple pole & neutral , 6-32Amps, 415 volts with ‘C’ curve, fixed in sheet metal board complete all as specified as directed by Engineer in Charge. |
| 97 | Supply and fix in replacement MCBstriple pole & neutral , 40-63 Amps, 415 volts with ‘C’ curve, fixed in sheet metal board complete all as specified as directed by Engineer in Charge. |
| 98 | S&F in repair 10/18 watt CFL , 2 pin/4 pin , 230 V, 50 HZ suitable for garden bollard light complete all as specified as directed by Engineer in Charge. |
| 99 | S&F in repair electromagnetic ballast, for 18 watt CFL, 230 V, 50 HZ complete all as specified as directed by Engineer in Charge. |
| 100 | Supply, install, testing and commissioning and testing in replacement factory made and tested (including CPRI type test certified) LT bus bar Chamber boxoutdoor type, platform mounted, suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, having Incomer - 100A,4P,25Ka MCCB rating and outgoingbus bar chamber for 4 Nos of 4 core cable runs with insulated Aluminum 4 bus bars 160 amp rated with installed on porcelain insulators.The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet 75mm x 30 mm thickMS Channelframe, duly powder coated finish. Front opening type with aprons for cable entry with double door shutter and locking arrangement, danger plate and earthing terminal . The scope of work includes pcc foundation and provision and also fame for mounting Bus bar Chamber complete all as specified as directed by Engineer in Charge. |
| 101 | Supply, install, testing and commissioning and testing in replacementfactory made and tested (including CPRI type test certified) LT feeder pillar box (KIOSK) outdoor type, platform mounted, suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, having bus bar chamber with insulated Aluminum bus bars 320 amps rating installed on porcelain insulators.The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet 75mm x 30 mm thickMS Channelframe, duly powder coated finish. Front opening type with aprons for cable entry with double door shutter and locking arrangement, danger plate and earthing terminal . The scope of work includes pcc foundation and provision of the following :-Incoming(a)MCCB 4 pole 160Amps, 36 KA, 415V-01 Nos(b) Bus bar (Al strip)320 Amp, 4 pole, for in comp supply 01 No(c) Multi function meterl meter including CTs -01 No.Outgoing(d) MCCB TPN 63 amp 16 KA, 415 V 50 Hz - 03 No. |
| 102 | (e)(d) MCCB - TPN 63 Amp,4 pole-01 ,auto street light Timer switch(GIC/hager)-01, slector switch-01, on/off push button-02 and on off indicator light ,contactor 60A, - 01 No. Existing cable (For various Bldg supply cable of sizes ) connect with busbar properly with suitable size copper Lug . |
| 103 | S&F in repair electronic drivers suitable for 25-46watt LED street light fitting, fixed in position & connecting complete all as specified as directed by Engineer in Charge. |
| 104 | S&F in repair electronic drivers suitable for 70-100 watt LED street light fitting, fixed in position & connecting complete all as specified as directed by Engineer in Charge. |
| 105 | S&F in repair electronic drivers suitable for 120-150 watt LED street light fitting, fixed in position & connecting complete all as specified as directed by Engineer in Charge. |
| 106 | S&F in repair electronic drivers suitable for 200-250 watt LED street light fitting, fixed in position & connecting complete all as specified as directed by Engineer in Charge. |
| 107 | HT/LT fault detection by Fault testing by fault testing maching exacavating detected site and rectifying the cable fault by Jointing kit , Supply and fixing of Jointing kit will be measured separately complete all as specified as directed by Engineer in Charge. |
| 108 | M&L for preparation of old painted surface of steel tubular pole 9 meter long & applying one coat of aluminium paint on exposed surface, painting of band in alternate strip of 0.25 meter each with yellow & black synthetic enamel paint up to 1.5 meter height above PCC coping, including writing pole No with black synthetic paint complete all as specified as directed by Engineer in Charge. |
| 109 | Deployment of manpower, instrument, tools, and all connected accessories for testing of earth resistance of existing earthing at provided earth test point for each earth set by competent calibrated digital earth test meter electronic type along with accessories (earth rod set with Cu wire with clips) and recording the result dully signed with date by MES representative and contractorcomplete all as specified as directed by Engineer in Charge.NOTE:- Testing of each earthing shall be carried out at the interval of 1 months and measurement shall be carried each time separately and test result shall be maintained dully signed with date by MES representative and contractor. |
