Tender For Electrical Work At Thdc Singrauli . - INTERNAL WIRING  2 Point wiring in PVC conduit, with modular type switch :-  3 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.  4 Group C  5 Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.  6 Group C  7 Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.  8 Power plug wiring in PVC conduit (2 x 4 Sq.Mm.) :-  9 Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.  10 Circuit / Sub main wiring in PVC conduit :-  11 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.  12 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire.  13 2 X 6 sq. mm + 1 X 6 sq. mm earth wire.  14 2 x 10 sq.mm. + 1 x 6 sq.mm. Earth wire  15 4 x 10 sq.mm. + 2 x 6 sq.mm. Earth wire  16 S/F light plug point Modular Type Accessories :-  17 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.  18 S/F power plug point modular Type Accessories :-  19 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.  20 Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, C curve including connections, painting etc. as required.  21 DISTRIBUTION BOARDS & MCBs  22 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, C curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as Required.  23 Single pole  24 Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.  25 Supplying and Fixing Following way, Horizontal Type Three Pole and Neutral, Sheet Steel, MCB Distribution Board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator).  26 6 Way (4 + 18), Double Door  27 8 Way (4 + 24), Double Door  28 Supplying and fixing following way, Single Pole and Neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator).  29 8 way , Double door  30 12 way , Double door  31 S/F DP MCB Isolator  32 Supplying and fixing following Rating, Double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as Required.  33 40 Amps  34 S/F 4P MCB Isolator  35 Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as Required.  36 63 Amps  37 S/F DP (RCCB)  38 Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as Required.  39 40 Amps  40 TELEPHONE, TELEVISION & DATA SYSTEM (socket,wiring & conduting only)  41 S/F MODULAR BOXES, BASE & COVER PLATE :-  42 Supplying and Fixing Following Size/ Modules, GI Box Alongwith Modular Base & Cover Plate for Modular Switches in Recess etc. as Required.  43 1 or 2 Module (75 mm x 75 mm)  44 S/F MODULAR TYPE SWITCH / SOCKET :-  45 Supplying and Fixing Following Modular Switch/ Socket on The Existing Modular plate & Switch Box including connections But Excluding Modular Plate etc. as required.  46 Telephone Socket outlet.  47 TV Antenna socket outlet.  48 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.  49 25 mm.  50 Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, Unarmored Telephone cable in the existing surface/ recessed steel/ PVC conduit as required.  51 2 Pair  52 Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required.  53 Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required.  54 1 run of cable  55 LIGHTINGFIXTURESANDFANS  56 Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.  57 Installation, testing and commissioning of pre-wired, fluorescent fitting /compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as Required.  58 Installation of Exhaust fan in the existing opening, including making good the damage, Connection, Testing, Commissioning etc. as Required.  59 Upto 450 mm sweep  60 Fixing Louvers / Shutters for Exhaust Fan:  61 Extra for Fixing the Louvers/ Shutters Complete with Frame for a Exhaust Fan of all sizes.  62 Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard drawing  63 CABLE & ACCESSORIES  64 LT CABLE LAYING  65 Laying of One Number PVC Insulated And PVC Sheathed / XLPE Power Cable of 1.1 kV Grade of Following Size Direct in Ground Including Excavation, Sand Cushioning, Protective Covering and Refilling the Trench etc. as required.  66 Upto 35 sq. mm  67 Above 35 sq. mm and upto 95 sq. mm  68 Above 95 sq. mm and upto 185 sq. mm  69 Above 185 sq. mm and upto 400 sq. mm  70 LT CABLE JOINTING & END TERMINATION  71 Supplying and Making End Termination With Brass Compression Gland and Aluminium lugs for Following Size of PVC Insulated and PVC Sheathed / XLPE Aluminium Conductor Cable of 1.1 kV Grade as Required.  72 3½ X 25 sq. mm (28mm)  73 3½ X 35 sq. mm (32mm)  74 3½ X 50 sq. mm (35mm)  75 3½ X 95 sq. mm (45mm)  76 3½ X 120 sq. mm (45mm)  77 3½ X 150 sq. mm (50mm)  78 3½ X 185 sq. mm (57mm)  79 3½ X 240 sq. mm (62mm)  80 MISCELLANEOUS ITEMS  81 Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.  82 EARTHING  83 Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required.  84 Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required.. (NEUTRAL EARTHING)  85 Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.  86 Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.  87 Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.  88 11KV HT Board, 250 KVA Transformer, 200 KVA DG Set, HT Cable & Accessories  89 H V CABLE LAYING  90 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.  91 Above 120 sq. mm and upto 400 sq. mm  92 Supply and making Indoor cable end jointing with cast resin compund, including lugs and other jointing materials for following size of 3 core, XLPE aluminium conductor cable of 11KV grade as required.  93 3 C x 240 Sq.mm  94 Supply and making Outdoor cable end jointing with cast resin compund, including lugs and other jointing materials for following size of 3 core, XLPE aluminium conductor cable of 11KV grade as required.  95 3 C x 240 Sq.mm  96 Supply and Making Straight Through Cable Jointing With Cast Resin Compund, Including Ferrule & Other Jointing Materials for Following Size of 3 core, XLPE Aluminium conductor cable of 11KV grade as required.  97 3 C x 240 Sq.mm  98 RCC Hume pipes  99 Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required.  100 250 mm dia  101 300 mm dia  102 100 mm dia  103 Manholes  104 Constructing masonry Chamber 60x60x75 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100mm top diameter, 160 mm bottom diameter and 180 mm deep ( inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) , i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design.  105 With common burnt clay F.P.S.(non modular) bricks of class designation 7.5  106 Constructing masonry Chamber 90x90x100 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100 mm top diameter, 160 mm bottom diameter and 180 mm deep (inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ), i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design :  107 With common burnt clay F.P.S.(non modular) bricks of class designation 7.5  108 HDPE PIPES  109 Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required.  110 200 mm dia (OD-200 mm & ID-175 mm nominal)  111 CABLE TRAYS  112 Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required. (Cable Tray Bends as per Requirement)  113 150 mm width X 50 mm depth X 1.6 mm thickness  114 300 mm width X 50 mm depth X 1.6 mm thickness  115 450 mm width X 50 mm depth X 2.0 mm thickness  116 600 mm width X 50 mm depth X 2.0 mm thickness  117 EXTERNAL LIGHTING  118 Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required.  119 Above 4.5 metre and upto 6.5 metre  120 Supplying and embedding following dia G.I. pipe (medium class) in pole collar/ foundation (during casting) for cable entry including bending the pipe to the required shape , Hole Seeling to be done complete as required.  121 32 mm dia  122 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size direct in ground including excavation and refilling the trench etc. as required, but excluding sand cushioning and protective covering.  123 Upto 35 sq. mm  124 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size in the existing RCC/ HUME/ METAL pipe as required.  125 Upto 35 sq. mm  126 Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.  127 3 core 2.5 sq.mm (for6/4 Mtr Poles)  128 Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required.  129 63 mm dia (OD-63 mm & ID-51 mm nominal)  130 TELEPHONE, TELEVISION & DATA SYSTEM (socket,wiring & conduting only)  131 Supplying & Fixing Modular Type Computer jack RJ 45 ISI mark 1 Module on existing Mounting plate and box Complete with all accessories as required.  