| 1 | Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth and getting out in soft/ loose soil, for laying of under ground electric cablecomplete all as specified and directed. |
| 2 | Taking out LT UG cables of any size by excavation and earth work in any type of soil, removing bricks or PCC cover of any size complete all as specified and directedNote:-Excavation, Joints & Jointing materials, new cable, additional bricks/PCC Covers, sand shall be measured & paid for separately. |
| 3 | Relaying old serviceable under ground LT cable of any size obtainedfrom serial item number 2.00 above complete all as specified and directed. |
| 4 | Supply, laying, jointing and testing in repairs/replacement of LT cable XLPE insulated, armoured, heavy duty electric cable multi stranded aluminum conductors, 1100V grade, of size 04 Sqmm 2 core with proper size of lugs and laid in trenches / ducts / through GI pipe / fixed to poles etc complete all as specified and directed.Note:-Excavation earthwork, cable covers, sand cushioning and GI protection pipe shall be measured and paid separately under respective item of this Schedule. |
| 5 | All as per serial item number 4.00 here-in-before but of size 16 Sqmm 4 core |
| 6 | Material and labour for river bed sand used in trenches/ ducts 08 cm under cable and 15 cm above the cable for cushioning/protection to cable and get thick 18cm after hand punning complete all as specified and directed |
| 7 | Laying onlyserviceable un-reinforced precast concrete cable cover class LV, Type 1, flat, of250 mm x 150 mm x 40 mm obtainedfrom trenches, abetting each other with gap between adjacent slab not exceeding10 mm over for cable protection complete all as specified and directed. |
| 8 | Supply and laying un-reinforced precast concrete cable cover, class LV, Type 1, flat, size 250 mm x 150 mm x 40 mm abetting each other with gap between adjacent slab not exceeding10mm over for cable protection complete all as specified and directed. |
| 9 | Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each complete all as specified and directed |
| 10 | Removing excavated surplus soil to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.50 metre above the starting point complete all as specified and directed. |
| 11 | Supply, fixing and testing LT cable jointing kitstraight through type heat shrinkable suitable for cable PVC /XLPEinsulated armoured heavy duty aluminum conductor 1100 volts grade LT cable of size 3.5/4core 16 to 50 sqmmand including taking out cable from faulty portion in any situation/position complete all as specified and directed. |
| 12 | All as per serial item number 11.00 here-in-before but size 3.5 core 70 sqmm to 150 sqmm . |
| 13 | Supply and laying galvanised steel water tubing, light grade, IS-1239 marked with all fittings IS marked and laid in trenches under roads in drains, fixed to poles/walls with required size flat iron clamp bolts, nuts and washers, pipesof40 mm bore , fixed in repair complete all as specified and as directed. |
| 14 | All as per serial item number 13.00 here-in-before but of size 50 mm. |
| 15 | Dismantling / taking down in repairs the street light / security lights of any capacity & description from existing LT pole/walls at any height and refixingthe fittings in existing / another location after repair work (replacement of defective parts, checking for loose connections etc) complete all as specified and as directed.Note:- (i) Replacement of defective parts / accessories shall be measured and paid separately under relevant items. (ii)Transport and T & P i.e. Ladder, safety items,lugs,insulation tape, GI screws, nut bolts etc.or any other equipment for repair of street light shall be provided by Contractor and cost for the same deemed to be include in respective items.(iii) Contractor shall submit job card for each repairs/maintenace under this item to concern JE (Printed Job card shall be provied by the contractor as per format given by Engineer-in-Charge). Charges for printing job card shall be inclusive in the item rate. |
| 16 | Supply and fix in repairs, brackets for street light fittingmade outof 32 mm dia G.I. Pipe light grade in shape and angle as directed not exceeding 1.5 mtrs in length fixedto pole with suitable size of M.S. clamps made of M.S flat of size 40 mm x 3 mm, 2 Nos, M.S nut & bolt with cup washers and dismantling old rusted/unserviceable bracket withits rusted clamps and nut bolts complete all as specified and directed.Note :- Rate of GI Pipe, clamps, flat and nut bolts inclusive in the item rate. |
