| Sl. No. | Item Description |
| 1 | SCHEDULE \"A\" PART IA (TO BE QUOTED BY THE CONTRACTOR) is not prepriced by MES and prepriced rates indicated as blank under col 5 signifies this fact only. Bidders shall insert their lumpsum amount of BOQ Ser item Nos. 1 to 7 in the Green coloured field under Col-6 only.Note: The quoted rates against the items under this schedule are deemed to include for the provisions contained in Scope of Work and Sch \"A\" Notes. Ref Sch \"A\" Notes complete before quoting these items. Structural designs and architectural/ structural drawings for structures and foundations for the buildings/ structures shall be prepared to comply with the provisions for design and analysis of RCC structures as per latest editions of relevant IS Codes. |
| 2 | Schedule ‘A’ Part IA BUILDINGS/ STRUCTURES (TO BE QUOTED BY THE CONTRACTOR) |
| 3 | Lumpsum price worked out for Design and Construction of RCC RADAR RAMP on \"Design-Build\" mode including all services as listed in Schedule ‘A’ Part IA complete all as specified in scope of work, Sch \"A\" Notes, drawings, specifications and other parts of tender documents as directed. |
| 4 | Lumpsum price worked out for Design and Construction of IFF TOWER on \"Design-Build\" mode including all internal services as listed in Schedule ‘A’ Part IA complete all as specified in scope of work, Sch \"A\" Notes, drawings, specifications and other parts of tender documents as directed. |
| 5 | Lumpsum price worked out for Design and Construction of MAIN RECEIVING STATION on \"Design-Build\"mode including all internal services as listed in Schedule ‘A’ Part IA complete all as specified in scope of work, Sch \"A\" Notes, drawings, specifications and other parts of tender documents as directed. |
| 6 | Lumpsum price worked out for Design and Construction of SUBSTATION on \"Design-Build\" mode including all internal services as listed in Schedule ‘A’ Part IA complete all as specified in scope of work, Sch \"A\" Notes, drawings, specifications and other parts of tender documents as directed. |
| 7 | Lumpsum price worked out for Design and Construction of SUBSTATION PUMP HOUSE on \"Design-Build\" mode including all internal services as listed in Schedule ‘A’ Part IA complete all as specified in scope of work, Sch \"A\" Notes, drawings, specifications and other parts of tender documents as directed. |
| 8 | Lumpsum price worked out for Design and Construction of BOREWELL PUMP HOUSE on \"Design-Build\" mode including all internal services as listed in Schedule ‘A’ Part IA complete all as specified in scope of work, Sch \"A\" Notes, drawings, specifications and other parts of tender documents as directed. |
| 9 | Lumpsum price worked out for Design and Construction of MAIN PUMP HOUSE CUM FIREFIGHTING BUILDING on \"Design-Build\" mode including all internal services as listed in Schedule ‘A’ Part IA complete all as specified in scope of work, Sch \"A\" Notes, drawings, specifications and other parts of tender documents as directed. |
| 10 | NOTE: Schedule ‘A’ Part IB to XII under Ser No. 8.00to 19.00 are prepriced by MES. Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only. |
| 11 | Lump sum price worked out for BUILDINGS/ STRUCTURES as listed in Sch \"A\" Part-IB. |
| 12 | Lump sum price worked out for EXCAVATION, EARTH WORK AND SITE CLEARANCE as listed in Sch \"A\" Part-II |
| 13 | Lump sum price worked out for TARMAC/ DISPERSAL as listed in Sch \"A\" Part III |
| 14 | Lump sum price worked out for ROAD/ PATH/ HARDSTANDING/ CULVERT as listed in Sch \"A\" Part IV |
| 15 | Lump sum price worked out for AREA DRAINAGE as listed in Sch \"A\" Part V |
| 16 | Lump sum price worked out for EXTERNAL WATER SUPPLY as listed in Sch \"A\" Part VI |
| 17 | Lump sum price worked out for EXTERNAL ELECTRIFICATION AND SCADA SYSTEM as listed in Sch \"A\" Part VII |
| 18 | Lump sum price worked out for SMART STREET LIGHT as listed in Sch \"A\" Part VIII |
| 19 | Lump sum price worked out for FENCING/ GATE/ COMPOUND WALL as listed in Sch \"A\" Part IX |
| 20 | Lump sum price worked out for FIRE FIGHTING SYSTEM as listed in Sch \"A\" Part X |
| 21 | Lump sum price worked out for LIGHTENING PROTECTION as listed in Sch \"A\" Part XI |
| 22 | Lump sum price worked out for SEWAGE DISPOSAL as listed in Sch \"A\" Part XII |
| 23 | SCHEDULE \"A\" PART - XIII MISCELLANEOUS ITEMS is not prepriced by MES and prepriced rates indicated blank under column 5 signifies this fact only. Bidder shall insert their rates in Green filed under Col-6. |
| 24 | ROAD/ PATH/ HARDSTANDING/ CULVERT |
| 25 | Material and labour for 200 mm thick (compacted thickness) Granular Sub Base (GSB) stabilised using cement forming Cement Treated Sub Base (CTSB) using granite, basalt, or trap stone coarse aggregates of grade IV grading as per MoRTH, Table 400-1, stabilised using cement OPC-43 Grade cement content @ 2% (exact quantity of cement to be finalized during design mix stage), mixed in mechanical mix plant at OMC arrived during the design mix stage; deposited, spread in uniform layer with mechanical paver and levelled in layers not exceeding 200 mm thick, compacted using 8 to 12 tonne vibratory roller to achieve minimum 7 day UCS 1.5 - 3.0 Mpa desired density 98% density as per MoRTH 5th edition clause 401 complete all as specified and directed.Note: For the purpose of pricing this item, the cement content shall be considered as 2%. However actual cement content shall be worked out as per design mix and nothing extra shall be paid on this account. Minus price adjustment shall be made @ Rs 6.91 per kg in case of quantity of cement used less than @ 2% by weight of Design Mix |
| 26 | Material and labour for 150 mm thick (compacted thickness) Granular Base Course stabilised using cement forming Cement Treated Base (CTB) using granite, basalt, or trap stone coarse aggregates of grading as per MoRTH (5th revision), Table 400-4, stabilised using cement OPC-43 Grade cement content @ 3% (exact quantity of cement to be finalized during design mix stage), mixed in mechanical mix plant at OMC arrived during the design mix stage; deposited, spread in uniform layer with mechanical paver and levelled in layers not exceeding 150 mm thick, compacted using 8 to 12 tonne vibratory roller to achieve minimum 7 day UCS 4.5 - 7.0 Mpa desired density 98% density as per MoRTH 5th edition clause 401 complete all as specified and directed.Note: For the purpose of pricing this item, the cement content shall be considered as 3%. However actual cement content shall be worked out as per design mix and nothing extra shall be paid on this account. Minus price adjustment shall be made @ Rs 6.91 per kg in case of quantity of cement used less than @ 3% by weight of Design Mix |
| 27 | Material and labour for providing stress absorbing membrane interlayer (SAMI) in accordance to clause 517 of MoRTH over the CTB layer with elastomeric modified binder (PMB-76-10 conforming to IS-15462-2019) @ 1.2 kg/sqm as per IRC-37-2018 and dry stone chipping of size 11.2 mm sprayed @ 0.01 cum/sqm using hydraulic chip spreader sweeping the surface for uniform spread of aggregate and rolled by pneumatic roller complete all as specified and directed. |
| 28 | Supply and fix precast RCC box culvert, M50 grade, of internal dimensions 500 x 500 mm, each piece of culvert 2 metre long and jointed and pointed in CM (1:3) as in box culvert for drainage or cable crossing or similar applications such as underpasses, service tunnels, subways, bridges, stream culverts, cattle pass etc. complete all as specified and directed.Note: 1. The quoted rate shall be inclusive of all reinforcement2. Box culvert shall be design for 50 Ton wheel load/ 10 Ton axle load with heavy truck movement and vetted by IIT/NIT. |
| 29 | Material and labour for providing, laying and consolidating 40 mm thick dense bituminous concrete (consolidated thickness) with minimum 5.5% binder content (by using paving bitumen of grade VG-40) by weight of total mix, mixed in hot mix plant and laid by using mechanical sensor paver, rolled and compacted to required camber and gradient complete all as specified and as directed. |
| 30 | SEWAGE DISPOSAL |
| 31 | Supply, laying and testing of Double Wall Corrugated (DWC) high density Polyethylene (HDPE) pipes of180mm outer dia/ 163mm internal dia and stiffness class-8 (SN-8) with ISI marked (with CML no) with and including all fittings and jointing material for sewage line laid in trenches as specified in IS 16098-2013 part-2 complete all as specified and directed.Note:- Construction method shall be strictly comiled as per clause no A-4 of Annex IA of ISA 16098 Part II. |
| 32 | Material and labour for on site LLDPE septic tank for 5 users designed to carry sewage and sullage water including excavation in any type of soil, PCC 1:4:8 below foundation, vent shaft, connection etc., with uplflow filter including media complete all as specified and as directed. |
| 33 | Material and labour for on site LLDPE septic tank for 10 users designed to carry sewage and sullage water including excavation in any type of soil, PCC 1:4:8 below foundation, vent shaft, connection etc., with uplflow filter including media complete all as specified and as directed. |