132 Light Fixtures and Fans  133 Supply of 40W LED Recessed Light Fixture Aesthetically designed 2x2 LED Flat panel light which provides soft-light and glare free symmetrical illumination complete with all accessories as required.  134 Supply of Surface Mounted Energy Efficient, LED Luminaires 12W LED DOWN LIGHT (Round/Square) Sutaible for 220v Single Phase Supply complete with driver circuit including making connections etc as required.  135 Supply of Recess Mounted Energy Efficient, LED Luminaires 12W LED DOWN LIGHT (Round/Square) Sutaible for 220v Single Phase Supply complete with driver circuit including making connections etc as required.  136 Supply of Recess Mounted Energy Efficient, LED Luminaires18W LED DOWN LIGHT (Round/Square) Sutaible for 220v Single Phase Supply complete with driver circuit including making connections etc as required.  137 Supply, of Linear & Compact 10W Mirror Light with Decorative Grey Caps, Polycarbonate Body & Ribbed Opal Diffuser.  138 Supply of LED LuminairesBATTEN20W LED Tube Light of Box Type Prewired Indoor Luminairewith Energy Efficient Electronic Ballast, with End Caps Complete as Required.  139 Supply of Bulk Head Luminaire, heat resistant Glass cover suitable for 10W to 15W LED complete as Required.  140 Supply of Following sweep exhaust fan with guard suitable operation on single phase 230 V, 50Hz. AC Supply, with lowers /shutters in the existing opening.  141 300 mm Sweep 900 rpm  142 Supply & Fixing of 400mm Wall Mounted Fan with all accesseries as required complete for installation.  143 DISTRIBUTION PANELS  144 MAIN LT PANEL  145 NOTE:- MCCBs Wherever Specified shall have Rotary Handle.  146 Suppy , installation, testing, Design, manufacture, supply inspection, handling, assembling, affecting proper connections, testing and commissioningof2mm CRCA sheet steel fabricated cubical type Main L.T. Panel (Totally Type Test Assembled - TTA) floor mounting, dust & vermin proof, front operatedconstruction, enclosure class - IP 52,As per IEC 61439 after proper treatment with 9 tank process with top/bottomremovable gland plates, as required, double compression type cableglands,earth bus, hinged and lockable doorsto achieve dust and vermin proofcomplete with all inter connectionssmall wiring by min. 2.5 sq. mm. FRLS copper wires, ckt labels etc.The panel feeders shall be suitable for terminating suitable nos. 3.5 / 4 core armoured aluminium cable as required. Panel Should Be Internal Arc tested at 50ka for .3 sec as per IEC61641.  147 (Under no case temperature of main LT panel shall be more at any point of the panel. To avoid heating necessary exhaust fans shall have to be provided along with top louvers).  148 Degree of protection IP-42  149 The internal control wiring shall fuse less. All control wiring and metering protection shall be by MCBs.  150 Colour: Siemens Gray Powder Coated or as per approved shade.  151 INCOMER 1 FROM 250 KVA OUTDOOR TRANSFORMER  152 1 Nos. 400 amps four pole MCCB of fault breaking capacity 50 KA (Ics=Icu)fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicator and frame earthing contact ,confiming to IS 13947-21993 as amended upto date complete with following Accessories.  153 1 set of 3 CTs of ratio 400/5A, Class 1.0 accuracy 15 VA burden for APFCR.  154 Independent manual spring closing mechanism - 1 No.  155 Microprocessor release (EMI and EMC certified) for over current, earth fault and short circuit protection - 1Set .  156 Multifunction meter with selector switch with suitable CTs and back up MCBs.  157 3Nos. Phase indicatingLED lamps with 2 Amp backup MCB, breaker ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB , circuits as per standatd practice , auxiallry contact for positive interlocking of the breakers as required.  158 Shunt trip coil 220 Volt AC.  159 INCOMER FROM DG SET (200 KVA) - 1 Nos  160 1 Nos. 400 amps four pole MCCB of fault breaking capacity 50 KA (Ics=Icu)fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicator and frame earthing contact ,confiming to IS 13947-21993 as amended upto date complete with following Accessories .  161 1 set of 3 CTs of ratio 400/5A, Class 1.0  162 Independent manual spring closing mechanism - 1 No.  163 Microprocessor release (EMI and EMC certified) for over current, earth fault and short circuit protection- 1Set .  164 Multifunction meter with selector switch with suitable CTs and back up MCBs.  165 Protection releaseswith LSIG and Over voltage ,under voltage,Reverse power protection Relay & Metering & Accessories for each D G set incomers  166 3 Nos. Phase indicatingLED lamps with 2 Amp backup MCB, breaker ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB , circuits as per standatd practice , auxiallry contact for positive interlocking of the breakers as required .  167 Shunt trip coil 220 Volt AC.  168 1 nos battery charger with DC voltmeter and ammeter suitable for the DG sets (200 KVA)  169 INTERLOCKING  170 Interlocking logic electrical Interlocking betweenincomers and bus coupler and it should have auto start and auto trip facility for Automatic Operation of The Breakers Wit Manual Over Rid Facility  171 BUS COUPLER  172 One Number 400A 50KA 4 poleMCCB as Bus Coupler with ON/OFF Indication.  173 BUS BAR  174 500 A TPN Aluminium bus bar with heat Shrink Sleeve  175 OUTGOINGs  176 All the MCCBs Shall be Equiped/Provided with all accessories & Inbuid protection releas & MCCBs Shall be Thermal Magnetic upto 250A & Above Microprocessor Based with inbuiltO/L & S/C release.  177 1 Nos. 200 AMPSTP MCCB (Capacitor Panel)  178 1 No. 125A 36KA4P MCCB. (Ground Floor Panel)  179 1 No. 125A 36KA4P MCCB. (First Floor Panel)  180 1 No. 125A 36KA4P MCCB. (UPS Panel)  181 1 No. 100A 36KA 4P MCCB (Lift Panel)  182 1 No. 100A 36KA 4P MCCB (Fire Fighting)  183 1 No. 100A 36KA 4P MCCB (Plumbing)  184 1 No. 125A 36KA4P MCCB. (External Lighting)  185 2 No. 125A 36KA4P MCCB (Spare)  186 2 No. 100A 36KA4P MCCB (Spare)  187 Other items such as  188 1 set of control wiring  189 1 Set of designation plates  190 NOTE :- Adequate Quantity of Fire Suppression system with Pneumatic gas cylinder and Heat Sensitive Pneumatic tubing to be used in panel as perthe current fire norms & SURGE PROTECTION DEVICES Type 1 ( Class B), 4 Mode, spar type suitable for 10/350µs surge,3Nos. phase to earth and 1Nos. neutral to earth with impulse Current Iimp. ≥ 50KA Per mode & In ≥ 25kA per Mode.  191 Complete Panel as Above and complete  192 AUTOMATICPOWERFACTORCORRECTIONPANEL(CAPACITOR PANEL) - 90 KVAR- INNOVATION CENTER BLOCK  193 Supplying, Installation, Testing and Commissioning of cubicle type capacitior panel suitable for 415 & 3 phase 50 HZ A.C. supply System fabricated in compartmentalised design from CRCA Sheet Steel of2 mm thick for frame work and cover, 3 mm thick for gland plates i/cpowder coating in approve shade having 500 AMP capacityTPN Aluminium bus bar DMC/SMC bus bar supprot entire pannel should have common Al. earth bar for size 50 mm x 5 mm i/c Providing & fixing following switch gear mounting there on fans,grills for propor ventillation complete with gaskets & inner connection i/c connection with existing CTS in the main CT Panel complete as reqd. The panel board shall be of dust and verm proof with degree of protection IP 42)  194 a) 200 Amps TP MCCB with Microprocessor Based release and E/F proctection with time dely(Ics=100% Icu) - 1 No.  195 b) 250A, 4 strip Tinned Aluminium busbar -1 Set  196 c) Micro processor based automatic Power factor control relay i/c power factor metre in 8 steps  197 d) Multi functional meters with suitable CTS and protection MCBS 1 set.  198 e) 3 Nos. Phase indieating right (lamp) with MCBs protection.  