| 1 | Dismantling unserviceable cross arms, clamps etc complete all as specified and directed. |
| 2 | M&L for Cross arms, bracings, supports, clamps, eye hook and back plates fabricated from structural steel sections including pole clamps, stay clamps, D clamps nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed including painting with twocoats ofaluminiumpaintover a coat of red oxide primercomplete all as specified and directed. |
| 3 | Refixing only serviceable Cross arms, bracings, supports, clamps, eye hook and back platesas obtained from dismantling of old cross arms including provision of new bolts, nuts etc .in any shape or size as indicated or directed including painting with one coat ofaluminiumpaint complete all as specified and directed. |
| 4 | M & L for pruning / trimming the branches of trees if any along overhead line, 3m on all side below/ above/ sides of overhead line and removing the same upto 150 m away each span not exceeding 45 m complete all as specified and directed. |
| 5 | M & L cutting grasses, shrubs/herbs surrounding LT poles, feeder pillar box installations by mechanical or manual T&P, removing the debris at a distance not exceeding 50m and depositing where directed complete all as specified and directed. |
| 6 | Dismantling of old insulator any type and description from existing poles complete all as specified and directed. |
| 7 | M&L for pin type insulators LT 1100 Volts grade porcelain vitreous white or brown including one galvanized mild steel spindle, two galvanized iron washers, iron nut, 100 mm height, 65 mm diacomplete all as specified and directed. |
| 8 | Refixing only serviceablepin type insulatorsas obtained from dismantling of old insulator including provision ofone galvanized mild steel spindle, two galvanized iron washers, iron nut, etc complete all as specified and as directed. |
| 9 | M&L for shackle type insulator LT 1100 volt grade porcelain vitreous white or brown including galvanised mild steel straps, washers, insulator bolts, nuts 12 mm dia, 75 mm height and 90 mm dia, section of straps 31mmx3mm of insulatorcomplete all as specified and directed. |
| 10 | Refixing only serviceableshackle type insulatorsas obtained from dismantling of old insulator including provision ofnew bolts, nuts, washers, etc complete all as specified and directed. |
| 11 | Dismantling of oldearth wire, craddle guard etc of any description and size complete all as specified and directed. |
| 12 | M&L for galvanised steel wire 3.15mm or 4.00mm dia as earth continuity conductor and fixed to pole, binding with aluminium binding wires complete all as specified and directed. |
| 13 | M & L for Stringing / stretching, including jointing in situ of each span not more than 45 m betweentwo electric poleshaving 4 Nos of ACSR of any size including GI earth continuity wire, with/ withoutguarding wires onelectric poles of any size at different locations all as ordered to the extent of permissible sag or tension by removing jumpers or bindings from insulators and making fresh binding with aluminium tapes after stringing complete as ordered . Note :- One span including 4 wire of LT over head line and 2 Nos of earth wire. |
| 14 | All as per item No 13.00 here-in-before but for 2 Nos of ACSR. |
| 15 | S&F PVC/Fibre seperator for LT lines 1100 volts overhead conductors 2 wire system for horizontal spacing between the conductors fixed with nuts, bolts, washer etc. complete all as specified and directed. |
| 16 | S&F PVC/Fibre seperator for LT lines 1100 volts overhead conductors 4 wire system for horizontal spacing between the conductors fixed with nuts, bolts, washer etc. complete all as specified and directed. |
| 17 | Dismantling unserviceable/old ACSR conductors of any size from over head lines, poles by removing binding wire, service wire, cables and removal from site complete all as specified and directed. |
| 18 | M & L for aluminium conductor, steel reinforced (ACSR) of any size as approved on HT/LT Poles including straining, binding to insulators with aluminium binding wire with connectors, etc, providing PVC sleeves for jumpers as in OH conductors including dismantling of old ACSR or AAD conductors complete all as specified and directed. |
