| 1 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320character graphics / LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile |
| 2 | power supply unit (230 ± 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories.The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. |
| 3 | Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete withmounting base complete as required. |
| 4 | Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixedtempreature thermistor complete with base as required. |
| 5 | Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED,metallic cover complete with all connections etc as required. |
| 6 | Supplying, installation, testing & commissioning of addressable manual call point complete as required |
| 7 | Supplying, installation, testing & commissioning of addressable strobe complete as required. |
| 8 | Supplying, installation, testing & commissioning of addressable fire control module complete as required. |
| 9 | Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size including connections and interconnections etc. as required. (speaker cable Twopair, 2-core, 1.5 sqmm) |
| 10 | Supplying, fixing testing and commissioning of butterfly valve of PN 1.6 rating with bronze/ gunmetal seat duly ISI markedcomplete with nuts, bolts, washer, gasket, following sizes as required. |
| 11 | 100 mm |
| 12 | 80 mm |
| 13 | Providing installation testing and commissioning of non return vlave of following sizes confirming to I.S.-5312 complete with rubber gasket, GI bolts, nuts, washer etc as required |
| 14 | 100 mm |
| 15 | Supply fixing first aid hose reel with MS construction spray painted in post office red, confirming to IS 884 complete with the following as required 20mm nominal internal dia water hose thermoplastic (Textile Reinforced) type-2 20mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipments on wall. Connections from riser with 25mmdia stop gun metal valve & MS Pipe and socket |
| 16 | SupplyingInstallationtesting& Commissioningof 25 mm Air Release valve gunmentalhavingrubberballandwith25mm BSP threaded male inletincluding necessary accessories and connections complete in all respect. |
| 17 | Supply & fixing 25mm dia ball valve, C.I. class- 125(Specification as per NBC 2016 by BIS Vol-1, Part-4 attached) |
| 18 | Providing/Fixing of Fire Hose internal cabinet box made out of 18 gauge MS sheet including two coats of post office red paint over one coat of primer with 4 mm, thick glass door in front painted \"FIRE\" in red luminous paint. The size of the box should be 750 mm X 600 mm X 250 mm size capable of accommodating a pair of hose wit h coupling and nozzle. The box should be floor mounted type with railway coach lock arrangement and lever for opening the door after breaking the glasscomplete.(Superior Quality) CE CERTIFIED |
| 19 | Supply & fixing 63mm dia 15m long |RRL hose pipe with 63 mm dia male/female coupling duly bounded with GI wire, rivet etc. confirming to I.S. 636 (type-A) as required:(Gun metal) |
| 20 | Supply and fixing of 63 mm dia gum metal short branch pipe with 20mm nominal internal diameter size nozzle confirmingto I.S. 903 suitable for instantaneous connection to interconnected hose pipe coupling.as required |
| 21 | (A) Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump)(B) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520(C) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-\"F\" insulation, conforming to IS-325.(D) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required.(E) Suitable cement concrete foundation duly plastered and with anti vibration pads. 450 Ipm at 35 m Head |
| 22 | Supplying & fixing airvessel made of 250 mm dia. 8mm thick MS sheet, 1200 mm in height with air release valve on topand flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure cauge and painting with synthetic enamel paint of approved shade as required. |
| 23 | Test Pressure 12 kg/sq.cm |
| 24 | SupplyingInstallationtesting& Commissioning of Pressure Guage ranging from0 to 14 kg. per sq.cm.ISI markedfromappovred manufactures complete in all respect. |
| 25 | Supply and Fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet coupling completewith cap and chain as reqd. for suitable dia MS pipe connection confirming to I.S. 904 as required. |
| 26 | 2 way- 100 mm dia M.S. Pipe |
| 27 | Providing/FixingofCubicaltypefloor mountedFire pump Controlpanel fabricated from16GM.S.sheetduly powdercoated finish of aproved shade and comprising of:a) One 63 amp. TP+NL M.C.C.B. with rotary handle of beacking capacity 35 KA.b) One Volt meter (0-500V) with selector switch.c) One set including lamps |
| 28 | Supplying and Laying of PVC insulated & PVC sheathed / XLPE power Cable of 1.1 KV grade of following size on wallsurface as required. |
| 29 | 2 core x 1.5 sq.mm CU Cable |
| 30 | 3.5 core x 35 sq.mm AL Cable |
| 31 | Supply, Installation, Testing &commissioning of Single/Double sided Signage with 20 mtr. viewing distance with built inLED, High efficiency L80 LED with 50,000 hour life, Usage: Exit Signage cum Emergency light with Function Use either as an emergency luminaire or exit sign, with standalone Testing system, Housing of Polycarbonate, Glow wire test : 850°C, RAL9003, Type of mounting: Wall or ceiling, Operation Mode Non -Maintained or Maintained mode selectable, Connection voltage 230V -/+ 5% [220V-240V], compliant with EN standards, with IEC CB test certificate LED, Built in Battery: Ni-Cd,Duration 3 hours, Viewing distance 2+A300m, Dimensions in mm: 270 x 119 x 49. |
| 32 | P&F of Fire man axe made of carbon steel handle insulated with rubber tested to 20,000 Volts. Manufactured as per Indianstandard IS:926. |
| 33 | Supply Fixing of following fire extinguisher CO2 type 4.5 kg. capacity (ISI Marked IS :2878 & TAC approved) completewith initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 34 | Supply & fixing of fire extinguisher, ABC Type 4.00 kg. capacity (ISI Marked IS:15683 & TAC approved) comlete with initialcharge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 35 | Providing and fixing pressure switch in M.S. pipe line including connection as required. |