199 OUTGOINGS-  200 1 Set - 63 Amp TP MCB 10 KA and Capacitor duly switching contactor for 20 KVAR capacity auto mannual selector switch start/stop puch button on/off indicatting lamp with protection MCB & delay timer complete i/c 20 KVAR mixed dielectric with 7% detuned filter copper reactor type capacitor bank with inter Connection  201 7 Set - 40 Amp TP MCB 10 KA and Capacitor duly switching contactor for 10 KVAR capacity auto mannual selector switch start/stop puch button on/off indicatting lamp with protection MCB & delay timer complete i/c 10 KVAR mixed dielectric with 7% detuned filter copper reactor type capacitor bank with inter Connection  202 complete panel as above and complete  203 GROUND & FIRST FLOOR PANEL (TYPICAL)  204 SITC of cubicle LT pannel suitable for 415V, 3 phase, 4 wire 50 HZ Ac supply system, fabricated in conmpartmentalized (preferbly) design from CRCA sheet of 2mm thick for frame work and covers, 3mm thick for gland, plates i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, having suitable Amp capacity extensible type TPN aluminium alloy bus bars of high conductivity, DMC/SMC bus bar supports, , bottom base channel of MS section not less than 50mm x 50mm x 5mm thick,entire pannel shall have a common copper earth bar 25mm x 5 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of AI. bus bars and control wiring with 2.5 sq.mm. FRLS PVC insulated copper conducter S/C cable, cable alleys, cable gland plates in two half. i/c providing following switch gears :-  205 INCOMER : 125 AMP 36KA FP MCCB  206 BUS BAR :160 AMP,500 Volts, 3 phase 50 HZ4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves.  207 OUT GOINGS:  208 63 AMP 4P MCB Including 1 no. of Indication Lamp (DBs) - 6  209 63 AMP 4P MCB with1 no. of Indication Lamp (Spare) - 2  210 40 AMP DP MCB with1 no. of Indication Lamp (Spare) - 1  211 complete panel as above and complete  212 UPS PANEL  213 SITC of cubicle LT pannel suitable for 415V, 3 phase, 4 wire 50 HZ Ac supply system, fabricated in conmpartmentalized (preferbly) design from CRCA sheet of 2mm thick for frame work and covers, 3mm thick for gland, plates i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, having suitable Amp capacity extensible type TPN aluminium alloy bus bars of high conductivity, DMC/SMC bus bar supports, , bottom base channel of MS section not less than 50mm x 50mm x 5mm thick,entire pannel shall have a common copper earth bar 25mm x 5 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of AI. bus bars and control wiring with 2.5 sq.mm. FRLS PVC insulated copper conducter S/C cable, cable alleys, cable gland plates in two half. i/c providing following switch gears :-  214 INCOMER : 160 AMP 25KA FP MCCB (Including BY Pass Switch for 50 KVA UPS)  215 BY PASS Switch for UPS 160 AMP FP- 1 no.  216 BUS BAR :200 AMP,500 Volts, 3 phase 50 HZ4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves.  217 OUT GOINGS:  218 63 AMP 4P MCB Including 1 no. of Indication Lamp (DBs) - 7  219 40 AMP DP MCB Including 1 no. of Indication Lamp (DBs) - 2  220 63 AMP 4P MCB Including 1 no. of Indication Lamp - 2  221 100 AMP 4P MCCB Including 1 no. of Indication Lamp - 1  222 63 AMP 4P MCB with1 no. of Indication Lamp (Spare) - 1  223 40 AMP DP MCB with1 no. of Indication Lamp (Spare) - 2  224 complete panel as above and complete  225 LIFT PANEL  226 Design, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out ofCRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ completewith aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid.  227 INCOMER :100 AMP FP MCCB  228 BUS BAR : 125 AMP, 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm / amp.  229 The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature.  230 OUT GOINGS:  231 1 No 63 AMP 4P MCB(Lift)  232 1 No 40 AMP DP MCB(Machine Room DB)  233 1 No 40 AMP DP MCB(Spare)  234 1 No 63 AMP 4P MCB(Spare)  235 complete panel as above and complete  236 EXTERNAL LIGHT FEEDER PILLAR  237 Design,Manufacture, Supply, Installation,Testing and CommissioningofPanelFabricated out of 16 SWG CRCA sheet steel,IP 54, wall / floor mounting type with rain canopyThe sheet steel shall undergo minimum 7 tank treatment followed by finishing powder coating of min 60 micron thickness. the board includes415 /240 V electrolitic Aluminium Bus Bar, removable gland plates, cable glands,including connection with outgoing feeders completeinall respect, Panel Should Have Double Earthing Provision Which Connected to the Nearest Earth Grid.  238 INCOMER:  239 1 no. 125A, 25KA 4P MCCB with microprocessor based releases, ON indication, 1 no. multifunction meter (showing all power parameters), with Selector Switch, Matching Cast Resin CTs. + 3 Nos 63A DP MCB For each Phase.with 3 Nos Astronomical Weekly programmabletime switch (SST- 1min) ON Phase for automaitc switching of landscape light fixtures at sun set and sun rise or twilight (auto on/ auto off and auto mode) with manual override faiclity with 12/24 hour display format with suitable battery and indication for relay status i/c programming at site.  240 BUS BAR  241 TPN Aluminium bus bar with heat Shrink Sleeve rated for 125A.  242 OUTGOING  243 18 nos 16A DP MCB  244 2 nos 40A DP MCB  245 1 nos 40A 4P MCB (SPARE)  246 Other items such as  247 1 Set of control wiring  248 1 Set of designation plates  249 All Items complete as above  250 CABLE & ACCESSORIES  251 Supplying of Following Sizes of 1.1 KV Grade MulticoreAluminium Conductor XLPE Power Cable Insulated armoured cable conforming to IS:7098 (Part - I) or as per Relevant IS Code complete with all Amendments etcand should be NABL certified as required.  252 3.5 C X 240 Sq.mm Al. XLPE arm.  253 3.5 C X 185 Sq.mm Al. XLPE arm.  254 3.5 C X 150 Sq.mm Al. XLPE arm.  255 3.5 C X 120 Sq.mm Al. XLPE arm.  256 3.5 C X 95 Sq.mm Al. XLPE arm.  257 3.5 C X 50 Sq.mm Al. XLPE arm.  258 3.5 C X 35 Sq.mm Al. XLPE arm.  259 3.5 C X 25 Sq.mm Al. XLPE arm.  260 MISCELLANEOUS ITEMS  261 SITC of CO2 Fire Extinguishers 4.5 kg capacity complete in all respect ISI : 15683 marked. As per Safety plus extinguisher fire carbondioxide 4.5kg, duly charged, portable and complete as per defence specification (safetyplus SPEC 4.5)  262 UPS  263 UNINTERRUPTED POWER SUPPLY (UPS) - 50 KVA  264 Supply of 50 Kva Online UPS, IGBT UPS(Transformer-less Design).  265 Supply of SMF Batteries (12Volt VRLA, 120 Ah, 28 Numbersto provide 30 Min Backup in total for 50 kva UPS at 0.8PF and ECV=1.7V.  266 Fully rated Inbuilt static switch at the inverter output and 100% rated Inbuilt static switch at the static bypass line integrated in UPS module.  267 Supply of Local Accessories (like Cabling Between UPS and the Battery onsidering Cable Routing ,Battery Interlinks , Battery Rack etc).  268 Backfeed protection at Mains & Bypass (Inbuilt / External).  269 Installation and Commissioning of 50 kVA UPS, Battery and Accessories.  270 Supply , installation , testing and commissioning 160A FP MCCB of25KA breaking Capacity in metal sheet enclosure with ON/OFF, TYB Indication lamps for Incoming of UPSComplete in All Respect as Required.  271 SUB STATION - 11KV HT BOARD, 250 KVA TRANSFORMER, 200 KVA DG SET, HT CABLE & ACCESSORIES  272 11KV SINGLE VCB PANEL BOARD  273 11KV SINGLE PANEL HT VCB (Indoor Type) - ONE INCOMERS CUM OUTGOING  274 Design, Manufacture and Supply of 1 Panel, 11 kV HT VCB Switch Board with Following Accessories :  275 Incoming Cum Outgoing  276 Indoor Type - 630A, 11kV, 350MVA for 3 Sec., TP, Horizontally isolated, horizontally drawout type, motorised spring charged, closing mechanism, motor voltage 230V AC, shunt tripping & Closing coil Voltage 24V DC, Electrically Operated, Trip Free, Dust & Vermin Proof, Vacuum Circuit Breaker (VCB) With Mechanical & Electrical OFF/ON Indicators & Provided with Following -1 No.  277 CT chamber with double wound single phase, cast resin CT, 15VA burden with core-1 for metering (CL-1) and core-2 for protection (CL-5P10) and of 60/5/5A ratio - 3Nos.  278 IDMT relay with 3 elements for over current (50-200%) and 1 element for earth fault protection(10-40%). - 1 Set  279 Anti Pumping Relay - 1 Set.  280 Master Trip Relay - 1 Set.  281 Trip circuit supervision relay - 1 Set.  282 Potential Transformers, 3 Phase, 3 Limb,Drawout Type, Resin Cast 11000/(Root 3)/110/(Root 3) Ratio Class 1 Accuracy, 100 VA Burden, with HV fuse on primary side and MCB/ MPCB on secondary side. - 1 Set  283 6 Windows Annunciator with Hooter - 1 Set  284 1 Window for over current trip - 1 Set  285 1 Window for earth fault trip - 1 Set  286 1 Window for master trip relay - 1 Set  287 1 Window for Emergency Stop Push Button - 1 Set  288 2 Windows Spare - 1 Set  289 Digital Ammeter with inbuilt selector switch - 1 Set  290 Digital Voltmeter with inbuilt selector switch - 1 Set  291 A set of breaker ON/OFF/Trip/DC control supply healthy/Trip circuit healthy/ Spring Charged VCB in test / VCB in service & R,Y,B phase indication lamps. - 1 Set  292 Emergency stop push button -1 Set  293 Limit switches with 6 NO/ 6 NC breaker auxiliary contacts - 1 Set  294 Control:- T-N-C (Trip, Neutral, Close) breaker control switch with indication arrangement. - 1 Set  295 All control wiring with protection & test terminal block as required. - 1 Set  296 Space heater with thermostat for moisture absorption. - 1 Set  297 Suitable for connection to 3C x 240 sq.mm. Cross linked polythelene(XLPE) 11kV cables or as called for. - 1 Set  298 Cable box for 3C x 240 sq.mm 11kV XLPE Al. conductor cable. - 1 Set  299 HT Danger Plate - 2 Set  300 Incoming as described above. 