| 19 | Material and labour for Refixing only ofaluminium conductor, steel reinforced (ACSR) of any size as approved on HT/LT Poles including straining, binding to insulators with aluminium binding wire with connectors, etc,including dismantling of old ACSR or AAD conductors complete all as specified and directed. |
| 20 | Dismantling unserviceable steel poles of any size including demolition of foundation concrete & removing from site complete all as specified and directed. |
| 21 | M&L for erection of steel tubularsteel tubular swaged pole type 410 SP - 31 (9.00 metres long) including cast iron base plate, finial taper plugandand painted with two coat of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed. |
| 22 | Dismantling unserviceable stay assembly completeincluding demolition of foundation concrete & removing from site complete all as specified and directed. |
| 23 | M&L for stay assembly comprising 14mm dia iron stay bow, stay strand wire of size 7/3.15mm with stay rod of diameter 16mm complete with all accessories as shown in electrical plate no. 1 of SSR part-I 2009 including dismsntling of oldstay assembly of any description with foundation, etc. complete all as specified and directed. |
| 24 | M&Lfor loop type insulator, vitreous porcelain, white, brown or green with overall dimension 95mmX65mm, clearence of hole 16mm suitable for 1100 Volts complete all as specified and directed. |
| 25 | M&L for cement concrete 1:4:8 type D-2 using 40 mm graded crushed stone aggregate as in foundation complete all as specified and directed. |
| 26 | M&L for PCC 1: 3 : 6 type C-1 (using 20 mm graded mechanically crushed stone aggregate) as in mass concrete including necessary form work for coping to the new/existingSteel Poles complete all as specified and directed. |
| 27 | M&L for cable jointing kit for LT (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for for aluminium Conductor cablesize 6-16 Sqmm 4 core complete all as specified and directed. |
| 28 | M&L for cable jointing kit for LT (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for for aluminium Conductor cablesize 25-50 Sqmm 3.5 core complete all as specified and directed. |
| 29 | M&L for cable jointing kit for LT (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for for aluminium Conductor cablesize 70-120 Sqmm 3.5 core complete all as specified and directed. |
| 30 | M&L for cable jointing kit for LT (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for for aluminium Conductor cablesize 150-185 Sqmm 3.5 core complete all as specified and directed. |
| 31 | M&L for cable jointing kit for LT (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for for aluminium Conductor cablesize 240-300 Sqmm 3.5 core complete all as specified and directed. |
| 32 | S&F MCCB with Thermal - magnetic release of 80-100 Amps, 4 Pole, 415V, 25 kA, Ics=100%Icu including all accessories and taking down old unserviceable one complete all as specified and directed. |
| 33 | S&F MCCB with Thermal - magnetic release of 160-250 Amps, 4 Pole, 415V, 36 kA, Ics=100%Icuincluding all accessories and taking down old unserviceable one complete all as specified and directed. |
| 34 | S&F MCCB with Thermal - magnetic release of 268-400 Amps, 4 Pole, 415V, 36 kA, Ics=100%Icuwith adjustable over load settingand adjustable short circuit setting including all accessories and taking down old unserviceable one complete all as specified and directed. |
| 35 | M&Lfor complete removal of existing treatment ofLT Panel, box, board, cross arms etc and applyingtwo coats synthetic enamel paint over a coat of red oxide primer, complete all as specified and directed. |