| 17 | Supply and fix in repairs,flexible PVC insulatedmulticore FR PVC sheathed multistrandedcopper conductor cable of 1.0 Sqmm x 3 corefor voltage grade up to 1100 V conforming to IS 694 : 2010for connection oflight fittingfrom junction box orfrom over head conductorsto fitting complete all as specified and directed.Note :- PVC Conduit shall be measuerd and paid seperately under respective item. |
| 18 | Supply and fix in repairs,service wire 1100 volts grade PVC insulated PVC sheathed cable weather proof multi stranded with aluminum conductor of size 2 core 4.0 sqmm complete all as specified and directed. |
| 19 | Material and labour for cutting under road/PCC path and passing GI pipe for cable protection and making good as existing complete all as specified and as directed. |
| 20 | Supply and fix in repairs, LED street light fitting 60/70 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed. |
| 21 | Supply and fix in repairs, LED street light fitting 100 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed. |
| 22 | Supply and fix in repairs,LED flood light 100 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp complete all as specified and directed. |
| 23 | Supply and fix in repairs, LED flood light 200 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp complete all as specified and directed. |
| 24 | Supply and fix in repairs, LED Aviation light at overhead tank/Signal tower/Telephone tower or any high rise buildings at anylocation of Red colour, 230V AC complete all as specified and directed. |
| 25 | Supply and fix in repairs/replacement of auto /manual street light timer nature switch weather proof IP 54 protection enclosure made out of UV stabilized, FR grade special molding compound, rust proof, electric sock proof, vermin proof outdoor pole mountable with mounting bracket made out of GI and nut, bolts, washers including cable glands, openable door with 05kW single phase load with Power contactors rating 25 Amps 01 nos as incoming and outgoing with MCB rating of 32 Amps/phase and circuit wiring of min 6 sqmm including taking down existing switch complete all as specified and directed. Note :- Rate of GI clamps, nut bolts inclusive in the item rate. |
| 26 | Supply and fix in repairs/replacement of auto /manual street light timer nature switch weather proof IP 54 protection enclosure made out of UV stabilized, FR grade special molding compound, rust proof, electric sock proof, vermin proof outdoor pole mountable with mounting bracket made out of GI and nut, bolts, washers including cable glands, openable door with 08kW three phase load with Power contactors rating 25 Amps3 nos as incoming and outgoing with MCB rating of 32 Amps/phase and circuit wiring of min 16 sqmm including taking down existing switch complete all as specified and directed. Note :- Rate of GI clamps, nut bolts inclusive in the item rate. |
| 27 | Supply and fix in repairs/replacement for kiosk box for luminaries, weather proof made out of PVC/HDPE /FRP housing fire retardant, non fusing, shock & rust proof, single piece molded andcover with hinged door, pole mounting type comprising of aluminum TPNbus bar of 20 Amps of minimum size 333x233x120mm, fixed on pole with MS, clamps 30x5mm with necessary nuts, washer including MCB 16 Amps for out going complete all as specified and directed. Note :- Rate of TPN bus bar and MS clamp inclusive in the item rate. |
| 28 | All as per serial item number 27.00 here-in-before but of size 450 x 375 x 200 mm. |
| 29 | Supply and fix in repairs, LED driver 45/50W 1500mA suitable for LED light fitting complete all as specified and dircted. |
| 30 | Supply and fix in repairs, LED driver 75W/80W 2600mA suitable for LED light fitting complete all as specified and dircted. |
| 31 | Supply and fix in repairs, LED driver 100W,2600mA suitable for LED light fitting complete all as specified and dircted. |
| 32 | Supply and fix in repairs, LED driver 150/240W3000mA suitable for 240 watt LED light fitting complete all as specified and dircted. |