1 Sets  301 Powerpack as Required to Be Included (220V/24V DC), 7AH Battery for Each Breaker Module.  302 SINGLE PANEL 11KV HT VCB PANEL AS DESCRIBED ABOVE  303 11KV TRANSFORMER(11 KV /0.433 KV) (250 KVA)  304 11KV TRANSFORMER(11 KV /433 V) (250 KVA)  305 Supply Installtion, Testing and commissioning of outdoorOil cooled Outdoor Type Transformer11 KV/433 Volt Rating 3 phase, Double Wound with copper Winding.(as per IS : 1180 (part 1) : 2014Level 2 (AMENDMENT 4)/ Equivalent IEC Standard , OLTCin Steps (+10% to -10% @ 1.25%), Insulation Class : Class A , Temperature Rise : 40 Deg.c in Oil , 45 deg.c by Resistance, 50 deg.c by Ambient , Dyn 11 Vector Group and other Standard Accessories as Required Including Followings :  306 PLEASE NOTE THE TRASNFOREMR SHALL BE IN COMPLINACE WITH NEW REGUALTION IS 1180 or Equivalent IEC Standard FOR LOSSES AND EFFICIENCY and ammended upto date  307 Civil work shall be paid extra as per actual.  308 Cable Termination box with disconnecting facility for 11 KV 3C-240 sq mm XLPE cable at 11 KV side  309 ON Load Tap Changer on HV side+10% to -10% @ 1.25%.  310 Standard Fittings , Accessories /Spares :-  311 Rating and Terminal Marking Plate - 1  312 Earthing Terminals - 2  313 Lifting Lugs - 2  314 Drain Valve with Blanking Plate - 1  315 Filter Valve with Blanking Plate - 1  316 Conservator - 1  317 Conservator Oil Filling Hole With Cap - 1  318 Oil Level Indicator with Min. Marking - 1  319 Dehydrating Breather - 1  320 Conservator Drain Plug - 1  321 Air Release Device - 1  322 Pressure Relief Valve - 1  323 Thermometer Pocket - 1  324 Rollers uni directional - 4  325 Radiators Detachable - 4  326 HV Cable Box- 1  327 LT Cable Box - 1  328 Seperate Neutral Terminal - 1  329 ON Load Tap Changer - 1  330 OTI with alarm and trip contacts  331 Buchholz relay with alarm & trip contact  332 Current Transformer  333 Radiator Valve  334 Marshalling Box  335 WTI with alarm & trip contact  336 WTI Pocket  337 Drain Valve with Blanking Plate (OLTC)  338 Filter Valve with Blanking Plate (OLTC)  339 OLTC Surge Relay  340 RTCC Indoor  341 AVR  342 250 KVA (11/433V) AS DESCRIBE ABOVE  343 DIESEL GENERATOR SET - 200 KVA DG SET :-  344 200 KVA DG SET  345 Supply, intastallation, Testing & Commissioning of200 KVA Capacity Radiator cooled DG Set with Suitable StandardAMF Panel & suitable capacity engine directly coupled withalternator for 415 volt, 3 phase, 50 Hz, 4 wire, Generation system complete with accessories, Fuel Oil Tank & Control Panel etc as Required and sound proof acquastic enclosurefor the DG SET (75 db @ 1m) , including supply,fixing of antivibration pads suitable for 200 KVA DG Set as per standards of Engine manufacture, provision of conrol cablefrom engine to control panelto engine. Provision of pipe fuel pipe line of suitable size from fuel tank to engine and over flow pipe engineto fuel tank complete gatevalve and fitting leader maker etc. Supply , Intallation of starting batteries of suitableAH as recommended by manufacterer Heavy duty complete as required at site complete with stand and battery charger residentials silencer sutaible for diesel engine exhaust pipe line complete complete flange, bend, flexible pipe all as required and as directed by Engineer Incharge.  346 Diesel Engine (CPCB-4 NORMS COMPLANT) 4 Stroke, Radiator Cooled, Diesel Engine Model Developing Output Prime 160 KW Having Following Arrangement :-  347 Flywheel With Starter Ring for Generating Set  348 Air Filter , Lube Oil Cooler Assembly with Accessories.  349 Exhaust Air Manifold  350 Exhaust Bellow  351 Fuel Fiter  352 Diesel engine pre heating arrangement  353 Lube Oil Filter  354 Exhaust Gas Turbo Charger with After Coller  355 Day Tank For fuel with Markings  356 ECP Panel mounted on a Separate Frame.  357 Radiator with Pusher Type Fan, With Fan Guard, Coolant Pump.  358 12V Electrical Starting System with Starter Motor and Battery Charging Alternator.  359 Engine Mounting Supports  360 ALTERNATOR Rated at 200 KVA, 415 Volts, 3 Phase, 4 Wire, 0.8 P.F (lag), 50HZ, 1500 RPM, IN Accordance with IS 4722 /IEC 60034 as per following Specification.  361 Rating: Suitable for an over-load of 10% for 1 hour in every 12 hours operation.  362 Voltage Regulation: Provided with Fast Response Thyristor Type Electronic automatic voltage regulator, which holds output voltage within desired limits. (+/- 1%).  363 Excitation: Self Excited - Self Regulated.  364 Alternator Loading: Suitable for Taking Rated load Immediately After Machine Reaches Rated Voltage and Speed.  365 Vibration: Suitable for Direct Coupling with Engine and Mounted on Common M.S. Channel Base Frame.  366 Enclosure: Screen protected drip proof enclosure with IP – 23 degree of protection.  367 Cooling: Air Cooled type with radial fan mounted on Rotor.  368 Winding and Insulation: Insulation class H as defined in IEC – 60034-1  369 ACCESSORIES :-  370 MS Base Frame Suitable for Mounting of the Offered Engine and Alternator.  371 Day Fuel Tank of Standard Capacity as per Rating Complete Fuel Gauge, Inlet/Outlet Connections, Drains Plug, Etc.  372 Residential Silencer (1.5 Meter with 750 mm diaApprox) Including Insulation of Silencer.  373 2 Nos 12 Volts DC Battery of Suitable Capacity with Leads.  374 1 Set of AVM Pads Fitted in Base Frame.  375 TOTAL FOR 200 KVA DG SET  376 Supply of H.T. Cable  377 Supply & Testing of following 11 KV (E) grade multicore Aluminium conductor XLPE insulated cable, insulation screening withextruded semi conducting compound in combination with copper tape armoured cores laid up, inner sheath of PVC tape, galvanised steel flat strip armoured and overall PVC sheathed cable conforming to IS: 7098 (Part - II) and complete with all latest amendments etc. complete as required.  378 3 C x 240 Sq. mm11 KV (E)  379 Supply , Installation, Testing & Commissioning of Integrated Post Top Lantern With 40W LED Lampincluding Pole &connection with 3 x 2.5 sq.mm single core PVC insulated copper conductor cable from junction box to fixture as required.  380 Supply , Installation, Testing & Commissioning of 50 W LED withcomplete with pot optic reflector connection with 3x2.5sq.mm single core PVC insulated copper conductor cable from junction box to fixture as required.  381 Supply, Installation, Testing and Commissioning of 200x160x98 (KVPC) Polycarbonate thermoplastics enclosure - junction box with I.P - 65 Protection with Terminals &cable hinged cover of approved design complete having gasket of internally embedded & made of polyeutherene & should be weather proof, rust proof, dust proof, water proof - box shall be tested as per IEC - 60670-2/60670-22. the box shall have self threaded holes & provision for mounting din rail. with 2 Nos cable gland including supplying & fixing crimping 2 nos lugs & 1 nos 32A connector 6 way for looping the incoming & outgoing cables and also connection of the street light one 6A SP MCB Including Connection of 2x6 sqmm Cable etc as Required.  