| 34 | Material and labour for construction of soakage well (1.2m dia x 3.0m effective depth) including excavation in any type of soil, foundation in PCC 1:3:6, walls of honey combed masonry with top ring of M25 concrete inclding intercepting chamber and screen chamber made of brick masonry in CM, RCC cover slab in M25/ SFRC cover, interconnecting pipes of RCC/ DWC complete filled with brick bats complete as per drawing No. CEAA/TD/80 Sht Nos. 1/2 and 2/2 all as specified and as directed. |
| 35 | Supply and fix precast Steel Fibre Reinforced Concrete (SFRC) Manhole cover 100mm thick complete all as specified and directed. |
| 36 | AREA DRAINAGE |
| 37 | Removing and refixing of precast RCC drain, M40 grade of internal size 450 x 450 mm, each piece of drain 2 metre long with and jointed and pointed with CM (1:3) as in open drain where required complete all as specified and directed. |
| 38 | Supply and fix precast RCC drain, M40 grade of internal size 450 x 450 mm, each piece of drain 2 metre long with precast RCC cover M40 grade and jointed and pointed with CM (1:3) as in covered drain, complete all as specified and directed.Note: 1. The quoted rate shall be inclusive of all reinforcement2. Box culvert shall be design and vetted by IIT/NIT. |
| 39 | EXTERNAL WATER SUPPLY |
| 40 | Supply, laying, jointing and testing of ductile iron (DI) pressure pipes, 200 mm nominal dia with spigot and socket ends, centrifugally cast, class K-9, with cement mortar lining in inner side as per IS:8329: 2000 (latest revision) and other relevant standards, with metallic zinc coating followed by a finishing layer of epoxy paint in outer side, suitable for push on joint (rubber gasket joint) including rubber gasket in any length with inside cement mortar lining laid in trenches/ over masonry pillar complete all as specified and directed. |
| 41 | Supply, laying, jointing and testing of ductile iron (DI) pressure pipes, 150 mm nominal dia with spigot and socket ends, centrifugally cast, class K-9, with cement mortar lining in inner side as per IS:8329: 2000 (latest revision) and other relevant standards, with metallic zinc coating followed by a finishing layer of epoxy paint in outer side, suitable for push on joint (rubber gasket joint) including rubber gasket in any length with inside cement mortar lining laid in trenches/ over masonry pillar complete all as specified and directed. |
| 42 | Supply, laying, jointing and testing of ductile iron (DI) pressure pipes, 100 mm nominal dia with spigot and socket ends, centrifugally cast, class K-9, with cement mortar lining in inner side as per IS:8329: 2000 (latest revision) and other relevant standards, with metallic zinc coating followed by a finishing layer of epoxy paint in outer side, suitable for push on joint (rubber gasket joint) including rubber gasket in any length with inside cement mortar lining laid in trenches/ over masonry pillar complete all as specified and directed. |
| 43 | Notes for item Nos. 32 to 34: (i) Excavation and earthwork shall be measured and paid separately under relevant items in schedule.(ii) The quoted rate shall also be deemed to include for provision of joints and jointing material for laying pipes. For jointing of pipe fittings or taking branch connection, provision of joints and jointing material shall be measured and paid separately.(iii) Before laying of pipe line, contractor has to submit layout diagram as per level difference and ensure proper alignment of the pipe. |
| 44 | Material and labour for ductile iron fittings for spigot socket pipe such as bends (any type, radius and angle) tapers any type (straight, bend, increasing, decreasing or double socket etc), tee pieces, single branch, \"Y\" junction, double branch, cross (all socket or socket and spigot), collars, restrained joint, mechanical joint, caps and plugs; 80 mm to 250 mm dia bore including cutting and jointing old/ new positions complete all as specified and directed. |
| 45 | Supply and fix cast iron air valves with single air outlets, conforming to IS- 14845 and fixing up in cast iron water supply mains, of size 200 mm dia, PN 1.6 complete all as specified and as directed. |
| 46 | Supply and fix cast iron air valves with single air outlets, conforming to IS- 14845 and fixing up in cast iron water supply mains, of size 150 mm dia , PN 1.6complete all as specified and as directed. |
| 47 | Supply and fix cast iron air valves with single air outlets, conforming to IS- 14845 and fixing up in cast iron water supply mains, of size 100 mm dia , PN 1.6complete all as specified and as directed. |
| 48 | Supply, installation and testing of cast iron foot valve of nominal size 80 mm dia, confirming IS 4038 complete all as specified and as directed |
| 49 | Supply, installation and testing of cast iron foot valve of nominal size 65 mm dia, confirming IS 4038 complete all as specified and as directed |
| 50 | Supply, installation and testing of cast iron foot valve of nominal size 50 mm dia, confirming IS 4038 complete all as specified and as directed |
| 51 | Supply, installation, testing and commissioning of electric motor driven submersible pump set suitable for lifting water from UG sump for 2500 LPM water flow and 12 metre head with AC, 3 phase, 50 Hz ,415 volts submersible motor of suitable capacity including non return valve 01 No. all as per IS: 8034:198 complete all as specified and directed (1W + 1S) (for GWSSB UG Sump to Main Pump House). |
| 52 | Supply, installation, testing and commissioning of centrifugal pump sets, multistage as per IS with electric motor of 20 HP, 1440-1500 RPM, 3 phase, 440 volts, 50 Hz heavy duty capacity and pumping water to a head 40 metre with discharge 1020 LPM with all necessary accessories and fittings including PVC insulated and PVC sheathed 3 core 25 sqmm copper cable from motor to starter including necessary suitable size foundation in PCC 1:2:4 type B-1 using 20mm gradeed stone aggregate; suction and delivery suitable bore pipe and mounting arrangement complete all as specified and directed (1W + 1S) (for Pump House No 1 to Single livingAccn Area) comprising of the following:(a) Priming funnel with valve(b) Pressure gauge at delivery side of pump set(c) Common base frame for pump set and prime mover |
| 53 | Supply, installation, testing and commissioning of centrifugal pump sets, multistage as per IS with electric motor of 20 HP, 1440-1500 RPM, 3 phase, 440 volts, 50 Hz heavy duty capacity and pumping water to a head 40 metre with discharge 990 LPM with all necessary accessories and fittings including PVC insulated and PVC sheathed 3 core 25 sqmm copper cable from motor to starter including necessary suitable size foundation in PCC 1:2:4 type B-1 using 20mm gradeed stone aggregate; suction and delivery suitable bore pipe and mounting arrangement complete all as specified and directed (1W + 1S) (for Pump House No 2 to BOCC Area) comprising of the following:(a) Priming funnel with valve(b) Pressure gauge at delivery side of pump set(c) Common base frame for pump set and prime mover |
| 54 | Supply, installation, testing and commissioning of monoblock, self-priming, single-stage, centrifugal volute type pump set having cast iron casing, enclosed type dynamically balanced phosphor-bronze/ SS impeller, high tensile steel shaft, carbon steel stuffing box (sealed by mechanical seal), deep groove ball bearings, base plate, mounting channel frame, elastomeric insulation, accessories and fittings, viz. mechanical seal, pressure gauges, thermometers, drains, coupling, coupling guard, vibration isolation arrangement by means of spring/ rubber type mounting and TEFC squirrel cage induction motor, suitable for operation on 3-Phase, 415 V ± 10%, 50 Hz AC supply and having IE- 3 efficiency and conforming to IS:12615: 2018 complete all as specified and directed for 657 LPM water flow and 25 Mtr head(1W + 1S) (for Main Pump House to Officers Accn Area and Pump House No 1).Note: Necessary civil work viz. foundation for placement of pump, mounting of pump accessories shall be covered in the scope of work. |
| 55 | All as per item No. 45, but for 650 LPM water flow and 30 Mtr head(1W + 1S) (for Main Pump House to Pump House No 2). |
| 56 | All as per item No. 45, but for 140 LPM water flow and 25 Mtr head(1W + 1S) (for Pump HouseNo 1 to Stn HQ Accn Area). |
| 57 | All as per item No. 45, but for 360 LPM water flow and 35 Mtr head (1W + 1S) (for Pump House No 2 to MT section Area). |
| 58 | Supply, installation, commissioning and testing pressure filter-cum iron removal plant suitable for 8000 GPH complete with PCC foundation of dimension and specification as per manufacurer\"s instructions, including provision of one man hole with manhole cover and lifting handle, provision of inlet, outlet and washout pipes made out of heavy duty MS pipe (inlet and outlet pipe will be connected to the main water pipes) provision of butterfly valves for inlet, outlet and wash out, back wash inter-connection etc. of appropriate size conforming to a IS-210 & 1570, air release valve, pressure relief valve, sampling cock, water level indicator, pressure guage on primary and secondary sides with stop cock,100 mm dia ERW pipe and MS pipe including two coats of black bituminous paint suitable for drinking purpose, non-toxic, non-dissolving in water on the inside walls and one coat of red-oxide primer with two coats of synthetic enamel paint on the external walls complete all as specified and directed including initial filling of filter media complete all as specified with following equipments/ accessories:- |
