Name of Work: PROVISION OF X-RAY BLOCK OF 6 ADV FD VET HOSP UNDER GE (WEST) BAREILLY
Sl. No.
Item Description
1
SCHEDULE A PART-I (BUILDING WORK)
2
Construction of X-ray block complete all as specified and as shown of drawing
3
SCHEDULE A PART III A (INTERNAL ELECTRIC SUPPLY) for details refer pdf folder
4
SCHEDULE A PART III B (INTERNAL ELECTRIC SUPPLY)
5
S&F LED mirror light fitting of 1 x 10 wattLED batten with aluminium housing with all accessories prewired suitable for wall /surface mounting complete with connection all as specified and directed.
6
S&F Bldg security light fitting, LED type, 25 Watt, 6000 K, pressure die cast housing with prismatic polycarbonate diffuser & indvl LEDs as light source withintegrated electronic driver complete with M&L GI pipe mounting bracket of size 25/32 mm dia and 1.20 m long fixed to wall with andincluding nut, bolts and GI clamps of size 50 x 6 mm as required including two coats of synthetic enameled paint over a coat of primer and making connection with three core 23/.0076 rubber insulated copper cable from ceiling rose to connector of street light complete all as specified and directed.
7
S&F TPN DB -VTPN DB 4 way with provn ofMCCB 63 Amps, 415 Volt, 3 Phase, 4 wire AC 50 Hz having aluminium Bas Bar phase and the neutral insulated with PVC sleeves, connected with appropriate size copper thimbles complete all as specified and directed.
8
SCHEDULE A PART IV A (AIR CONDITIONING AND REFRIGERATION) for details refer pdf folder
9
SCHEDULE A PART IV B (AIR CONDITIONING AND REFRIGERATION)
10
S&F voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 3.0 KVA complete all as specified and directed.
11
SCHEDULE A PART V A (ROAD/ PATH) for details refer pdf folder
12
SCHEDULE A PART V B (ROAD/ PATH)
13
M&L for out door vitrified tile 400 x 400 mm x 7 to 9 mm thick even finished on top of apporved design and pattern over and including 20 mm thick screed bed or bedding layer in cement mortar 1:4 with grey cement and pigment complete all as specified and directed.
14
SCHEDULE A PART VI (EXTERNAL ELECTRIFICATION) for details refer pdf folder
15
SCHEDULE A PART VII (SEWAGE DISPOSAL)for details refer pdf folder
16
SCHEDULE A PART VIII (AREA DRAINAGE)for details refer pdf folder
17
SCHEDULE A PART IX (SITE CLEARANCE) for details refer pdf folder
We takes all possible care for accurate & authentic tender information, however Users