382 Supplying of 6 mtr long hot dip Galvanized octagonal Pole with top of the pole 70 mm dia (A/F) and bottom of the pole 130 mm dia (A/F) made out of 3mm sheet with MS base plate of size 200mm (NS) x 200mm (NS) x 16mm (NS) on precast RCC foundation complete with suitable size openinginside the pole with flush weather proof door with locking facility preferably with LN key having proper arrangement with Accommodating of 1 Nos. 6 Amp.,10 KA MCB & neutral link4 way connector suitable for 25 Sqmm cable complete with electrically safe including inside cable termination with thimbles i/c wiring from pole box to fitting with 3x1.5 sq.mm. FRLS PVC insulated copper conductor wire, earth connection, din channel, earth stud and other accessories pertaining to this pole (But without street light fitting) etc as reqd.including providing & laying in position suitable RCC foundation as required for 6 mtr. octagonal hot dip Galvanized Pole as per Manufacturers drawing with 1:1.5:3 concrete (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size ) including excavation of all kind of earth such as all type of soil/soft rock or hard rock etc. as per existing site condition i/c providing, cutting, bending and placing reinforcement & IncludingJ typefoundation bolts , anchor plate and templates in position as per manufacturer Standard and Providing PVC Pipe for Cable Entry and Exits Including Disposal of Surplus Malba / Softrock / Hardrock Stone etc.as Required.  383 Supplying of Following sizes 1100 volt grade XLPE insulated PVC sheathed aluminium conductor armoured cables as per specification in existing laid in ground including cost of digging upto required depth, 150 mm sand all around the cable, brick protection and back filling, clamped to wall with suitable clamps including saddles fixing bolts, Connection Testing and commissioning as Required.  384 2x6 sqmm  385 Supplying of Following sizes 1100 volt grade XLPE insulated PVC sheathed aluminium conductor armoured cables as per specification in existing trenches/pipes, cable trays, ducts, clamped to wall with suitable clamps including, saddles fixing bolts, connecting testing and commissioning as Required.  386 2x6 sqmm  387 Supply, Installation, Testing and Commissioning of 120w Flood Light, Energy saving, environmental friendly, long life, exclusive innovative die-cast aluminium IP65 flood light, suitable for highlighting architectural facade and general purpose lighting.  388 SOLAR POWER SYSTEM  389 Supplying, installation, testing and commissioning of Grid interactive roof top solar photo voltaic power generation system including space frame  390 (SCHEDULED ITEMS - AS PER DSR (E&M) 2022  391 (A) Supplying , installation , testing and commissioning of electric driven terrace pump suitable for automatic opeartion and consisiting of the following, complete in all respects as required:( Terrace pump)  392 (B) Horizontal type, multistage, centifugal, split casing pump of cast iron body & bronze impeller with stainless shaft, mechanical conforming to IS:1520  393 © Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 hz, AC supply with IP55 clas of protection for enclosure, horizontal foot mounted type with class-F insulation, conforming to IS-325.  394 (d)M.S fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required.  395 (E)Suitbalecement concrete foundation duly plastered and with anti vibration pads.  396 Discharge : 450 liter per minute  397 Head : 35 meter  398 Providing, laying, testing & commissioningof C class heavy duty MS pipe conforming to IS 3589/IS 1239 including welding, fittings like elbows, tees, flangers, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required:  399 100 mm dia  400 Providing, laying, testing & commissioning of B class medium duty G.I. pipe conforming to IS 1239 including welding, fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc, and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required:  401 100mm dia  402 Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type-A) with blank Gunmetal/Stainless Steel cap and chain as required:  403 Single headed Stainless steel.  404 Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required.  405 100 MM NB  406 Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required  407 100 NB  408 Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange  409 100 mm dia.  410 Supplyinig and fixing 63 mm dia , 15 mm long RRL hose pipe with 63 mm dia male and female couplings duly bound with GIwire , rivets etc.confirming to IS 636 (type-A) as required:  411 Supply, fixing first aid Hose Reel with MS costruction spray painted in post office red , conforming to IS 884 complete with the following as required 20 mm nominal internals diawater hoseThermo plastic (Textile reinforced) type -2as per IS 12585) 20 mm nominal internal dia gun metal globe valve & nozzle Drum and brackets for fixing the equipments on wall .connections from riser with 25 mm dia stop gun metalvalve & M.S . Pipe and socket.40 M  412 Supplying and fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle confirming to IS 903 Suitable for instantaneous connection to interconnect hose pipe coupling as required:Stainless steel (Grade 304)  413 Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required :  414 2 way-100 mm dia M.S. Pipe  415 Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and painting with synthetic enamel paint of approved shade as required.  416 TOTAL- A(SCHEDULED ITEMS - AS PER DSR E&M 2022)  417 (NON SCHEDULED ITEMS - AS PER MARKET RATES)  418 Supply & erection of ISI marked portable fire extinguishers, confirming to IS:15683, wall mounted type, wall brackets complete in all respect as per standard item with all accessories, delivery hose & nozzle whereever required, including fixing on walls as per the directions ofEngineer-in-charge.  419 Water CO2type. 9 Lt. capacity  420 D.C.P.Type 6 kg. capacity  421 ABC dry powder Type 6 kg. capacity  422 CO2 gas type. 6.5 kg. cap. -Trolley mounted  423 Providing & fixing neoprene rubber double flangedrubber expansion joint(anti vibration bellow) of standard length as per manufacturers specifications. suitable for hydrostatic test pressure of 21 kg/sqcm including all necessary fittings i.e. rubber gasket, nuts, bolts, washers etc complete as required.  424 100 mm dia.  425 150 mm dia.  426 Providing & fixing standard carbon steel fireman axe with rubber insulated handle tested to 20000 Volts.  427 Supply, fixing, testing & commissioning of 25 mm dia inspecting and testing assembly with gun metal valve, sight glass, by pass valve and connection to the drain line as required to complete the system.  428 Providing and fixing of cast iron body 100 mm dia Draw out connection in Under ground water storage tankwith heavy class MS suction pipe of required length,foot valve, suction coupling in conformity with local regulations complete in all respects.  429 Providing and fixing weather proof standard fire hose cabinet (750 mm x 600 mm x 250 mm)outdoor typemade of not less than 16 SWG MS sheethaving glassed hinged door (5 mm thick glass) including necessary locking arrangement with handle for housing two nos.15 meter long fire hose pipes, branch pipeas required as per drawings, including brackets for mounting accessories, painting (one coat primer and two coat of fire red colour). The cabinet shall be mounted onself standing mounted type MS Angle iron frame as required. The words FIRE HOSE to be painted on the box.  430 Providing and fixing standard fire hose cabinet door with frame (900 mm x 2000 mm ) or (suitable to fit in the duct made of not less than 16 SWG MS sheethavingglass hinged door (5 mm thick glass) including necessary locking arrangement with handle as required as per drawings, including brackets for mounting accessories, painting (one coat primer and two coats of fire red colour). The door shall be fixed in the masonry wall or as required. The words FIRE HOSE to be painted on the box.  431 Supply, installation and testing of cylindrical type flanged pressurevessel tank, 450 mm dia, 2 m long and of 10 mm thick M.S., common for a set of fire pumpsincluding flanged connection, suitable supporting legswith MS plate of size 75x75x5 mm at the bottom and grouted in CC foundation. The air vessel tank shall be provided with air release valve, stop cock, safety valve, pressure gauge, 50 mm dia drain valve, suitable length of connecting pipe and valve from delivery header to vessel tank, suitable pressure switches to operate all pumps (1 nos each), tested to min 25 KG/cm2complete including painting with synthetic enamel paint of approved shade with all accessories as per direction of the Engineer-in-charge. (For Pump House)  432 Providing & fixing 100 mm dia dial pressure gauge including making connections with MS pipecomplete in all respects.  