| 59 | (a) Iron removal plant:-2500 mm dia x 1500 mm height vertical, cylindrical and single deck type of shell thickness 10 mm, dish end thickness 12 mm and bed plate thickness 12 mmmade of mild steel conforming to IS 2062(b) Oxidation chamber:- 1000 mm dia x 1200 mm height with shell thickness 6 mm, bed plate thickness 8 mm and dish end thickness 8 mm made of mild steel conforming to IS 2062(c) Air compressor:- 12 cfm capacity fitted with 3 HP 440 V AC motor 1440 RPM(d) Aluminium Nitrate Dosing system:- Cast iron alum pot with brass fittings capacity 14 ltrs(e) Soda dosing system:-Cast iron soda pot with brass fittings capacity 14 ltrs(f) Chlorine Dosing pump:- 100 ltrs capacity FRP solution preparation cum dosing with motor agitator fitted(g) Inlet Parameter:- (i) Turbidity less than 100 NTU (ii) Iron content 8 to 10 PPM (h) Outlet Parameter:- (i) Turbidity less than 100 NTU (ii) Iron content 0.3 PPMNotes: (i) Cost of chlorine required for testing of water treatment plant is deemed to be included in the quoted rate(ii) The chemical/ bacteriological test of water to be recorded before and after filteration. |
| 60 | Supply, fabrication, installation and testing of Motor Control LT Panel, factory made, Type Test Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, outdoor type, weather proof, water proof, dust proof, vermin proof, shock proof protection, made out of 3.15 mm thick CRCA sheet of suitable size to accommodate accessories/ fittings with front and back double door opening/ lockable by the key from both side with IP 65 protection and provision of suitable bus bar chamber and switch gear compartments for MCCB incoming and outgoing feeders etc. with copper extension links of suitable current carrying capacity not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC/ Epoxy insulator including provision for termination with incoming and outgoing cables with cable glands. Motor Control LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminous paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1(using 20 mm graded stone aggregate) complete all as specified and directed and including the following accessories:-(Near GWSSB UG Sump) |
| 61 | Note:-(i)Rate of earthwork and PCC work etc are deemed to be inclusive in this item.(ii)Design of LT Panel including components, layout, their design as per IEC-61439 duly certified by ASTA or other approved agency.(iii)OEM design & GA drawingshall be submitted to GE for approval before start the manufacture(iv) Requisite tests required as per IEC-61439 guidelines to be conducted and report shall be submitted by OEM to Garrison Engineer. Further Factory inspection for routine inspection/ testing shall be carried out by Rep of accepting officer along with Rep of OEM before dispatch from factory. Testing charges shall be included in the quoted rates of item.(v) Make of Factory made TTA Panel shall be limited to : ABB/ SIEMENS/ SCHNEIDER/ L&T/ C&S/ LEGRAND INFRASTRUCTURE and also their approved Channel Partner/ Authorized Partner/ Licensee Partner, which are also Approved by MESand further the following:-(a) The name of proposed channel Partner with necessary certificate from OEM which the TTA Panels shall be first got approved from Accepting Officer.(b) The invoice of LT Panel/ components of LT Panel (Switch gears & protection material) shall be from original manufacturer only & not from the channel Partner |
| 62 | INCOMING:- (a) Copper strip busbar of 120 Amps rated capacity wrapped with PVC sleeves with maintaining the colour code and provision of making holes with copper nuts, bolts and washers for cable connections including hydrographic insulators with nuts and bolts at both ends - 04 Nos.(b) On load change over switch TPN of capacity 63 Amps - 01 No.(c) 4 Pole MCCB , 63 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links - 01 No.(d) LED Neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC - 01 set (set of three)(e) Digital multifunctional meter, flush mounting type with CTs and selector switch - 01 set. |
| 63 | OUTGOING:- (a) 3 Pole MCCB 32 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links - 02 Nos.(b) Fully automatic star-delta starter (soft starter type) with suitable relay range conforming to IS -1347 (Part IV) suitable for discharge capacity 2500 LPM (150 Cum/Hr) at 12 metre head, 10.0 HP, 99% energy efficient when running with soft start technology avoids harmonic distortion complete with R-G-O indication lamp including overload relay, auto timer and single phase preventer, suitable range of digital ammeter with selector switch, voltmeter with selector, indicating lamps (LED) and bakelite fuse showing RYB phase etc. mounted on ebonite sheet 10mm thick with flat strip frame of suitable size complete - 02 Nos. |
| 64 | Supply, fabrication, installation and testing of Motor Control LT Panel, factory made, Type Test Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, indoor type, weather proof, water proof, dust proof, vermin proof, shock proof protection, made out of 2 mm thick CRCA sheet of suitable size to accommodate accessories/ fittings with front and back double door opening/ lockable by the key from both side with IP 65 protection and provision of suitable bus bar chamber and switch gear compartments for MCCB incoming and outgoing feeders etc. with copper extension links of suitable current carrying capacity not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC/ Epoxy insulator including provision for termination with incoming and outgoing cables with cable glands. Motor Control LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminous paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1(using 20 mm graded stone aggregate) complete all as specified and directed and including the following accessories:-.(For main pump house) |
| 65 | Note:-(i)Rate of earthwork and PCC work etc are deemed to be inclusive in this item.(ii)Design of LT Panel including components, layout, their design as per IEC-61439 duly certified by ASTA or other approved agency.(iii)OEM design & GA drawingshall be submitted to GE for approval before start the manufacture(iv) Requisite tests required as per IEC-61439 guidelines to be conducted and report shall be submitted by OEM to Garrison Engineer. Further Factory inspection for routine inspection/ testing shall be carried out by Rep of accepting officer along with Rep of OEM before dispatch from factory. Testing charges shall be included in the quoted rates of item.(v) Make of Factory made TTA Panel shall be limited to : ABB/ SIEMENS/ SCHNEIDER/ L&T/ C&S/ LEGRAND INFRASTRUCTURE and also their approved Channel Partner/ Authorized Partner/ Licensee Partner, which are also Approved by MESand further the following:-(a) The name of proposed channel Partner with necessary certificate from OEM which the TTA Panels shall be first got approved from Accepting Officer.(b) The invoice of LT Panel/ components of LT Panel (Switch gears & protection material) shall be from original manufacturer only & not from the channel Partner |
| 66 | INCOMING:- (a) Copper strip busbar of 200 Amps rated capacity wrapped with PVC sleeves with maintaining the colour code and provision of making holes with copper nuts, bolts and washers for cable connections including hydrographic insulators with nuts and bolts at both ends - 04 Nos.(b) On load change over switch TPN of capacity 100 Amps - 01 No.(c) 4 Pole MCCB, 100 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links - 01 No.(d) LED Neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC - 01 set (set of three)(e) Digital multifunctional meter, flush mounting type with CTs and selector switch - 01 set. |
| 67 | OUTGOING:- (a) 4 Pole MCB 16 Amps 10 KA breaking capacity \"C\" curve - 01 No.(b) 3 Pole MCCB 32 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links - 04 Nos.(c) Fully automatic star-delta starter (soft starter type) with suitable relay range conforming to IS -1347 (Part IV) suitable for discharge capacity 657 LPM (39.45 Cum/Hr) at 25 metre head, 8.0 HP, 99% energy efficient when running with soft start technology avoids harmonic distortion complete with R-G-O indication lamp including overload relay, auto timer and single phase preventer, suitable range of digital ammeter with selector switch, voltmeter with selector, indicating lamps (LED) and bakelite fuse showing RYB phase etc. mounted on ebonite sheet 10mm thick with flat strip frame of suitable size complete - 02 Nos. (Officers Area and Pump House No. 1)(d) Fully automatic star-delta starter (soft starter type) with suitable relay range conforming to IS -1347 (Part IV) suitable for discharge capacity 650 LPM (39 Cum/Hr) at 30 metre head, 10.0 HP, 99% energy efficient when running with soft start technology avoids harmonic distortion complete with R-G-O indication lamp including overload relay, auto timer and single phase preventer, suitable range of digital ammeter with selector switch, voltmeter with selector, indicating lamps (LED) and bakelite fuse showing RYB phase etc. mounted on ebonite sheet 10mm thick with flat strip frame of suitable size complete - 02 Nos. (for Pump House No. 2) |