| 36 | Earthing complete with GI earth plate electrode of size 60cm x 60cm x 6mm burieddirectly in ground vertically at a depth not less than 2.25 metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level sorrounded from all sides by 15cm thick and packed layer of charcoal dust and common salt fliing in alternate layers etc and connected to and including galvanised earth strip of size 25 x 4mm upto 7.5 mtr by means of bolts, nuts, check nuts and washers made of galvanised iron and protected by light grade 40 mm dia GI pipe connected to main control board and GI pipe medium grade 20 mm bore for watering and including funnel, wire mesh, charcoal salt etcRCC pit cover flush to earth pit 50mm thick reinforced with 8mm TMT bar 100mmC/C and PCC chamber pit with PCC (1:3:6) type C1 (using 20mm graded aggregate)including excavation and earthwork disposal of surplus soil to distance not exceeding 50 metre) and testing after completion all as specified and shown on plate No 3 of SSR Part-I 2009 |
| 37 | S&F inreplacement Aluminium strip 25 x 4mm with saddles and fixing screws and run through wall provided with nonconducting plank as in down conductors of lighting arrestor complete all as specified and directed. |
| 38 | S&F inreplacement copper strip 20X3.15mm burried in ground/ fixing with saddle and screws for roof and wall as earth continuity conductor complete all as specified and directed. |
| 39 | Cutting out burnt out cable end and reconnecting with providing new lugs, tapes etc. for cable of size 25 sqmmto 50 sqmm 3.5 core complete all as specified and directed. |
| 40 | Cutting out burnt out cable end and reconnecting with providing new lugs, tapes etc. for cable of size 70 sqmmto 95 sqmm 3.5 core complete all as specified and directed. |
| 41 | Cutting out burnt out cable end and reconnecting with providing new lugs, tapes etc. for cable of size 120 sqmmto 300 sqmm 3.5 core complete all as specified and directed. |
| 42 | S&Faluminium thimble for cable of size 300sqmm/400sqmm complete all as specified and directed. |
| 43 | S&Faluminium thimble for cable of size 95sqmm/120sqmm complete all as specified and directed. |
| 44 | S&Faluminium thimble for cable of size 70sqmm complete all as specified and directed. |
| 45 | S&Faluminium thimble for cable of size 50sqmm complete all as specified and directed. |
| 46 | S&Faluminium thimble for cable of size 35sqmm complete all as specified and directed. |
| 47 | S&Faluminium thimble for cable of size 25sqmm complete all as specified and directed. |
| 48 | S&Faluminium thimble for cable of size 16sqmm complete all as specified and directed. |
| 49 | S&Faluminium thimble for cable of size 10sqmm complete all as specified and directed. |
| 50 | Supply and fixing LED street light of capacity 46/45 Watt made up of pressure die cast aluminium housing withhigh power LED as light source and lens embedded PC cover including electronic driver should have luminaire efficacy ≥120 lumens/watt,CRI>70 ,PF > 0.95,CCT≥5500,IP66,impact resistance IK 07 ,inbuiltprotection against lightning , over voltage , short circuit and surge/spike protection device upto5 kVincluding taking out old unserviceable luminare complete all as specified and directed. |
| 51 | Supply and fixing LED street light of capacity 60 Watt made up of pressure die cast aluminium housing withhigh power LED as light source and lens embedded PC cover including electronic driver should have luminaire efficacy ≥120 lumens/watt,CRI>70, PF > 0.95,CCT≥5500,IP66,impact resistance IK 07, inbuiltprotection against lightning , over voltage , short circuit and surge/spike protection device upto5 kVincluding taking out old unserviceable luminare complete all as specified and directed. |
| 52 | S &F in repair street light fitting of 90 Watt LED made ofpressure die cast aluminium housing with toughned glass and LEDs with secondary optics and IP 66 protectionand lens embedded PC Cover having top opening seperate driver compartment,should have luminaire efficacy ≥110 lumens/watt,CRI>70 ,PF > 0.95,CCT≥5500,IP66,impact resistance IK 07 ,inbuiltprotection against lightning , over voltage , short circuit and surge/spike protection device upto5 kVcomplete also tested for 440 Volt for 8 hour Phase to phase without any damage complete all as specified and directed. |