| 110 | M &LPCC earthpitin PCC 1:2:4 type B-1 and RCC 1:2:4, type B1 for precast chamber cover 50 mm thick, reinforced with welded steel wire fabric or XPM Jali (weight not less than 4.00 Kg / sqm) with disconnecting and connecting existing earth lead or strip including taking out broken pit and surface dressing complete all as specified as directed by Engineer in Charge. |
| 111 | Supply and fix in repair Heavy duty poly plastic Earth pit cover of HDPE material, green color,Bottom diameter ( OD 320 mm / ID 290 mm) of wall thickness 5 mm ,height 260 mm with top cover and grouted with the use of concrete along the pheriphery of eart pit complete all as specified as directed by Engineer in Charge. |
| 112 | Supply and pouring Earthing Soil Resistivity improvement compound Gel, Enhancement compound Transparent Liquid Jel in 5 Kg packing complete all as specified as directed by Engineer in Charge.Make -JJ Engineering / SM Infotech / Powertack |
| 113 | M&L for Brazing of copper strip using brazing touch suitable temp and using brazing rod complete all as specified as directed by Engineer in Charge. |
| 114 | Supply and fixingcopper strip 32X6 earth strip of size with epoxy insulators and fixing screws etc for earth continuity conductors to test point terminals to test point terminal including taking down old strip complete all as specified as directed by Engineer in Charge. |
| 115 | Supply and fixing in repair GI strip 32X6 earth strip of size mm with epoxy insulators and fixing screws etc for earth continuity conductors to test point terminals to test point terminal including taking down old strip complete all as specified as directed by Engineer in Charge. |
| 116 | Supply and fixing in repair copper earth strip of size 20X3mm with epoxy insulators and fixing screws etc for earth continuity conductors to test point terminals to test point terminal including taking down old strip complete all as specified as directed by Engineer in Charge. |
| 117 | Supply and fixing in repair copper earth strip of size 25 x 4 mm with epoxy insulators and fixing screws etc for earth continuity conductors to test point terminals to test point terminal including taking down old strip complete all as specified as directed by Engineer in Charge. |
| 118 | supply and Fixing only in repairnew epoxy insulators on loomingexisting copper/GI earth strip of any sizewith at distance of 1m and fixing screws etc for earth continuity conductors on roof /wall to test point terminals ncluding taking down old strip complete all as specified as directed by Engineer in Charge. |
| 119 | Material and labour of earthing complete with galvanised earth plate electrode 600 mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m deep below normal ground connected toGI strip of size 32x6 mm by means of bolts nuts check nuts and washer of galvanized steel, watering pipe of 20 mm bore, galvanised iron, light grade, and 40 mm bore galvanised iron light grade for earth wire protectionincluding all excavation earth work in any type of soil, PCC pit in PCC 1:2:4 type B-1 and RCC 1:2:4, type B1 for precast chamber cover 50 mm thick, reinforced with welded steel wire fabric or XPM Jali (weight not less than 4.00 Kg / sqm),with charcoal, salt, funnel complete all as shown in the electrical plate No 3 of SSR part –I and testing on completion including taking down old earth pit complete all as specified as directed by Engineer in Charge. Note:-Quoted rates shall be deem to include for earth strip with protection pipe up to 7.5 M length. |
| 120 | Material and labour in replacement of earthing complete with copper earth plate electrode 600 mm x 600 mm x 3.15 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m deep below normal ground connected tocopper strip of size 20 mm x 3 mm by means of bolts nuts check nuts and washer of galvanized steel, watering pipe of 20 mm bore, galvanised iron, light grade, and 40 mm bore galvanised iron light grade for earth wire protectionincluding all excavation earth work in any type of soil, PCC pit in PCC 1:2:4 type B-1 and RCC 1:2:4, type B1 for precast chamber cover 50 mm thick, reinforced with welded steel wire fabric or XPM Jali (weight not less than 4.00 Kg / sqm),with charcoal, salt, funnel complete all as shown in the electrical plate No 3 of SSR part –I and testing on completion.Note:-Quoted rates shall be deem to include for earth strip with protection pipe up to 7.5 M length. |