| 68 | Supply, fabrication, installation and testing of Motor Control LT Panel, factory made, Type Test Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, indoor type, weather proof, water proof, dust proof, vermin proof, shock proof protection, made out of 2.0 mm thick CRCA sheet of suitable size to accommodate accessories/ fittings with front and back double door opening/ lockable by the key from both side with IP 65 protection and provision of suitable bus bar chamber and switch gear compartments for MCCB incoming and outgoing feeders etc. with copper extension links of suitable current carrying capacity not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC/ Epoxy insulator including provision for termination with incoming and outgoing cables with cable glands. Motor Control LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminous paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1 (using 20 mm graded stone aggregate) complete all as specified and directed and including the following accessories:- (for Pump House No. 1). |
| 69 | Note:-(i)Rate of earthwork and PCC work etc are deemed to be inclusive in this item.(ii)Design of LT Panel including components, layout, their design as per IEC-61439 duly certified by ASTA or other approved agency.(iii)OEM design & GA drawingshall be submitted to GE for approval before start the manufacture(iv) Requisite tests required as per IEC-61439 guidelines to be conducted and report shall be submitted by OEM to Garrison Engineer. Further Factory inspection for routine inspection/ testing shall be carried out by Rep of accepting officer along with Rep of OEM before dispatch from factory. Testing charges shall be included in the quoted rates of item.(v) Make of Factory made TTA Panel shall be limited to : ABB/ SIEMENS/ SCHNEIDER/ L&T/ C&S/ LEGRAND INFRASTRUCTURE and also their approved Channel Partner/ Authorized Partner/ Licensee Partner, which are also Approved by MESand further the following:-(a) The name of proposed channel Partner with necessary certificate from OEM which the TTA Panels shall be first got approved from Accepting Officer.(b) The invoice of LT Panel/ components of LT Panel (Switch gears & protection material) shall be from original manufacturer only & not from the channel Partner |
| 70 | INCOMING:- (a) Copper strip busbar of 200 Amps rated capacity wrapped with PVC sleeves with maintaining the colour code and provision of making holes with copper nuts, bolts and washers for cable connections including hydrographic insulators with nuts and bolts at both ends - 04 Nos.(b) On load change over switch TPN of capacity 100 Amps - 01 No.(c) 4 Pole MCCB ,100 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links - 01 No.(d) LED Neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC - 01 set (set of three)(e) Digital multifunctional meter, flush mounting type with CTs and selector switch - 01 set. |
| 71 | OUTGOING:- (a) 4 Pole MCB 16 Amps 10 KA breaking capacity \"C\" curve - 01 No.(b) 3 Pole MCCB 40 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links - 02 Nos.(c) 3 Pole MCB 10 Amps, 415 Volts, 10 KA breaking capacity including all fixing accessories with both ends spreader links - 02 Nos.(d) Fully automatic star-delta starter (soft starter type) with suitable relay range conforming to IS -1347(Part IV) suitable for discharge capacity 1016 LPM (61 Cum/Hr) at 40 metre head, 20.0 HP, 99% energy efficient when running with soft start technology avoids harmonic distortion complete with R-G-O indication lamp including overload relay, auto timer and single phase preventer, suitable range of digital ammeter with selector switch, voltmeter with selector, indicating lamps (LED) and bakelite fuse showing RYB phase etc. mounted on ebonite sheet 10mm thick with flat strip frame of suitable size complete - 01 No. (for single living accn area)(e) DOL starter (soft starter type) with suitable relay range conforming to IS -1347 (Part IV) suitable for discharge capacity 140 LPM (8.40 Cum/Hr) at 25 metre head, 2.0 HP, 99% energy efficient when running with soft start technology avoids harmonic distortion complete with R-G-O indication lamp including overload relay and single phase preventer, suitable range of digital ammeter with selector switch, voltmeter with selector, indicating lamps (LED) and bakelite fuse showing RYB phase etc. mounted on ebonite sheet 10mm thick with flat strip frame of suitable size complete - 01 No. (for Station HQ area) |
| 72 | Supply, fabrication, installation and testing of Motor Control LT Panel, factory made, Type Test Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, indoor type, weather proof, water proof, dust proof, vermin proof, shock proof protection, made out of 2.0 mm thick CRCA sheet of suitable size to accommodate accessories/ fittings with front and back double door opening/ lockable by the key from both side with IP 65 protection and provision of suitable bus bar chamber and switch gear compartments for MCCB incoming and outgoing feeders etc. with copper extension links of suitable current carrying capacity not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC/ Epoxy insulator including provision for termination with incoming and outgoing cables with cable glands. Motor Control LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminous paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1 (using 20 mm graded stone aggregate) complete all as specified and directed and including the following accessories:- (for Pump House No. 2). |
| 73 | Note:-(i)Rate of earthwork and PCC work etc are deemed to be inclusive in this item.(ii)Design of LT Panel including components, layout, their design as per IEC-61439 duly certified by ASTA or other approved agency.(iii)OEM design & GA drawingshall be submitted to GE for approval before start the manufacture(iv) Requisite tests required as per IEC-61439 guidelines to be conducted and report shall be submitted by OEM to Garrison Engineer. Further Factory inspection for routine inspection/ testing shall be carried out by Rep of accepting officer along with Rep of OEM before dispatch from factory. Testing charges shall be included in the quoted rates of item.(v) Make of Factory made TTA Panel shall be limited to : ABB/ SIEMENS/ SCHNEIDER/ L&T/ C&S/ LEGRAND INFRASTRUCTURE and also their approved Channel Partner/ Authorized Partner/ Licensee Partner, which are also Approved by MESand further the following:-(a) The name of proposed channel Partner with necessary certificate from OEM which the TTA Panels shall be first got approved from Accepting Officer.(b) The invoice of LT Panel/ components of LT Panel (Switch gears & protection material) shall be from original manufacturer only & not from the channel Partner |
| 74 | INCOMING:- (a) Copper strip busbar of 200 Amps rated capacity wrapped with PVC sleeves with maintaining the colour code and provision of making holes with copper nuts, bolts and washers for cable connections including hydrographic insulators with nuts and bolts at both ends - 04 Nos.(b) On load change over switch TPN of capacity 100 Amps - 01 No.(c) 4 Pole MCCB ,100 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links - 01 No.(d) LED Neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC - 01 set (set of three)(e) Digital multifunctional meter, flush mounting type with CTs and selector switch - 01 set. |
| 75 | OUTGOING:- (a) 4 Pole MCB 16 Amps 10 KA breaking capacity \"C\" curve - 01 No.(b) 3 Pole MCCB 40 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links - 02 Nos.(c) 3 Pole MCB 20 Amps, 415 Volts, 10 KA breaking capacity including all fixing accessories with both ends spreader links - 02 Nos.(d) Fully automatic star-delta starter (soft starter type) with suitable relay range conforming to IS -1347(Part IV) suitable for discharge capacity 990 LPM (59.40 Cum/Hr) at 40 metre head, 20.0 HP, 99% energy efficient when running with soft start technology avoids harmonic distortion complete with R-G-O indication lamp including overload relay, auto timer and single phase preventer, suitable range of digital ammeter with selector switch, voltmeter with selector, indicating lamps (LED) and bakelite fuse showing RYB phase etc. mounted on ebonite sheet 10mm thick with flat strip frame of suitable size complete - 01 No. (for BOCC area)(e) Fully automatic star-delta starter (soft starter type) with suitable relay range conforming to IS -1347 (Part IV) suitable for discharge capacity 360 LPM (21.6 Cum/Hr) at 35 metre head, 7.5 HP, 99% energy efficient when running with soft start technology avoids harmonic distortion complete with R-G-O indication lamp including overload relay and single phase preventer, suitable range of digital ammeter with selector switch, voltmeter with selector, indicating lamps (LED) and bakelite fuse showing RYB phase etc. mounted on ebonite sheet 10mm thick with flat strip frame of suitable size complete - 01 No. (for MT section area) |
| 76 | Supply, fabrication, installation and testing of Motor Control LT Panel, factory made, Type Test Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, indoor type, weather proof, water proof, dust proof, vermin proof, shock proof protection, made out of 2.0 mm thick CRCA sheet of suitable size to accommodate accessories/ fittings with front and back double door opening/ lockable by the key from both side with IP 65 protection and provision of suitable bus bar chamber and switch gear compartments for MCCB incoming and outgoing feeders etc. with copper extension links of suitable current carrying capacity not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC/ Epoxy insulator including provision for termination with incoming and outgoing cables with cable glands. Motor Control LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminous paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1 (using 20 mm graded stone aggregate) complete all as specified and directed and including the following accessories:- (for Borewell No. 1 and No. 2). |