| 53 | S &F in repair street light fitting of 120 Watt LED made ofpressure die cast aluminium housing with toughned glass and LEDs with secondary optics and IP 66 protectionand lens embedded PC Cover having top opening seperate driver compartment,should have luminaire efficacy ≥110 lumens/watt,CRI>70 ,PF > 0.95,CCT≥5500,IP66,impact resistance IK 07 ,inbuiltprotection against lightning , over voltage , short circuit and surge/spike protection device upto5 kVcomplete also tested for 440 Volt for 8 hour Phase to phase without any damage complete all as specified and directed. |
| 54 | Supply and fixing LED flood lightof capacity 50 Watt made up of pressure die cast aluminium housing withhigh power LED as light source and lens embedded PC cover including electronic driver should haveLED efficacy≥100 lumens/watt, CRI>70 PF 0.95,CCT≥5500, IP66, impact resistance IK 07, inbuilt 5kV surge protection device including taking out old unserviceable luminare complete all as specified and directed. |
| 55 | Supply and fixing LED flood lightof capacity 80 Watt made up of pressure die cast aluminium housing withhigh power LED as light source and lens embedded PC cover including electronic driver should haveLED efficacy≥100 lumens/watt,CRI>70 PF 0.95, CCT≥5500, IP66, impact resistance IK 07, inbuilt 5kV surge protection deviceincluding taking out old unserviceable luminare complete all as specified and directed. |
| 56 | Supply and fixing LED flood lightof capacity 100 Watt made up of pressure die cast aluminium housing withhigh power LED as light source and lens embedded PC cover including electronic driver should haveLED efficacy ≥100 lumens/watt,CRI>70 PF 0.95, CCTCCT≥5500, IP66, impact resistance IK 07, inbuilt 5kV surge protection device including taking out old unserviceable luminare complete all as specified and directed. |
| 57 | Supply and fixing LED flood lightof capacity 150 Watt made up of pressure die cast aluminium housing withhigh power LED as light source and lens embedded PC cover including electronic driver should have LED efficacy ≥100 lumens/watt, CRI>70 PF 0.95, CCTCCT≥5500, IP66, impact resistance IK 07, inbuilt 5kV surge protection deviceincluding taking out old unserviceable luminare complete all as specified and directed. |
| 58 | Supply and fixing LED flood lightof capacity 200 Watt made up of pressure die cast aluminium housing withhigh power LED as light source and lens embedded PC cover including electronic driver should haveLED efficacy ≥100 lumens/watt, CRI>70 PF 0.95, CCTCCT≥5500, IP66, impact resistance IK 07, inbuilt 5kV surge protection deviceincluding taking out old unserviceable luminare complete all as specified and directed. |
| 59 | Supply and fixing LED flood lightof capacity 250 Watt made up of pressure die cast aluminium housing withhigh power LED as light source and lens embedded PC cover including electronic driver should haveLED efficacy ≥100 lumens/watt, CRI>70 PF 0.95, CCTCCT≥5500, IP66, impact resistance IK 07, inbuilt 5kV surge protection deviceincluding taking out old unserviceable luminare complete all as specified and directed. |
| 60 | Supply & fixing in repair and testing of bollard light upto 20W, 230 voltsor nearest size with die cast aluminiumlighting with high power LED with B22 holder as light source body,IP-65, with all necessary fixing arrangments, exacavation work, PCC work and earth work etc complete all as specefied and directed. |
| 61 | Supply & fixing and testing of Gate light / post-top light fitting 35W / 40W LEDwith die cast aluminium body with drive, 230 volts or nearest size and withIP-65 protection with high power LED as sourceall necessary fixing arrangments and fittings etc including taking out old one of any type complete all as specefied and directed.Note: For Item No. 50.00to Item No. 61.00. (i) PVC insulated PVC sheathed, multistranded aluminium or copper conductor cable of size 1.5 sqmmX 3 core from light fitting to Street light feeder (max 2.0 mtr) deemed to be included in quoted rate. |
| 62 | Taking down old unsv/ corrodedLT feeder pillar box/ DB Box/ Busbar Chamber of any sizes or types (after disconnection of all electrical connections) complete for replacement with new one complete all as specified and directed. |