| 33 | Material and labour for maintenance/repair of highmast light of height upto 16 mtr. after safely lowering down head frame lantern carriage accomodating flood lights. Greasing and adequate tightening of all movable parts of base section i.emotor chain, sprockets, shaft of 3 phase elect wintch motor, steel wire rope after removing all rust/stain over surface of equipments by stain remover. Checking all electrical connections of feeder pillar box and replacing defective flood lights, drivers, switchgears, lugs etc before liftinglantern carriage frame assembly in its initial position complete all as specified and directed.Note:- (i) Replacement of defective flood lights/drivers shall be measured and paid separately under relevant items. (ii)Transport and T & P i.e. Ladder, safety items,or any other equipment for repair of high mast light shall be provided by Contractor and cost for the same to be incl in job itself. (iii) Contractor will ensure that periodical check to be done for making good all defects by replacing nuts/bolts/PVC connection etc and keep the light fitting in working condition through out the period of contract. |
| 34 | Trimming of tree branches touching to over head lines, up to 1.5 mtr distance all around of ACSR conductors of span 30meter to 50 meterof HT/LT feeders and depositing cut branches away from site as directedand clearance of HT/LT pole and sub station premises complete all as specified and directed. Note:- (i)Trimming of all branches oftrees falling under one span between two poleshall be considered as one span only. (ii) Contractor have to arrange all T&P, safety equipments manpower and vehicle for trimming at different locations. Contractor or his rep has to ensure power shut down of overhead lines before carrying out trimming. Contractor shall be responsible for any lapses/ mishappening occurred due to negligence of safety aspects. |
| 35 | Restretching/ tightening of ACSR conductor of any type and size by disconnectingfrom insulators from any location complete all as specified and directed.Note:- (i) Proper shut down has to be taken from MES. (ii)T & P i.e. Ladder, safety items,or any other equipment for repair tightening of ACSR conductor shall be provided by Contractor and cost for the same deemed to be included in respective items. |
| 36 | Supply and fix in repairs, pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut,100mm height, 65mm dia for 1100 volts grade complete all as specified and drected. |
| 37 | Supply and fix in repairs, shackle Type, Porcelain, vitreous, white, brown or green insulator including galvanised mild steel straps, washers, insulator bolts, washers and nuts, 1100 volt grade of size 75 mm height and 90mm dia complete all as specified and directed. |
| 38 | S&F in replacement, Contactor Triple Pole18Amps, 415 V ,9.0 kW cat part CE15D1 or equivalent for street light Auto Timers complete all as specified and directed. |
| 39 | Supply and fix in replacement, MCB Triple Pole and Neutral 40/63Amps, 415 V ,10KA B curve breaking capacity complete all as specified and directed. |
| 40 | Supply and fix in replacement, MCB Single Pole 6 to 32Amps, 240 V ,10KA B curve breaking capacity complete all as specified and directed. |
| 41 | Disconnecting and taking down security light fitting, brackets from poles of any height and shifting/reorientation the fitting in other/existing pole by using old brackets and reconnecting the same with all accessories complete all as specified and as directed. Note :- (i) The rate of Nut, bolts if required will be deemed to be included in quoted rate. (ii) T & P i.e. Ladder, safety items,or any other equipment for repairs shall be provided by Contractor. |
| 42 | Material and labour for painting of steel tubular swaged street light poles of height upto 11 mtrs with one coat of oil based alumunium paint, heat & UV protection,durable and long lasting,corrosion resistantand chemicals,including necessary preparation of surfaces before painting complete as specified and directed. Note:-T & P i.e. Ladder, safety items,or any other equipment for painting shall be provided by Contractor and cost for the same to be included in job itself. |
| 43 | Material and labour for preparation and painting 04 nos band / strips with blue and white paint alternately all around the HT/LT/street light pole with synthetic enamel paint at a distance of 30 cm and painting both side for numbering with black enamelled paint and writing LT/ PL No on both side of pole with white enamelled paint complete all as specified and directed. |
| 44 | Material and labour for surface excavation not exceeding 30cm deep and avaraging 15cm deep for cleaing, grass cutting, small trees, unwanted vegitions, grubbing of tree trunk including cutting of trunk portion protruding over ground, digging out roots, filling space holes and levelling of ground in the installation/sub stations and removing cut grass, roots and trees complete all as specified and diected. |