| 36 | Pipes- providing laying testing & commissioning of C class heavy duty MS pipe including Welding Fitting like elbow. Tees, flanges, tapers, nuts bolts, gasket etc. and fixing the pipe on the wall/ ceiling with suitable clamp/ support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required.(Specification as per NBC 2016 by BIS Vol-1, Part-4 attached) |
| 37 | 100 mm |
| 38 | 80 mm |
| 39 | 25 mm |
| 40 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover andsuitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base |
| 41 | Providing and laying cement concrete in retaining walls, return walls, walls (any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts, buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window sills, fillets, sunken floor etc., up to floor five level, excluding the cost of centering, shuttering and finishing: 1:1%:3 (1 cement : 1% coarse sand (zone-lll) derived from natural sources : 3 graded stone aggregate 20 mmnominal size derived from natural sources). For base plateform of water tank. (3.14x0.9x0.9x0.15 =0.38 Cum) |
| 42 | Single Headed External Yard Hydrant Gun Metal Landing Valve comprising of 75mm inlet dia complete with min. 63mm diasingle female outlet (Type A) with pull out gun metal /PVC blank cap, lugs (to lock, unlock blank cap) & chain with ISI marked. CE CERTIFIED |
| 43 | Surface dressing of road withPaintingbetweenusing2.25kg.of bitumen per sq.mt with 1.65 cum of stone chipping, 13.2mm nominal size/100sq.mt of road surface including corolidation . |
| 44 | Excavation in foundations in ordinary soil (Loam clay or sand) including lift upto 1.5 m (5 fts.) and lead upto 30 mt. (100 fts.) & including filling, watering and ramming of excavated earth into the trenches or into the space between the building and the sides of foundation trenches or into the plinth and removal and disposal of surplus earth asdirected by the Engineer-Incharges upto a distance of 30mt. (100 fts) from the foundation trenches. |
| 45 | boring providing &installingcast in situ single under reamed piles |
| 46 | Providing and laying cement concrete 1:4:8 (1 cement :4 coarse sand :8 graded Stone aggregate 40 mm nominal size) including supply of all materials, labour T & P rtc required for proper completion of the work and curing complete alsoincluding cost of formwork in foundation & floors. |
| 47 | R.C.C. work with cement approved coarse sand and 20 mm. guage approved stone ballast in the proportion of 1:1.5:3 (M-20) in slab excluding supply of reinforcement and its fixing and binding the same with 24 B.W.G.G.I. binding wire and excluding necessary centering and shuttering etc.and also including supply of all materials, labour and tools and plants etc, required forproper completion of the works. Binding wire cost being inluded in the item. |
| 48 | R.C.C. work with cement approved coarse sand and 20 mm. guage approved stone ballast in the proportion of 1:1.5:3 (M-20) in beams excluding supply of reinforcement and its fixing and binding the same with 24 B.W.G.G.I. binding wire andexcluding necessary centering and shuttering etc. and also including supply of all materials, labour and tools and plants etc,required for proper completion of the works. Binding wire cost being inluded in the item. |
| 49 | R.C.C. work with cement approved coarse sand and 20 mm. guage approved stone ballast in the proportion of 1:1.5:3 (M-20) in raft foundation and footing excluding supply of reinforcement and its fixing and binding the same with 24 B.W.G.G.I.binding wire and excluding necessary centering and shuttering etc.and also including supply of all materials, labour and toolsand plants etc, required for proper completion of the works. Binding wire cost being inluded in the item. |
| 50 | R.C.C. work with cement approved coarse sand and 20 mm. guage approved stone ballast in the proportion of 1:1.5:3 (M-20) in columns excluding supply of reinforcement and its fixing and binding the same with 24 B.W.G.G.I. binding wire and excluding necessary centering and shuttering etc.and also including supply of all materials, labour and tools and plants etc,required for proper completion of the works. Binding wire cost being inluded in the item. |
| 51 | P/F Mild steel or iron in plain work such as reinforced concrete or reinforced, brick work (when not included in over all rates) wrought to required shape as necessary including bending for proper completion of the work and including supply of all steeland and over lapping & hooks. |
| 52 | M-150 brick work in 1:6 cement and coarse sand of 2.25 F.M. mortar in foundation and plinth including supply of all materials,labour, tools and plants etc. required for proper completion of the work. (1:6 cement & coarse sand) |
| 53 | 12mm cement plaster in single coat on single or half brick wall for exterior plastering up to floor two level including internal rounded angles chamfers, and/or roundedangles not exceeding 80mm in girth and finished even and smooth no extra formixing any additive. (1) 1 cement : 6 course sand. |
| 54 | Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade. New work (Two or morecoats applied @ 1.43 ltr/ 10 sqm. over and including priming coat of exterior primer applied @ 2.20 kg/ 10 sqm). |
| 55 | Chequerred precast cement concrete tiles 22 mm thick in footpath & courtyard, jointed with neat cement slurry mixed with pigment to match the shade of tiles, including rubbing and cleaning etc. complete, on 20 mm thick bed of cement mortar 1:4(1 cement: 4 coarse sand).) : Light shade pigment using white cement. |
| 56 | grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel boltsetc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in- charge, ( for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such |
| 57 | Centering and shuttering including strutting, propping etc. and removal of form for all heights : |
| 58 | Foundations, footings, bases of columns, etc. for mass concrete. |
| 59 | Columns,Pillars, Piers, Abutments, Posts and Struts. |
| 60 | Lintels, beams, plinth beams, girders, bressumers and cantilevers. |
| 61 | Suspended floors, roofs, landings, balconies and access platform. |
| 62 | of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, |
| 63 | cost of staff traning & modulas |
| 64 | GST Extra As per Applicable |