| 63 | Supply and fixstreet light junction box ofmade of high quality polycarbonate with IP-66 protection (Dust and vermin proof according to IEC-60529) Totally insulated made of halogen and silica free recyclable material having high quality gasket made out of polyurethane Din rail , with locking arrangement with cable glandsuitable upto 10 sqmm cable and necessary fixing arrangements such as clamps, nuts, bolts etccomplete all as specified and directed. |
| 64 | M&L for sub-main wiring with 2 runs of 1.5 sqmm, single core, FR-LSH PVC insulated & unsheathed cable conforming to IS-694, 1100 volts with copper conductor multi stranded drawn in and including 20mm dian non metallic PVC grey conduit with all accessories such as Tees, Elbows, junction box, reducers etc as requied alongwith one run of 1.5 sqmm single core FR-LSH PVC insulated & unsheathed copper conductor as continuous earth wire dolly and connecting from junction box to street light and tiding with aluminium strip with the pole as ordered and testing on completion including taking down old wiring any type of conduit complete all as specified and directed. Note: 2 run of 1.5 Sqmm cable + 1 run of 1.5 Sqmm cable earthed cable + 1 run of PVC conduit together shall be measured as one unit. |
| 65 | Supply and fixing in repairs street light bracket made of GI pipe 40 mm bore light grade(bend to shape), 2 metre long and fixed with Ms flat iron clamp (clamp shall be 40 X 5mm), nuts, bolts and washers on pole complete all as specified and directed. |
| 66 | Supply & fix fabrication of LT Panel Board floor mounted outdoor cubical type with compartments for each out going and incoming feeders made of CRCA sheet of 3.15 mm thick CPRI approved, CRCA sheet powder coated of suitable size with support of angle iron of 50 x 50 x 6 mm angle iron bottom legs frame with double hinged with front and rear opening, hinged doors with projected on raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for existing cables, danger notice plate, strickering of Switch gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS tinned Aluminium bus bar with TPN AC, 50 Hz ,415 V 600 Amp capacity complete with powder coating, with accomodating and including with following items:-Incoming:(a) MCCB 4 Pole, 415 V, Adjustable type, 400 Amps with breaking capacity 36 KA-01 No.Outgoing:a) MCCB 4 Pole, 415 V, 160 Amps with breaking capacity 36 KA-04 Nos.b) Intelligent Panel meter to measure voltage, current, frequency, power factor, kWH, etc with all connected CTs c) LED indicating lamps with colour Red, Yellow, Blue - 01 Set |
| 67 | Supply & fix fabrication of LT Panel Board floor mounted outdoor cubical type with compartments for each out going and incoming feeders made of CRCA sheet of 3.15 mm thick CPRI approved, CRCA sheet powder coated of suitable size with support of angle iron of 50 x 50 x 6 mm angle iron bottom legs frame with double hinged with front and rear opening, hinged doors with projected on raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for existing cables, danger notice plate, strickering of Switch gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS tinned Aluminium bus bar with TPN AC, 50 Hz ,415 V 1000 Amp capacity complete with powder coating, with accomodating and including with following items:-Incoming:a) ACB, 4P, 630 Amp, 50 KA, Microprocessor based with LSIG protection alongwith complete connected assy as per OEMManual draw out typecomplete all as specified and directed- 01 No.Outgoing:a) MCCB 4 Pole, 415 V, Adjustable type, 250 Amps with breaking capacity 36 KA-05 Nos.b) Intelligent Panel meter to measure voltage, current, frequency, power factor, kWH, etc with all connected CTsc) LED indicating lamps with colour Red, Yellow, Blue - 01 Set |