| 77 | Note:-(i)Rate of earthwork and PCC work etc are deemed to be inclusive in this item.(ii)Design of LT Panel including components, layout, their design as per IEC-61439 duly certified by ASTA or other approved agency.(iii)OEM design & GA drawingshall be submitted to GE for approval before start the manufacture(iv) Requisite tests required as per IEC-61439 guidelines to be conducted and report shall be submitted by OEM to Garrison Engineer. Further Factory inspection for routine inspection/ testing shall be carried out by Rep of accepting officer along with Rep of OEM before dispatch from factory. Testing charges shall be included in the quoted rates of item.(v) Make of Factory made TTA Panel shall be limited to : ABB/ SIEMENS/ SCHNEIDER/ L&T/ C&S/ LEGRAND INFRASTRUCTURE and also their approved Channel Partner/ Authorized Partner/ Licensee Partner, which are also Approved by MESand further the following:-(a) The name of proposed channel Partner with necessary certificate from OEM which the TTA Panels shall be first got approved from Accepting Officer.(b) The invoice of LT Panel/ components of LT Panel (Switch gears & protection material) shall be from original manufacturer only & not from the channel Partner |
| 78 | INCOMING:- (a) Copper strip busbar of 250 Amps rated capacity wrapped with PVC sleeves with maintaining the colour code and provision of making holes with copper nuts, bolts and washers for cable connections including hydrographic insulators with nuts and bolts at both ends - 04 Nos.(b) On load change over switch TPN of capacity 125 Amps - 01 No.(c) 4 Pole MCCB ,125 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links - 01 No.(d) LED Neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC - 01 set (set of three)(e) Digital multifunctional meter, flush mounting type with CTs and selector switch - 01 set. |
| 79 | OUTGOING:- (a) 4 Pole MCB 16 Amps 10 KA breaking capacity \"C\" curve - 01 No.(b) 3 Pole MCCB 100 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links - 02 Nos.(c) Fully automatic star-delta starter (soft starter type) with suitable relay range conforming to IS -1347(Part IV) suitable for discharge capacity 570 LPM (34.20 Cum/Hr) at 325 metre head, 55.0 HP, 99% energy efficient when running with soft start technology avoids harmonic distortion complete with R-G-O indication lamp including overload relay, auto timer and single phase preventer, suitable range of digital ammeter with selector switch, voltmeter with selector, indicating lamps (LED) and bakelite fuse showing RYB phase etc. mounted on ebonite sheet 10mm thick with flat strip frame of suitable size complete - 01 No. (for borewell) |
| 80 | Supply and installation of heavy duty chemical dosing system, plunger type, suitable to inject solution upto 25 LPH working pressure, 10 Kg/cm2, comprising of dosing pump coupled with 3 phase electric motor of capacity 0.50 HP, 1440 rpm assembly with agitator in one motor, agitator with stainless steel sweep blade duly FRP coated, FRP tank 150 Ltrs capacity, complete unit mounted on heavy duty MS fabricated frame duly anti-corrosive paint complete with chemical grade PVC NRV along with control panel for dosing pump suitable, made of powder coated MS fabricated box consisting of LED indicator, digital Voltmeter, single phase preventor, high voltage/ low voltage protection complete all as specified and directed. |
| 81 | Material and labour for drilling of 02 Nos. of trial bore hole 250 mm dia, from ground level upto depth of 200 metre from ground level, by Direct Rotary Rig Method/ Hydraulic rotary drilling of works in all kinds of soils strata, hard stone, boulders etc. and submitting the strata detail as in both graphical record and samples including the cost of all consumable stores, fuel oil, soil stabilising, material arrangement and transportation of rig and other accessories to site of proposed bore and back including disposal of spoil from the site complete all as specified and directed.Notes:- (i) The quoted rate shall be deemed to be inclusive of the cost of drilling rig, pipe, pumps, fittings etc. which shall be provided by the contractor under his own arrangement for execution of the work.(ii) Contractor should submit Strata Litholog laminated chart with sample collected in a sample boxsystematically made out of 20 mm thick veneered particle board brown in colour and aluminium frame overall length with front glass openable door with lock and the quoted rate shall be deemd to be inclusive of this provision. |
| 82 | Material and labour for drilling of 02 Nos. of trial bore hole 250 mm dia, for depth exceeding 200 metre and upto 400 metre from ground level, by Direct Rotary Rig Method/ Hydraulic rotary drilling of works in all kinds of soils strata, hard stone, boulders etc. and submitting the strata detail as in both graphical record and samples including the cost of all consumable stores, fuel oil, soil stabilising, material arrangement and transportation of rig and other accessories to site of proposed bore and back including disposal of spoil from the site complete all as specified and directed.Notes:- (i) The quoted rate shall be deemed to be inclusive of the cost of drilling rig, pipe, pumps, fittings etc. which shall be provided by the contractor under his own arrangement for execution of the work.(ii) Contractor should submit Strata Litholog laminated chart with sample collected in a sample boxsystematically made out of 20 mm thick veneered particle board brown in colour and aluminium frame overall length with front glass openable door with lock and the quoted rate shall be deemd to be inclusive of this provision. |
| 83 | Material and labour for development/ enlargement of trial bore by reaming from bore well in step from (a) 200mm to 350mm, (b) from 350mm to 450mm, (c) from 450mm to 550mm, suitable for lowering ERW Mild steel 250mm dia, 8 mm thick casing pipes, gravel and clay packing for the required length below the ground level complete all as specified and directed. |
| 84 | Supply, assembling, lowering into bore hole and fixing in position 250 mm nominal (10\") bore ERW MS pipe, ISI marked as per IS 3589, of 8 mm wall thickness in random length upto 6 mtr with screwed and socketed, including necessary fittings and welding including painting both inside and outside with black bituminous paint suitable for drinking water purpose complete all as specified and directed. |
| 85 | Supply, assembling, lowering into bore hole and fixing in position 250 mm nominal (10\") bore ERW MS slotted pipe, ISI marked as per IS 3589 or as per IS 4270, of 8 mm wall thickness with screwed and socketed, including necessary fittings and welding including painting both inside and outside with black bituminous paint suitable for drinking water purpose complete all as specified and directed.Notes: (i) As per site, required suitable length of slotted pipe 250mm dia strainer cage type wire wound rate should be included in the quoted rate of this item.(ii) Slots in 250 mm dia pipes of width 1.63 mm with sides perpendicular to the surface of the pipe and length varying from 62 mm to 80 mm, the open area of slots shall not be less than 12% to 15% of the total surface area of the strainer pipe. Slots shall be milled and not punched preferably tapered with smaller opening on the outside of pipe, slotting with oxy-acetylene flame will not be allowed. |
| 86 | Supply and fix suitable size MS bail plug, well cap, MS strip for centering of pipe etc. fitted to casing pipe, threaded and continuous welded by electric arc welding at both ends complete all as specified and directed. |
| 87 | Supply, filling and packing washed pea gravels of size 3 mm to 5 mm all around casing pipe and slotted pipe complete all as specified anddirected. Note: Pea gravel shall be meausured and paid as per stack measurement carried out on site. |
| 88 | Supply and fix well cap suitable for 250 mm dia internal dia housing pipe, made out of 6 mm thick steel plate complete all as specified and directed.Note: After completion of the work, the cap shall be used to keep the tube well closed untill the pump set is installed. |
| 89 | Material and labour for sanitary sealing of tube well by PCC (1:2:4) type B-1 (using 20mm gradedstone aggregate), of size 1000 mm x 1000 mm x 500 mm with 2 Nos. of 50 mm bore GI tubing, medium grade of required length (not less than 1.5 metre) for gravel packing, complete all as specified and as directed. |
| 90 | Material and labour for development of tube well with air compressor of capacity 250 psi, 11000 cum till sand/ mud free water of potable quality is obtained and to achieve minimum discharging capacity of 25000 LPH complete all as specified and as directed.Note: Compressor with accessories and fuel shall be arranged by the contractor and same shall be deemed to be included in the quoted rate. |