433 PART-A EQUIPMENT  434 OUTDOOR UNITS (HEAT PUMP TYPE)  435 Supplying,installing,testingandcommissioningofaircooled variable refrigerant volume / Flow modular typeairconditioning system with R410a refrigerant. The PCB Chamber of outdoor unit should be refrigerant cooled suitable for 415±10% 3 Phase, 50 cycles. The unit shall consist of indoor and out door units withindividual controllerasperdetailgiveninspecifications andhaving followingitems:(Theseitemsareto be giveninIndian rupeeswithcustomduites,inlandfrt,clearanceetconSitebasis)  436 Modular type outdoor units equippedwith highlyefficient 100% inverter type hermitically sealed scroll compressors, minimum two comprossors for and above 14 HP modules, with special precoated heat exchanger, low noise condenser fan housed in compact housing duly powder coated and manufacturer of compressor and outdoor unit should be same. The Unit should have automatic refrigerant charge function. The static pressure of the outdoor unit shall be more then78Patoavoidhotairrecirculation.The unitshallbeabletooperateuptoto45°Cin coolingmode.The unit shall also have feature to automatically modulate the evaporative temperature between 6 deg C to 11 deg C with respecttoloadforbettercomfortandenergy efficiency etc complete as reqd. The units should have free phase technology for countinued operation. The unit shall deliver the rated capacity at AHRI Conditions and work even at 50°C ambient temperature without tripping .The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5 of following capacitites:  437 Cost of R 410 A Gas should be inclusive  438 The outdoor unit should include all loading, unloading, transportation, power cabling/wiring from near the indoor and outdoor units respectively.  439 The outdoor unit should include all loading, unloading, transportation, power cabling/wiring,( Y/T joints which is required for ODU Zone requirement Modules) from near the indoor and outdoor units respectively. Outdoor Units-Heat Pump , Fully Gas Charged and Aluminum fins within the ODU (condensing) unit shall be coated with polysiloxane based coating.  440 The Vendor should considere the deration on ODU election as per Singroli MP Ambient conditions  441 18 HP Outdoor unit VRV/VRF Zone-01  442 16 HP Outdoor unit VRV/VRF Zone-02  443 22 HP Outdoor unit VRV/VRF Zone-03  444 26 HP Outdoor unit VRV/VRF Zone-02  445 INDOOR UNITS  446 Supply, installation, testing and commissioning of following minimum capacity 4-way flow VRV/VRF Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolation, cord less remote control etc., suitable for operation on single phase 230 V ±10%, 50Hz AC supply, complete, as required. The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree CDB and 19 Degree C WB temperature.  447 Ceiling Mounted Cassette Unit  448 300-318 CFM / 0.63-0.80 TR  449 310-335 CFM / 1.0 TR  450 600-670 CFM / 1.2-1.3 TR  451 812-830 CFM / 1.6-2.0 TR  452 850-865 CFM / 2.5-2.8 TR  453 1130-1165 CFM / 3.1-3.2 TR  454 Ceiling Mounted HSP Ductable Unit  455 1130 -1150 CFM / 3.0-3.40 TR  456 1200-1377 CFM / 3.95-4.0 TR  457 1600-2050 CFM / 4.5-5.5 TR  458 2047-2295 CFM / 6.36-7.1 TR  459 REMOTE CONTROLLERS  460 Supply, installation, tesing and commissioning of Imported Remote controllers (Corded) for operation of ductable indoor units and AHUs.  461 Touch screen controller for indoor units controller - VRV  462 Supply, installation, testing and commissioning of touch screen controller (Which is controlled 45 nos. indoor units in terms of ON/Off Status, temp. Status, Fan Speed, ODU On/Off Status etc.) with all accessories and controls.  463 REFNUTS /T/ Y-JOINTS  464 Supply, installation, tesing and commissioning of Imported fittings Y-joints insulated, distributer and headers for all Indoor units at both the ends floors layout as per layout drawings.All interconnecting joints, Y Joints withpolysiloxane based coating  465 REFRIGERANT PIPING  466 Supply, installation, testing and commissioning of Interconnectingrefrigerantpipe work with (13/ 19mm thick) cross linked closed cell Oxide Acetate Foam tubular insulation between each set ofindoor & outdoor units asper specifications, allpiping inside the room shall be properly supported with hangersandv All interconnecting Copper piping, joints, U bends withoxycoat dual barrier coating shall run incable tray. (Note: Ref. Piping Length may be review as per site routing)  467 06.35 mm with 13 mm thick cross linked closed cell Oxide Acetate Foam insulation  468 09.52 mm with 13 mm thick cross linked closed cell Oxide Acetate Foam insulation  469 12.70 mm with 13 mm thick cross linked closed cell Oxide Acetate Foam insulation  470 15.88 mm with 13 mm thick cross linked closed cell Oxide Acetate Foam insulation  471 19.05 mm with 13 mm thick cross linked closed cell Oxide Acetate Foam insulation  472 22.22 mm with 19 mm thick cross linked closed cell Oxide Acetate Foam insulation  473 28.58 mm with 19 mm thick cross linked closed cell Oxide Acetate Foam insulation  474 34.92 mm with 19 mm thick cross linked closed cell Oxide Acetate Foam insulation  475 41.30 mm with 19 mm thick cross linked closed cell Oxide Acetate Foam insulation  476 TRANSMISSION & CONTROL WIRING  477 Supply, installation, testing, termination and commissioning of control cum transimission wiring (should be shielded cable in PVC Pipe) of 2C x 1.5 Sqmm Cu between indoor unit and out door unit and indoor units and its remote controller.  478 2C x 1.5 Sqmm Cu Cable or as per Manufacturer OEM  479 Perforated GITray with hangers & supports for copper piping (250 mm wide)  480 Refrigerant-410a  481 Supply , charging & Leackage testing of refrigerant -410a in additionalcopper piping circuit.  482 CONDENSATE DRAIN PIPE  483 Supplying, fixing,testing and commissioning offollowing PVC pipes for condensate drain duly insulated with Fire rated Class O kinny foam /Nitrile Rubber & vapour barrier duly secured with adhesive tape as per specification ,cut to required length and installed with all joints , including the necessary fittings. (For all the AHU/FCU units upto the main header in the shaft dor vertical risers)  484 65mm dia  485 50mm dia  486 40mm dia  487 30mm dia  488 25 mm dia  489 TOTAL CARRIED OVER TO SUMMARY ( PART-A EQUIPMENTS)  490 PART-B VENTILATION  491 Propeller fan  492 Supply,installation,testing and commissioning of Certified Propeller fan of the following capacity of approved make and specification. Fan shall be supplied with aluminum gravity louver & bird screen and Speed Regulator.  493 200 mmdia propeller fan,with single phase motor  494 300 mmdia propeller fan,with single phase motor  495 450 mmdia propeller fan ,with single phase motor  496 Inline fan  497 Supply, installation, testing and commissioning ofCertified Circular/Rectangular swing type Inline fan with fiire retardent Canvas connection Speed Regulatorof the following capacity of approved make and specification.  