| 121 | M&L in repair for Earthing complete with galvanised steel earth plate electrode 600mmx600mmx6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less\"than 1.5 metres below normal ground level, connected to galvanised iron wire lead 4 mm earthing lead by means of bolts, nuts, check nuts and washers of galvanised , watering pipe of 20 mm bore, galvanised iron, light grade, and 40 mm bore galvanised iron light grade for earth wire protectionincluding all excavation earth work in any type of soil, PCC pit in PCC 1:2:4 type B-1 and RCC 1:2:4, type B1 for precast chamber cover 50 mm thick, reinforced with welded steel wire fabric or XPM Jali (weight not less than 4.00 Kg / sqm),with charcoal, salt, funnel complete all as shown in the electrical plate No 3 of SSR part –I and testing on completion.Note:-Quoted rates shall be deem to include for earth strip with protection pipe up to 7.5 M length. |
| 122 | M&L in replacement for Earthing complete with galvanised steel earth plate electrode 600mm×600mm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less\"than 1.5 metres below normal ground level, connected to galvanised iron strip 25x4 mm earthing lead by means of bolts, nuts, check nuts and washers of galvanised, watering pipe of 20 mm bore, galvanised iron, light grade, and 40 mm bore galvanised iron light grade for earth wire protectionincluding all excavation earth work in any type of soil, PCC pit in PCC 1:2:4 type B-1 and RCC 1:2:4, type B1 for precast chamber cover 50 mm thick, reinforced with welded steel wire fabric or XPM Jali (weight not less than 4.00 Kg / sqm),with charcoal, salt, funnel complete all as shown in the electrical plate No 3 of SSR part –I and testing on completion.Note:-Quoted rates shall be deem to include for earth strip with protection pipe up to 7.5 M length. |
| 123 | M & L in repair for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4 mm dia galvanised iron or steel wire complete all as specified as directed by Engineer in Charge. |
| 124 | Supply and fix in repair air termination rod 15 mm dia 1500 mm longbase fixed in position on pole/roof complete with clamp nut bolts insulator complete all as specified as directed by Engineer in Charge. |
| 125 | Material and labour in replacement for tripod chemical earthing (comprising of three chemical earthing. The chemical earthing will have specification as follows :- (a) Copper electrode of wall thickness minimum 2 mmnot less than 3 mtr length with not less than 75mm outer dia .(b) Fixing of copper Earth Electrode by drilling / boring 175 mm dia hole, 5.00 mtr deep in any type of strata, placing electrode in hole, return filling excavated soil by mixing min 10 kg GEL per bore and 75 kgSoil Resistivity Improvement (SRIP) compound as per manufacturer instruction (c)FRP earthing result display board 254 x 380mm made out of plastic material showing information related to type of earthing, earthing result, due date of testing along with fixing size 610mm height made of plastic hollow pipe of dia 20 mm. |
| 126 | (d) PCC earthing protection chamber for each earthing pit in PCC 1:2:4 type B1for precast chamber cover 50 mm thick, reinforced with welded steel wire fabric or XPM Jali (weight not less than 4.00 kg/sqm) including taking out old tripod earthingMake:- Powertrac/McML Earthing Solution/Ashlock.Note :-(a) The copper strip connection to each electrode and to the equipment will be measured and paid separately.(b) All other items are included for chemical earthing in the item except copper strip as mentioned innote(a) every other items is deemed to be included in the item.(c)The chemical earthing will be carried out by the manufacturer or its authorized representative on the site. |
| 127 | (d) The earthing result will be obtained for each electrode must be less than 1Ω.Otherwise contractor is liable to do chemical earthing to meet the result without extra cost if the results are above 1Ω.(e) Contractor must visit the site before quoting the tender to understand the difficulty and cost for carrying out the job in the station. It is important that contactor ascertain the quantum of work.(f) Contractor must produce the certificate from the manufacturer that chemicalearthing has been carried out by manufacturer. The manufacturer must also mention the warranty for chemical earthing.(g) Extension strip from electrode strip upto 0.15 m height from GL to be deemed included in quoted rate including brazing(h) The contractor has to give in writing for 3 years minimum warranty for constant result of earth below 1Ω. |