| 91 | Material and labour for yield testing for the tube well by suitable capacity submersible pump and motor for minimum discharging capacity of 10000 gallons per hour for at least continuous 16 hours uninterrupted runcomplete all as specified and directed.Note: (i) \"V\" Notch and other equipment including pump set shall be arranged by the contractor at his own cost.(ii) Electricity shall be supplied by the department for yield testing as free of cost. |
| 92 | Material and labour for electrologing test using suitable equipments for upto complete drilling depth of tube well before sinking/ lowering of pipes, filters etc. for arresting proper delineation of water from Govt. recognised agency/ Govt. firm qualified Hydrologist and report shall be submitted to GE/ Engineer-in-Charge for approval complete all as specified and as directed. |
| 93 | Material and labour for 80mm bore column pipe made out of galvanised iron heavy grade (6 metre long of each pipe length)with welded heavy duty flanges at both ends including a coat of anti-corrosive paint complete all as specified and directed.Note: Column pipes have been designed to withstand system load comprising the weight of the pump, water and pipes with an adequate factor of safety . |
| 94 | Supply and fix PVC insulated, PVC sheathed, submersible flat cable, ISI marked as per IS: 694/1990 with multi stranded copper conductor, 1100 volt grade of size 3 core x 25 sqmm including water proof joint to motor terminal complete all as specified and as directed. |
| 95 | Supply, fixing and testing of stainless steel shaft, impeller and motor body submersible pumping set with copper rotor electric driven star delta connection 415 Volts, 50 Hz for water discharge of 570 LPM at 325 metre head, submersible motor of suitable capacity including heavy duty male/ female threaded GI coupler and non-return valve all as per IS : 8034:1989 complete all as specified and directed. |
| 96 | Supply and fix wire rope of stainless steel, 5mm dia flexible for borewell hoisting including rop clip complete all as specified and directed. |
| 97 | Material and labour for borewell chart on acrylic sheet of size 60cm x 15cm duly marked with permanent marking including 12mm thick plywood frame, clamps for fixing on wall etc. complete all as specified and directed. |
| 98 | Material and labour for construction of brick masonry valve pit of size 900 mm x 900 mm x 900 mm internal dimension, one brick thick wall in cement mortar 1:4 on 100 mm thick PCC 1:4:8 (using 40mm graded stone aggregate) in foundation, rendering 15mm thick (1:4) internally and externally upto 150mm below GL, providing 3.0mm thick MS sheet valve pit cover, welded with 40X5mm flat iron frame alround including provision of hinges, handle and locking arrangement and 40 x 40 x 6mm angle iron frame fixed on top of valve pit by means of holdfast 150mm long, embedded in PCC 1:2:4 (using 20mm graded stone aggregate) block of size 230 x 200 x 100 mm, applying two coats of anti-corrosive paint over a coat of red oxide zinc chrome primer after preparation of all exposed steel surfaces including necessary earthwork in soft/ loose soil complete all as specified and as directed. |
| 99 | EXTERNAL ELECTRIFICATION |
| 100 | Supply, laying and testing of Double Wall Corrugated (DWC) high density Polyethylene (HDPE) pipes of63mm outer dia/ 50mm internal dia and stiffness class-8 (SN-8) with ISI marked (with CML no) with and including all fittings and jointing material for sewage line laid in trenches as specified in IS 16098-2013 part-2 complete all as specified and directed.Note:- Construction method shall be strictly comiled as per clause no A-4 of Annex IA of ISA 16098 Part II. |
| 101 | Supply, laying and testing of Double Wall Corrugated (DWC) high density Polyethylene (HDPE) pipes of90mm outer dia/ 76mm internal dia and stiffness class-8 (SN-8) with ISI marked (with CML no) with and including all fittings and jointing material for sewage line laid in trenches as specified in IS 16098-2013 part-2 complete all as specified and directed.Note:- Construction method shall be strictly comiled as per clause no A-4 of Annex IA of ISA 16098 Part II. |
| 102 | Supply, laying and testing of Double Wall Corrugated (DWC) high density Polyethylene (HDPE) pipes of120mm outer dia/ 103.5mm internal dia and stiffness class-8 (SN-8) with ISI marked (with CML no) with and including all fittings and jointing material for sewage line laid in trenches as specified in IS 16098-2013 part-2 complete all as specified and directed.Note:- Construction method shall be strictly comiled as per clause no A-4 of Annex IA of ISA 16098 Part II. |
| 103 | Supply, laying and testing of Double Wall Corrugated (DWC) high density Polyethylene (HDPE) pipes of160mm outer dia/ 136mm internal dia and stiffness class-8 (SN-8) with ISI marked (with CML no) with and including all fittings and jointing material for sewage line laid in trenches as specified in IS 16098-2013 part-2 complete all as specified and directed.Note:- Construction method shall be strictly comiled as per clause no A-4 of Annex IA of ISA 16098 Part II. |
| 104 | Supply and fix cable route indicator/ marker made up of PCC block in cement concrete 1:3:6 (using 20 mm graded stone aggregrate) of size 900 x 300 x 100 mm thick with \"DANGER/ 11 KV CABLE/ MES\" embossing on cable route indicator/ marker including painting as per approved colour and buried 45 cm in ground including necessary earthwork (as required/ ordered at site) complete all as specified and as directed. |
| 105 | Supply and fix cable route indicator/ marker made up of PCC block in cement concrete 1:3:6 (using 20 mm graded stone aggregrate) of size 900 x 300 x 100 mm thick with \"DANGER/ LT 433 VOLTS CABLE/ MES or DANGER/ MES\" embossing on cable route indicator/ marker including painting as per approved colour and buried 45 cm in ground including necessary earthwork (as required/ ordered at site) complete all as specified and as directed. |
| 106 | Material and labour for boring of holes under road, pavement, hard standing by trenchless technology using ultrasound technique and necessary machine including provision of HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure for cable protection and making good as existing complete all as specified and as directed. |
| 107 | Supply, installation, testing and commissioning of indoor type (IP 3X), Primary SF6 Gas Insulated Switchgear 11 KV, 1250 Amps, 26.30 kA for 3 Sec, GIS SF6 insulated, both side extensible, consisting of Two Nos (02) motorised vacuum circuit breaker (Incomer) and Seven Nos (07) motorised vacuum circuit breaker (Outgoing), inside robotically welded stainless steel 304 (Non Ferrite Non Magnetic Grade) tank having min thickness 2.5 +/- 0.5mm with IP 67 degree of protection and enhanced BIL of 75 kVp internally to manage voltage surges and Air Insulated Metering Module of Class-0.5. GIS should be provided with internal air insulated busbars with touch proof insulating sleeve, as well as earthing busbars of electrolytic grade copper, padlock provisions complete with all accessories. The complete GIS must be type tested for internal arc 25 KA for 1 sec with AFLR classification for gas tank and cable chamber as per IEC 62271-200. HT GIS shall preferably have on-site-repairability features such as site replaceable bushing/ coupling/ mechanism and gas refilling to have very less downtime in the event of bushing breakage and restoration can be done at site immediately without sending the GIS to OEM Works, the Vaccum Interrupter must be RMU manufacturer\"s own make. The earthing busbar shall be provided inside each cable compartment for solid earthing of cable shields. The unit shall include the following with all necessary standard fittings complete all as specified and as required at site:- (for Main Receiving Station) |
| 108 | Notes:- (i) Erection, testing and commissioning of 11kV GIS SF6 Panels (RMU) including necessary termination kit preparation of required quantity as per site by OEM to be included in quoted rate.(ii) Make of RMU shall be limited to : ABB/ SIEMENS/ SCHNEIDER INFRASTRUCTURE(Channel partner/ System Integrator/ Authourized Partner/ License partner make RMU shall not be accepted.)(a) Vacuum Circuit Breaker shall consist of the following accessories:-(i) Microprocessor based Numerical Protection Relay for Circuit Breakers - REX615, Feeder Protection and Control Relay, Protections 50, 51, 50N, 51N, 46, 49, 67, 67N, 32, 27, 59, 25, 81U, 81O, 95, Measurement for 3I, I0, 3U, U0, Kw, KVA, PF, Hz, Kwh, 16 DI + 10 DO, One front RJ45 Port, One Rear RJ45 Port for IEC-61850 Protocol, Drawout Type with CT Shorting feature, Graphical LCD Display.(ii) Capacitive voltage indication fixed type system with LED for all feeder (iii) GIS SF6 Gas pressure indicator (Scada Compatible) on the gas tank(iv) Operating sequence of VCB must be O-0.3Sec-CO-3 Mins-CO amd suitable for 10,000 mechanical operation(v) CT shall be minimum 300-600/1-1A, 2.5VA, Class 0.5 & 5P10 - 3 Nos. for protection and metering for both incomer and 100-200/1-1A, 2.5VA, Class 0.5 and 5P10 - 3 Nos for protection and metering for all outgoing feeders |