498 100-300 CFM,5-7 mm SP WG with Single phase motor  499 350-400 CFM,10-12 mm SP WG with Single phase motor  500 600-800 CFM,10-12 mm SP WG with Single phase motor  501 Tube Axial Flow fans  502 SITC of Long case Tube axial flow fans, as per specifications and approved makes suitable for three phase operation respectively Normal/Smoke case.  503 SITC of AMCA Certified (For Air and Sound Performance) tube axial flow fan of different capacity as mentioned below in standard M.S.contruction. Entire fan model & AMCA Seal shall apear in techncial submittal of fan. All the fans are synthetic enamelled panited/hot dip galvanized with minimum 220 GSM Zinc Coating and complete with bird screen at inlet. The electric motor coupler shall be squirrel cage induction motor (IE-2 type) confirming to IS - 325-IP - 55 with class `F insulation.Fan efficiency should not be less than 70 %, noise level should not be more than 85 db @ 3 m distance when measured in hemisperical reverberant room conditions. Fans should be as per specification and drawings. (As per Vent. Fan Schedule ) (Makeup Air & Pressurization Fans with St. Press. of 40 mmWG/Make Up Air Fan at 30mm WG)  504 6000 CFM (For Stairwell/Liftwell Pressurization)  505 6500 CFM (For Smoke Extract,with H Class insulation)  506 AIR SIDE WORKS  507 Site Fabricated Duct - GI duct  508 Supply,Installation,balancing and commissioning of fabricated at site GSS sheet metal ducts (rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter,vanes, hangers, Gripple supportsetc.) in accordance with the approved shop drawings and specifications , and shall also confirm to the BIS specifications.The duct shall be fabricated at site for to suit pieces.  509 0.63mm (24 gauge) GSS  510 0.8 mm (22 gauge)GSS  511 Factory Fabricated Duct - GI duct  512 Supply,Installation,balancing and commissioning of factory fabricated GSS sheet metal ducts (rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter,vanes, hangers, Gripple supportsetc.) in accordance with the approved shop drawings and specifications , and shall also confirm to the BIS specifications.The duct shall be fabricated at site for to suit pieces.  513 0.63mm (24 gauge) GSS  514 0.8 mm (22 gauge)GSS  515 Supply, Fabrication, Installation and testing of Insulated Al. Flexible ducts in accordance with the approved shop floor drawings and specifications and shall also confirm to the BIS specifications.  516 200 mm Dia.  517 150 mm Dia.  518 Grilles/Diffusers  519 Supplying and fixing of Extruded aluminium supply and return air grilles/diffusers/louvres with dampers, supply air plenum etc. duly powder coated as per specifications and drawings.  520 Aluminium supply air grilles with damper.  521 Aluminium return air grilles without damper.  522 Aluminium supply air square diffuser with damper  523 Aluminium return/exhaust air square diffuser without damper.  524 Aluminium return/exhaust airValve circular/squirell diffuser without damper.  525 Fresh Air/Exhaust Air Louvers  526 Supplying and fixing ofextruded aluminium louvres with frame bird screeen , mounting arrangement etc. as per specifications and drawings.  527 Fresh Air/Exhaust Louvers  528 Supply,Installation,Testing and commissioning of doble layer canvas connection with 1/2 hr. fire ratingasper specification.  529 MECHANICAL INSULATION  530 DUCT LINE ACOUSTIC TREATMENT  531 Supply and installation of cross linked open cell Oxide Acetate( AccoIsolate) Foam Acoustic insulation on ducts having density of 30 to 60Kg/ M³ ,having K value 0.029 W/m ° K at 0°C Deg temp and temp range of-70°C to +100°C and fire rating Class O as per BS 476 Part 6 fromCBRI,Roorkee and CFC/HCFC free as per US EPA 5021 A(2014 ). • Smoke & Toxicity index of material shall be passed as per IMO MSC 307 ( 88 ) 2010 Anexx 1 Pt 2 andas per the approved specifications.  532 15mm thick Oxice Acetate Acco IsolateAcoustic open cell insulation on one side for Duct acoustic insulation  533 DUCT LINE THERMAL INSULATION  534 Supply and installation of cross linked closed cell Oxide Acetate( Thermo Isolate) Foam Thermal insulation on ducts having density 0f 30 ±3Kg/ M³ ,having K value 0.029 W/m ° K at 0°C Deg temp and temp range of-70°C to +100°C and fire rating Class O as per BS 476 Part 6 fromCBRI,Roorkee and CFC/HCFC free as per US EPA 5021 A(2014 ). • Smoke & Toxicity index of material shall be passed as per IMO MSC 307 ( 88 ) 2010 Anexx 1 Pt 2 andas per the approved specifications.  535 25 mm thick insulation oxide acetatefoam with 2 coat layer of 7 mile cloth with starbond or eql. adhesive on Exposed supply air duct  536 13 mm thick insulation oxide acetatefoam laminated with aluminium foil supply air duct  537 9mm thick insulation oxide acetatefoam laminated with aluminium foil supply air duct  538 EXPOSED ROOF INSULATION  539 Supply and installation of cross linked closed cell Oxide Acetate( Thermo Isolate) Foam Thermal insulation on ducts having density 0f 30 ±3Kg/ M³ ,having K value 0.029 W/m ° K at 0°C Deg temp and temp range of-70°C to +100°C and fire rating Class O as per BS 476 Part 6 fromCBRI,Roorkee and CFC/HCFC free as per US EPA 5021 A(2014 ). • Smoke & Toxicity index of material shall be passed as per IMO MSC 307 ( 88 ) 2010 Anexx 1 Pt 2 andas per the approved specifications.  540 19mmthick oxide acetate insulation for underceck plain  541 TOTAL CARRIED TOSUMMARY(Mechanical Insulation works)  542 ASSOCIATED ELECTRICAL WORKS  543 Therates for the distribution boards from the Breakers andinstrumentsshall also include the following :  544 Wiring forlight / Fan points with 1.5 sq. mm PVC insulatedcopper conductor1100 Volt grade strandedflexible FRLS wiresofapproved makein1.6mmthick25mmdiaMS conduitincluding costof providing & fixing saddles, hangers, supports, cutting chases and filling chases for recessed conduiting, and including the cost of providing and fixing a6 amp240Volt ModularPlatetypeswitchesof approved quality,colour, makeanddesign with mouldedcover platein zinc chromate passivated MS box and including the cost of running 1.5 sq. mm PVC insulated copper earth wire for loop earthing etc. complete  545 TPN ACB’s / MCCB’s shall mean 3 pole ACB’s / MCCB’s with adequatesize of neutral link.  546 All MCB’s shall be of minimum 10 KA breaking capacity and MCCB s shall be not lessthan 25KA  547 The breaking capacity of MCCB’s are mentioned panel wise. All MCCB’s shall be with thermalmagnetic microprocessorreleasesas per BOQand following :  548 i.MCCB rating upto 250 Amps with thermal magnetic releases.  549 ii. MCCB above 250 Amps with microprocessor releases.  550 All MCB’s used for protection ofresistiveand lightlyinductive loadshallbetype “B”characteristic and inductive(motor)loadshall be of type “C” characteristic.  551 Degree of protection for following type of distribution panel enclosureshall be as per IS:13947-1993.  552 i.IP 42 for indoor panels.  553 ii. IP 55 for ODU panel.  554 AllMCCB’sshall beprovidedwithoperatingmechanismfordoorinterlock.  555 All hinged door shall be earthedthrough2.5 sq mm tinnedbraidedcopper wire.  556 Providing cableclamps/ supportswithin distributionboardscablealley.  557 Current density of aluminium shall be 1sq mm for 1.0 Amps for ratedcurrent of bus bars.  558 Model, current capacity location and frame size of switchgear shall be writteninside of thepanel doors with paint / permanent marker asapproved shop drawings / site requirment.  559 All meter shall be digital type and all starter shall be as per Type-2 Coordination chart  560 Current Transfomer shall be resin cast.  561 All Panel Shall be BMS Compitable  562 AHU/Fan Panel  563 Design, fabrication, assembling, wiring, supply, installation, testing and commissioning of following LT panels fabricated out of 14 guage CRCA sheet steel in cubical formationwith reinforecment of suitable size angle iron and channel T iron flats. All steel material used in the construction of panels shall be powder coated. A solid busbar shall be provided at the bottom of the panel with two connecting eyes for termination. The boards shall be suitable for 415 volts, 50 Hz, 3 phase , 4 wire supply system. All the hardware used in the fabrication of the panel shall be galvanized with zinc passivation. The panel shall be compartmentalized to accommodate one feeder in each compartment. A vertcal cable alley of suitable width shall be provided to serve on or two vertical feeder sections. Also the opening between the busbar chamber and the feeder section shall be shrouded with bakelite / hylam sheet with min.3 mm thickness.  564 The panel drawing shall be approved before taking up the fabrication and compitable BMS if in future required. (ALL AHU PANEL WITH  565 In All panel Each starter should have remote control and interlocking facilities including auto manual switch, NO/NC contacts for control and must have auto manual operation suitable to take signal from fire alarm panel for automatic operation of fan in case of fire.All smoke /vent. fan panel the starters shall have suitable facility to operate with fire sensing control modules.  