| 68 | Supply & fix fabrication of LT Panel Board floor mounted outdoor cubical type with compartments for each out going and incoming feeders made of CRCA sheet of 3.15 mm thick CPRI approved, CRCA sheet powder coated of suitable size with support of angle iron of 50 x 50 x 6 mm angle iron bottom legs frame with double hinged with front and rear opening, hinged doors with projected on raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for existing cables, danger notice plate, strickering of Switch gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS tinned Aluminium bus bar with TPN AC, 50 Hz ,415 V 1000 Amp capacity complete with powder coating, with accomodating and including with following items:-Incoming:a) MCCB 4 Pole, 415 V, Adjustable type, 630 Amps with breaking capacity 50 KA-01 No. Outgoing:a) MCCB 4 Pole, 415 V, Adjustable type, 200 Amps with breaking capacity 36 KA-5 Nos.b) Intelligent Panel meter to measure voltage, current, frequency, power factor, kWH, etc with all connected CTs c) LED indicating lamps with colour Red, Yellow, Blue - 01 Set |
| 69 | Taking out old unserviceable UG cable of any size/ type from trenches / wall / roof etc. for necessary repair/ replacement / re-laying works complete all as specified and directed.Note : Excavation and earth work shall be measured and paid seperately. |
| 70 | M&L for relayingof faulty UG XLPE cable of size 3.5 core, 120 to 240 sqmm alongwith brick protection, sand cushioning etc as obtained from taking up/down old cable here in before intrenches/ wall/ roof etc. including cutting and jointing through cable jointing kit as required and connecting to the main switches/cut outs MCB/MCCB with necessary lugs after cutting to required length complete all as specified and directed. |
| 71 | M&L for relayingof faulty UG XLPE cable of size 4 core, 16 to 95 sqmm alongwith brick protection, sand cushioning etc as obtained from taking up/down old cable here in before intrenches/ wall/ roof etc. including cutting and jointing through cable jointing kit as required and connecting to the main switches/cut outs MCB/MCCB with necessary lugs after cutting to required length complete all as specified and directed. |
| 72 | Supply & Laying in trenches or fixing on wall or passing through pipe or in cable ducts, 1100 volts grade XLPE (FRLS), armoured, electric power cables (heavy duty) with aluminium conductorof size 25 sqmm 4 core complete all as specified and directed. Note : The rate quoted inclusive of cable glands with suitable aluminium lugs where ever required. |
| 73 | Supply & Laying in trenches or fixing on wall or passing through pipe or in cable ducts, 1100 volts grade XLPE (FRLS), armoured, electric power cables (heavy duty) with aluminium conductorof size 50 sqmm 3.5 core complete all as specified and directed. Note : The rate quoted inclusive of cable glands with suitable aluminium lugs where ever required. |
| 74 | Supply & Laying in trenches or fixing on wall or passing through pipe or in cable ducts, 1100 volts grade XLPE (FRLS), armoured, electric power cables (heavy duty) with aluminium conductorof size 70 sqmm 3.5 core complete all as specified and directed. Note : The rate quoted inclusive of cable glands with suitable aluminium lugs where ever required. |
| 75 | Supply & Laying in trenches or fixing on wall or passing through pipe or in cable ducts, 1100 volts grade XLPE (FRLS), armoured, electric power cables (heavy duty) with aluminium conductorof size 95 sqmm 4 core complete all as specified and directed. Note : The rate quoted inclusive of cable glands with suitable aluminium lugs where ever required. |
| 76 | Supply & Laying in trenches or fixing on wall or passing through pipe or in cable ducts, 1100 volts grade XLPE (FRLS), armoured, electric power cables (heavy duty) with aluminium conductorof size 120 sqmm 3.5 core complete all as specified and directed. Note : The rate quoted inclusive of cable glands with suitable aluminium lugs where ever required. |
| 77 | Supply & Laying in trenches or fixing on wall or passing through pipe or in cable ducts, 1100 volts grade XLPE (FRLS), armoured, electric power cables (heavy duty) with aluminium conductorof size 150 sqmm 3.5 core complete all as specified and directed. Note : The rate quoted inclusive of cable glands with suitable aluminium lugs where ever required. |