| 109 | (vi) Touch Proof Termination Kit(vii) Line PT shall be plug-in type and shall have Isolator(viii) Multifunction meter shall have Modbus RS485 port for communication(ix) 12 port (10 RJ45 & 2 FO) Ethernet switch with LIU to be provided for scada communication with DCS(x) Capacitive voltage indication fixed type system as per IE(xi) Interlocked cable box for front termination of the cable suitable upto 3 core 300 Sqmm, 11 KV XLPE cable (IP3X) safety interlocked to prevent access to cable termination in live-condition(xii) GIS shall be compatible and type tested with both SF6 Gas and Green Gas(xiii) Cable covers with self interlocking mechanism between doors, earth switch, disconnector and VCB(xiv) Necessay interclocking arrangement for safety and operations(xv) One no. operating handle for manual operation and one no. manometer(xvi) Safety interlocks shall be provided as per relevant IEC/ IS standards and manufacturer\"s directions(xvii) Above switchgear shall confirm to all relevant IEC/ IS standards |
| 110 | Supply, installation, testing and commissioning of indoor type (IP 3X), 05 way RMU (Ring Main Unit), 11 KV, 630 Amps, 25kA-3 Sec, IP 3X SF6 insulated, one side extensible, consisting of One No (01) motorised vacuum circuit breaker (Incomer) and Four Nos (04) motorised vacuum circuit breaker (Outgoing) and Metering Panel Bus PT with Top LV, Battery and Battery charger, Ethernet switch and LIU (Configuration VVVVV+M), inside robotically welded stainless steel 304 (Non Ferrite Non Magnetic Grade) tank having min thickness 2.5 +/- 0.5mm with IP 67 degree of protection and enhanced BIL of 75 kVp internally to manage voltage surges and Air Insulated Metering Module of Class-0.5. RMU should be provided with internal busbars, as well as earthing busbars of electrolytic grade copper, padlock provisions complete with all accessories. The complete RMU must be type tested for internal arc 25 KA for 1 sec with AFLR classification for gas tank and cable chamber as per IEC 62271-200. HT RMU shall preferably have on-site-repairability features such as site replaceable bushing/ coupling/ mechanism and gas refilling to have very less downtime in the event of bushing breakage and restoration can be done at site immediately without sending the RMU to OEM Works, the Vaccum Interrupter must be RMU manufacturer\"s own make. The earthing busbar shall be provided inside each cable compartment for solid earthing of cable shields. The outer hinged main door should cover entire front of switchgear including cable doors for providing fail-safe protection. The unit shall include the following with all necessary standard fittings complete all as specified and as required at site:- (for Sub Station No.1) |
| 111 | Supply, installation, testing and commissioning of indoor type (IP 3X), 04 way RMU (Ring Main Unit) 11 KV, 630 Amps, 25kA-3 Sec, IP 3X SF6 insulated, One side Extensible, consisting of Two Nos (02) motorised vacuum circuit breaker (Incomer) and Two Nos (02) motorised vacuum circuit breaker (Outgoing) & Metering Panel Bus PT with Top LV, Battery & Battery charger, Ethernet switch & LIU (Configuration VVVV+M), inside robotically welded stainless steel 304 (Non Ferrite Non Magnetic Grade) tank having min thickness 2.5 +/- 0.5mm with IP 67 degree of protection and enhanced BIL of 75 kVp internally to manage voltage surges and Air Insulated Metering Module of Class-1. RMU should be provided with internal busbars, as well as earthing busbars of electrolytic grade copper, padlock provisions complete with all accessories. The complete RMU must be type tested for internal arc 25 KA for 1 sec with AFLR classification for gas tank and cable chamber as per IEC 62271-200. HT RMU shall preferably have on-site-repairability features such as site replaceable bushing/ coupling/ mechanism and gas refilling to have very less downtime in the event of bushing breakage and restoration can be done at site immediately without sending the RMU to OEM Works, the Vaccum Interrupter must be RMU manufacturer\"s own make. The earthing busbar shall be provided inside each cable compartment for solid earthing of cable shields. The outer hinged main door should cover entire front of switchgear including cable doors for providing fail-safe protection. The unit shall include the following with all necessary standard fittings complete all as specified and as required at site:- (for Sub Station No.2 & 3) |
| 112 | Supply, installation, testing and commissioning of indoor type (IP 3X), 04 way RMU (Ring Main Unit) 11 KV, 630 Amps, 25kA-3 Sec, IP 3X SF6 insulated, One side Extensible, consisting of One No (01) motorised vacuum circuit breaker (Incomer) and Three Nos (03) motorised vacuum circuit breaker (Outgoing) & Metering Panel Bus PT with Top LV, Battery & Battery charger, Ethernet switch & LIU (Configuration VVVV+M), inside robotically welded stainless steel 304 (Non Ferrite Non Magnetic Grade) tank having min thickness 2.5 +/- 0.5mm with IP 67 degree of protection and enhanced BIL of 75 kVp internally to manage voltage surges and Air Insulated Metering Module of Class-1. RMU should be provided with internal busbars, as well as earthing busbars of electrolytic grade copper, padlock provisions complete with all accessories. The complete RMU must be type tested for internal arc 25 KA for 1 sec with AFLR classification for gas tank and cable chamber as per IEC 62271-200. HT RMU shall preferably have on-site-repairability features such as site replaceable bushing/ coupling/ mechanism and gas refilling to have very less downtime in the event of bushing breakage and restoration can be done at site immediately without sending the RMU to OEM Works, the Vaccum Interrupter must be RMU manufacturer\"s own make. The earthing busbar shall be provided inside each cable compartment for solid earthing of cable shields. The outer hinged main door should cover entire front of switchgear including cable doors for providing fail-safe protection. The unit shall include the following with all necessary standard fittings complete all as specified and as required at site:- (for Sub Station No.4 & 7) |
| 113 | Supply, installation, testing and commissioning of indoor type (IP 3X), 03 way RMU (Ring Main Unit) 11 KV, 630 Amps, 25kA-3 Sec, IP 3X SF6 insulated, One side Extensible, consisting of Two Nos. (02) motorised vacuum circuit breaker (Incomer) and One No (01) motorised vacuum circuit breaker (Outgoing) & Metering Panel Bus PT with Top LV, Battery & Battery charger, Ethernet switch & LIU (Configuration VVVV+M), inside robotically welded stainless steel 304 (Non Ferrite Non Magnetic Grade) tank having min thickness 2.5 +/- 0.5mm with IP 67 degree of protection and enhanced BIL of 75 kVp internally to manage voltage surges and Air Insulated Metering Module of Class-1. RMU should be provided with internal busbars, as well as earthing busbars of electrolytic grade copper, padlock provisions complete with all accessories. The complete RMU must be type tested for internal arc 25 KA for 1 sec with AFLR classification for gas tank and cable chamber as per IEC 62271-200. HT RMU shall preferably have on-site-repairability features such as site replaceable bushing/ coupling/ mechanism and gas refilling to have very less downtime in the event of bushing breakage and restoration can be done at site immediately without sending the RMU to OEM Works, the Vaccum Interrupter must be RMU manufacturer\"s own make. The earthing busbar shall be provided inside each cable compartment for solid earthing of cable shields. The outer hinged main door should cover entire front of switchgear including cable doors for providing fail-safe protection. The unit shall include the following with all necessary standard fittings complete all as specified and as required at site:- (for Sub Station No.5, 6 & 10) |
| 114 | Supply, installation, testing and commissioning of indoor type (IP 3X), 05 way RMU (Ring Main Unit) 11 KV, 630 Amps, 25kA-3 Sec, IP 3X SF6 insulated, One side Extensible, consisting of Two Nos (02) motorised vacuum circuit breaker (Incomer) and Three Nos (03) motorised vacuum circuit breaker (Outgoing) & Metering Panel Bus PT with Top LV, Battery & Battery charger, Ethernet switch & LIC (Configuration VVVVV+M) inside robotically welded stainless steel 304 (Non Ferrite Non Magnetic Grade) tank having min thickness 2.5 +/- 0.5mm with IP 67 degree of protection and enhanced BIL of 75 kVp internally to manage voltage surges and Air Insulated Metering Module of Class-1. RMU should be provided with internal busbars, as well as earthing busbars of electrolytic grade copper, padlock provisions complete with all accessories. The complete RMU must be type tested for internal arc 25 KA for 1 sec with AFLR classification for gas tank and cable chamber as per IEC 62271-200. HT RMU shall preferably have on-site-repairability features such as site replaceable bushing/ coupling/ mechanism and gas refilling to have very less downtime in the event of bushing breakage and restoration can be done at site immediately without sending the RMU to OEM Works, the Vaccum Interrupter must be RMU manufacturer\"s own make. The earthing busbar shall be provided inside each cable compartment for solid earthing of cable shields. The outer hinged main door should cover entire front of switchgear including cable doors for providing fail-safe protection. The unit shall include the following with all necessary standard fittings complete all as specified and as required at site:- (for Sub Station No- 8) |