566 Vent. Fan Panel- MCC -1  567 Incoming  568 1 no. 63 amp MCCB  569 Phase indicating lights with control fuses.  570 Breaker ON/OFF/TRIP indicating lights.  571 Bus Bars  572 100 amp TPN Aluminum Bus Bar with heat shrinkable insulation colored sleeves.  573 Outgoings  574 3 nos. 6-10 A,TP MPCB(With DOL Starter)  575 The base frame shall be 75 mm x 5 mm.  576 Panel as described above and in drawings.  577 METER BOARD / SUB PANELS  578 Supplying, Installation, Testing and Commissioning of dust, damp and vermin proof free floor standing / wall mounted factory built sheet steel enclosed modular construction extendable panel, suitable for operation on 415 + 10% volts, 50 Hz AC 3 phase 4 wire system fabricated out of suitable sized square tubular section and covered with 2.0mm thick CRCA sheet, hinged doors of 2mm thick CRCA sheet, duly painted complete with aluminium bus bars, interconnection with solid copper conductor wires / aluminium strips, neutral links, earth bus etc. necessary metering protections & indications and mounted with the following as per drawing and technical specifications attached etc. complete as required.  579 ODUs Panel-01-TERRHVAC  580 Same as above item but outdoor Panel with following accessories.  581 INCOMING:  582 1 No. 200 amps, 415VTPN MCCB with overcurrent and short circuit releases, all indication, push button etc.  583 Coloured (Red, Yellow, Blue) phase indicating lamp - 1 set  584 (0 - 200 A) CT operated Ammeter with selector switch& 3 nos. CTs ratio 200/5A , 15VA burden & accuracy class of 1.0 - 1 set  585 0-500 V Voltmeter with selector switch - 1 set  586 BUSBAR:  587 250 Amp. TPN, 35 kA Al. Bus Bar  588 OUTGOINGS:  589 80A, TPN ELCB with 300mA- 3 Nos. (Incl. 1No. Spare)  590 40A, TPN ELCB with 300mA- 5 Nos. (Incl. 1No. Spare)  591 ODU Panel Described as above/As per Manufacturer ODU Configuration.  592 Spcl. Note : All Above mentionedpanel SITC as per actual GA dwgs. equipments and final config,. Of ODUs.  593 CABLING (POWER )  594 Power Cabling and Earthing:  595 Spcl. All Cables Should be fire survival Cables (FRLS)  596 Supply, installation, testing & commisioning of LPCB approved mineral insulated copper conductor cables, construction as per BSEN 60702-1:2002 suitable for withstanding 950 deg under fire conditions as per BS 6387 CWZ and 850 deg under fire conditions on one single sample as per BSEN 50200. Cable should be manufactured with seamless copper tube and should be HFLS sheathed. (Tagging to be provided with aluminium strips on both the ends as approved).  597 3Cx10 Sqmm  598 3Cx06 Sqmm  599 3Cx04 Sqmm  600 4Cx06 Sqmm Cu  601 4Cx10 Sqmm Cu  602 Control Cabling  603 Supply, installation, testing & commisioning ofCopper conductor , PVC insulated, PVC sheathed armoured cable of 1.1 KV grade (Which is Interconnecting wiring for the fire alarm system with the AHU and the smoke dampers and AHU to Control Consol Panel).  604 8C x 1.5 Sqmm  605 Supply, installation, testing & commisioning of cable termination of above cables with copper lugs & flameproof brass compression glands on both the ends with inhibting compound etc. complete as required.  606 3Cx10 Sqmm  607 3Cx06 Sqmm  608 3Cx04 Sqmm  609 4Cx06 Sqmm Cu  610 4Cx10 Sqmm Cu  611 Supplying and installing following size of perforated G.I. cable trays, G.I. bends with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with suitable suspenders including G.I. bolts & nuts, painting of suspenders etc. complete as required.  612 100 mm. Width x 50mm. Depth x 1.6mm. Thickness.  613 150 mm. Width x 50mm. Depth x 1.6mm. Thickness.  614 225 mm. Width x 50mm. Depth x 1.6mm. Thickness.  615 Providing and fixing following size of G.I. strip / G.I. wire on surface or in recess for loop earthing alongwith the existing surface/ recessed conduit/ submain wiring / on cable tray/ on surface including G.I. clamps etc. complete as required.  616 6 SWG G.I. wire  617 Electrical work i.e.  618 3 Pin socket switch for Cassette, fcu, inline fan, propeller fan etc. near to the each unit.  619 Isolator Switch (Weather Proof) near to the each ODU.  620 Copper wiring /earthing from Isolator switch to M/C (chillers, pump, AHU , Fan etc.)  621 All DOL Starter Panel and Power cable for Fans/AHU  622 RCC Foundation for chiller, pumps, panels/outdoor units etc..  623 Spcl. Note:The work includes design, supply, fabrication, erection, testing & commissioning of the complete air conditioning system with items specified above.  624 Supply Installation , Testing & Commissioning of 8 Passangers, 544 Kg. 1mps. Automatic Elevator, with VVVF and Microprocessor based Simplex Collective Selectivewith/without Provision ofattendant control. Separate Landing Push Button Box for all Landings with scrolling indicator. with provision of Attendant control, having 2 stops , 2 Openings with SS Cabin (Hair Line Finish) havingCross flow fan for Ventillation , having sleek (SS hair Line finish-PVC) and LED small Circular lighting all complete.  625 Other Features  626 Battery Operated Emergency Light And Alarm Bell  627 Call Register Signal And Vf Door Operator  628 False Ceiling In Car  629 Vandal Proof S.S. Button With S.S. Cover  630 Firemans Switch  631 Infra Red Door Screen  632 Full Car Operating Panel  633 3 Way Intercom / Press And Speak Phone  634 Push Button - Orange L E D Illumination  635 Dot Matrix Led D & P Indicators In Car & Landings -Orange Colour  636 Automatic Rescue Device  637 Minor Builders Work  638 Scaffolding  639 Floor Annunciator With Music  640 Braille Buttons  641 Sill Support  642 Lift License  643 Overload Warning Indicator With Audio Announcement  644 Pit Ladder  645 Auto Light & Fan Switch Off (Pod)  646 SUB HEAD - I: CIRCUIT CUM POINT WIRING  647 SWITCH CONTROL LIGHT POINTS  648 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.  649 Group C  650 MCB CONTROL LIGHT POINTS  651 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. (Switch Control Primary Points)  652 Primary point controlled by one MCB.  653 Same as item above but Secondary point. i.e. Points to be looped with Primary pointwith 2.5 sqmm wire and Point wiring  654 Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.  655 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required.  656 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire  657 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire  658 2 X 6 sq. mm + 1 X 6 sq. mm earth wire  659 2 x 10 sq. mm + 1 x 10 sq.mm earth wire  660 4 X 10 sq. mm + 2 X 6 sq. mm earth wire  661 4 X 16 sq. mm + 2 X 6 sq. mm earth wire  662 Supplying and fixingsuitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing3 pin 5/6 Amp modular socket outlet and 5/6 A modular switch, connection etc. as required.  663 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.  664 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.  665 Telephone socket outlet  666 SUBHEAD -II - FITTINGS & FIXTURES  667 Supply, Installation, Testing and Commissioning of 18/20W Wall/Surface mouted 4 ft. LED  668 Supply, Installation, Testing and Commissioning of 40W LED POST TOP LANTERN  669 Supply, Installation, Testing and Commissioning of 40W LED GATE LIGHT  670 Supply, Installation, Testing and Commissioning of9W (Nominal)Wall Bracket Light  671 Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019),THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.  672 SUBHEAD - III - DISTRIBUTION BOARDS  673 Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)  674 12 way, Double door  675 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, C curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.  676 Single Pole  677 Single Pole Neutral  678 Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.  679 40 A  680 63 A  681 Supplying and fixing following rating, double pole, (single phaseand neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.  682 40 A  683 Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.