| 78 | Supply & Laying in trenches or fixing on wall or passing through pipe or in cable ducts, 1100 volts grade XLPE (FRLS), armoured, electric power cables (heavy duty) with aluminium conductorof size 185 sqmm 3.5 core complete all as specified and directed. Note : The rate quoted inclusive of cable glands with suitable aluminium lugs where ever required. |
| 79 | Supply & Laying in trenches or fixing on wall or passing through pipe or in cable ducts, 1100 volts grade XLPE (FRLS), armoured, electric power cables (heavy duty) with aluminium conductorof size 16 sqmm 4 core complete all as specified and directed. Note : The rate quoted inclusive of cable glands with suitable aluminium lugs where ever required. |
| 80 | Supply & Laying in trenches or fixing on wall or passing through pipe or in cable ducts, 1100 volts grade XLPE (FRLS), armoured, electric power cables (heavy duty) with aluminium conductorof size 10 sqmm 4 core complete all as specified and directed. Note : The rate quoted inclusive of cable glands with suitable aluminium lugs where ever required. |
| 81 | Supply & Laying in trenches or fixing on wall or passing through pipe or in cable ducts, 1100 volts grade XLPE (FRLS), armoured, electric power cables (heavy duty) with aluminium conductorof size 10 sqmm 2 core complete all as specified and directed. Note : The rate quoted inclusive of cable glands with suitable aluminium lugs where ever required. |
| 82 | Excavation in trenches n.exc 1.5mtr wide and n.exc. 1.5m in depth for foundation and getting out in soft/loose soil complete all as specified and directed. |
| 83 | Supply & laying Sand coarse dry as in cushioning of underground electric cable in trenches, laid to a uniform thickness of 23cm (15cm under the cable & 8cm over the cable) and gently punned down to 18cm thickness complete all as specified and as directed. Note :- Only punned down sand shall be measured. |
| 84 | M&L for bricks sub class ‘B’ brick old size for cable protection laid in flat in trenches over the cable perpendicular to the direction of cable complete all as specified and directed. |
| 85 | Returning filling in including spreading, levelling, watering and well ramming in layers n.exc. 25cm complete all as specified and directed. |
| 86 | Removing of excavated soil not exc 50cm & depositing where as directed at a level n.exc 1.5m above starting point complete all as specified and directed. |
| 87 | Refixing only serviceable GI pipe light grade 40mm boreas obtained from taking up/down cablewith provision of newfittingsas in protection of cable at road crossing/hard standing/pole protection fixed with clamps, including taking up/ down old pipecomplete all as speciffied and directed. |
| 88 | Refixing only serviceable GI pipe light grade 50mm boreas obtained from taking up/down cablewith provision of new fittings as in protection of cable at road crossing/hard standing/pole protection fixed with clamps,including taking up/ down old pipe complete all as speciffied and directed. |
| 89 | M &L Complete removal of old paint by scrappingand removing for preparingsurfaces of existing old steel tubular poles 8.5m/9.00m long including scrapping, brushing down old paint with emery paper and applying one coat of aluminium paint including cross arms, street light brackets etc and making strip upto 1.5m above ground level by black/yellow paint in alternate layers with numbering of poles complete all as specified and directed. |
| 90 | M&L for GI pipe light grade 40mm bore dia with all fittings to be laid in trenches or in floors,including taking down rusted one complete all as speciffied and directed. |
| 91 | M&L for GI pipe light grade 50mm bore dia with all fittings to be laid in trenches or in floors,including taking down rusted one complete all as speciffied and directed. |
| 92 | M& L for Manual boring under roads/hard standingby reqd T&P without disturbing the top surface of the road for throughing the cable in GI Pipe of n exc 80 mm dia complete all as specified and directed. |
| 93 | Excavation in trenches n.exc 1.5mtr wide and exc. 1.5m in depth for foundation and getting out in soft/loose soil complete all as specified and directed. |