| 115 | Supply, installation, testing and commissioning of indoor type (IP 3X), 03 way RMU (Ring Main Unit) 11 KV, 630 Amps, 25kA-3 Sec, IP 3X SF6 insulated, One side Extensible, consisting of One No (01) motorised vacuum circuit breaker (Incomer) and Two Nos (02) motorised vacuum circuit breaker (Outgoing) & Metering Panel Bus PT with Top LV, Battery & Battery charger, Ethernet switch & LIU (Configuration VVV+M) inside robotically welded stainless steel 304 (Non Ferrite Non Magnetic Grade) tank having min thickness 2.5 +/- 0.5mm with IP 67 degree of protection and enhanced BIL of 75 kVp internally to manage voltage surges and Air Insulated Metering Module of Class-0.5. RMU should be provided with internal busbars, as well as earthing busbars of electrolytic grade copper, padlock provisions complete with all accessories. The complete RMU must be type tested for internal arc 25 KA for 1 sec with AFLR classification for gas tank and cable chamber as per IEC 62271-200. HT RMU shall preferably have on-site-repairability features such as site replaceable bushing/ coupling/ mechanism and gas refilling to have very less downtime in the event of bushing breakage and restoration can be done at site immediately without sending the RMU to OEM Works, the Vaccum Interrupter must be RMU manufacturer\"s own make. The earthing busbar shall be provided inside each cable compartment for solid earthing of cable shields. The outer hinged main door should cover entire front of switchgear including cable doors for providing fail-safe protection. The unit shall include the following with all necessary standard fittings complete all as specified and as required at site:- (for Sub Station No- 9) |
| 116 | Supply, installation, testing and commissioning Outdoor type (IP 54), 03 way RMU (Ring Main Unit) 11 KV, 630 Amps, 21kA-3 Sec,IP54 SF6 insulated, One side Extensible,consisting of One No (01) motorised vacuum circuit breaker (Incomer) and Two Nos (02) motorised vacuum circuit breaker (Outgoing) & Metering Panel Bus PT with Top LV, Battery & Battery charger, Ethernet switch & LIU (Configuration VVV+M) inside robotically welded stainless steel 304 (Non Ferrite Non Magnetic Grade) tank having min thickness 2.5 +/- 0.5mm with IP 67 degree of protection and enhanced BIL of 75 kVp internally to manage voltage surges and Air Insulated Metering Module of Class-0.5. RMU should be provided with internal busbars, as well as earthing busbars of electrolytic grade copper, padlock provisions complete with all accessories. The complete RMU must be type tested for internal arc 25 KA for 1 sec with AFLR classification for gas tank and cable chamber as per IEC 62271-200. HT RMU shall preferably have on-site-repairability features such as site replaceable bushing/ coupling/ mechanism and gas refilling to have very less downtime in the event of bushing breakage and restoration can be done at site immediately without sending the RMU to OEM Works, the Vaccum Interrupter must be RMU manufacturer\"s own make. The earthing busbar shall be provided inside each cable compartment for solid earthing of cable shields. The outer hinged main door should cover entire front of switchgear including cable doors for providing fail-safe protection. The unit shall include the following with all necessary standard fittings complete all as specified and as required at site:- (At guard room Road Junction at P2) |
| 117 | Notes for item Nos. 82 to 88:-(a) Make of RMU shall be limited to : ABB/ SIEMENS/ SCHNEIDER INFRASTRUCTURE(Channel partner/ System Integrator/ Authourized Partner/ License partner make RMU shall not be accepted.)(b)Vacuum Circuit Breaker shall consist of the following accessories:-(i) Microprocessor based Numerical Protection Relay for Circuit Breakers - REF615, Feeder Protection and Control Relay, Protections 50, 51, 50N, 51N, 46, 49, 67, 67N, 32, 27, 59, 25, 81U, 81O, 95 Measurement for 3I,I0,3U,U0,Kw,KVA,PF,Hz,Kwh, 16 DI + 10 DO, One front RJ45 Port, One Rear RJ45 Port for IEC-61850 Protocol, Drawout Type with CT Shorting feature, Graphical LCD Display(ii) Capacitive voltage indication fixed type system with LED for all feeder and FPI in all load break switch feeder (iii) SF6 Gas pressure indicator on the gas tank(iv) Operating sequence of VCB must be O-0.3Sec-CO-3 Mins-CO amd suitable for 10,000 mechanical operation(v) CT shall be minimum 50-100/1A ,2.5VA , 5P10 - 3 Nos. for protection(vi) CT shall be minimum 50-100/1A ,2.5VA , Class 0.5 - 3 Nos. for metering |
| 118 | (vii) Right angle boot to be provided in each module(viii) 2 x12 Volts, 26 AH Battery with Charger - 1 Set(ix) Bus VT shall be 11KV/V3/110V/V3, 20VA , Class 0.5 - 3 Nos. for metering(x) Auxiliary VT shall be 11KV/230, 500VA for AC supply input to Battery Charger(xi) Capacitive voltage indication fixed type system as per IE(xii) Interlocked cable box for front termination of the cable suitable upto 3 core 120 Sqmm, 11 KV XLPE cable (IP3X) safety interlocked to prevent access to cable termination in live-condition(xiii) Right angle boots (push on type)(xiv) Cable covers with self interlocking mechanism between doors, earth switch, disconnector and VCB(xv) Necessay interclocking arrangement for safety and operations(xvi) One no. operating handle for manual operation and one no. manometer(xvii) Safety interlocks shall be provided as per relevant IEC/ IS standards and manufacturer\"s directions(xviii) Above switchgear shall confirm to all relevant IEC/ IS standards |
| 119 | Supply, installation, commissioning and testing of Transformer of capacity 500 KVA (for Hanger), confirming to IS 1180 (Part-1)- 2014 with latest amendments, BEE 3 star rated, Energy Efficient Level- 3, step down outdoor type complete with standard fittings, HT 11 KV 3 phase, LT 433 volts, 3 phase, 4 wire 17 position On Load tap changer of rating + 10% to -10% in steps @ 1.25% each by means On load tap changing gear (OLTC)+ Remote Tap Cubical Changer (RTCC) Panel+ Automatic Voltage Regulator transformer copper wound, double wound, oil immersed naturally cooled with external cooling tubes core type delta connected on primary side (HV) and star connected on secondary side (LV) in accordance with vector symbol Dyn -11 (vector group with neutral brought on secondary side (LV side) and the maximum temperature rises should not exceed 40 degree centigrade in oil and 45 degree centigrade in HV/LV winding ring measured by resistance after continuous full load run in ambient temp as per IS -2026 per transformer, IS-3639 for fitting and accessories, IS-2099 for high voltage porcelain bushings and the transformer shall be comprised with the following standard fitting with on load tappings on HT side to vary secondary voltage within limit all as per IS -1180 with latest policy and with the specifications given in notes below complete all as specified and as directed. |
| 120 | All as per Item No. 89 above but transformer of capacity 400 KVA (for scientific lab) with the specifications given in notes below complete all as specified and as directed. |
| 121 | Notes for item Nos. 89 and 90:- (a) The quoted rate shall include for supplying transformers with standard fittings and installing complete including all jointing materials, connecting with electrical system, earthing, testing and commissioning.(b) The transformer shall have its initial oil filling to appropriate level (cost of oil including testing with desired dielectric strength to be included in supplied and installed rates, cost of PCC foundation shall be included as per manufacturer drawing)(c) Transformer shall have following specifications:(i) Three Nos porcelain bushing suitable for 11 KV on HV side, complete with copper rods, nuts and washers with cable end box.(ii) Four Nos porcelain bushing suitable for 433V on LV side, complete with copper rods, nuts and washers with cable end box.(iii) Monogram plate.(iv) Oil conservator with filter and drain plug.(v) Prismatic/transparent oil gauge.(vi) De-hydrating breather with first fill of dehydrating agent (silica gel).(vii) Thermometer pocket(viii) Air release plug(ix) Inspection cover(x) Lifting lugs for complete transformer |
| 122 | (xi) Top cover lifting lugs(xii) Jacking lugs(xiii) Top filter valve(xiv) Instruction plate(xv) Drain cum bottom filter valves(xvi) Earthing terminal and stud(xvii) On load tap changer with RTCC & AVR(xviii) Rating and Diagram plate(xix) Buchholz relay with alarm & trip contacts(xx) Bi directional roller wheel -04 Nos.(xxi) Marshalling box for termination of all alarm & trip controls of the transformer.(xxii) WTI (Winding temperature indicator) with alarm & trip contact(xxiii) Oil surge relay.(xxiv) Shut off valve for buchholz relay.(xxv) OTI (Oil temperature indicator) dial type of 150 mm with alarm and trip contact capillary type.(xxvi) Two earthing terminals on tank cover to facilitate fixing of 50x6 mm galvanised iron earth strip for earthing of body.(xxvii) Necessary PCC foundation/ block masonry platform as directed by OEM. (xxviii) First filling of new and unused transformer oil, IS-335 marked. |
| 123 | Supply and fix cable jointing kit for 1100 Volts grade LT UG cable for straight through joint complete with jointing material cold shrink type and accessories suitable for XLPE, armoured, aluminium conductor cable of size 3.5 core x 50 to 95 sqmm for indoor/ outdoor type complete all as specified and directed. |
| 124 | Supply and fix cable jointing kit for 1100 Volts grade LT UG cable for straight through joint complete with jointing material cold shrink type and accessories suitable for XLPE, armoured, aluminium conductor cable of size 3.5 core x 120 to 185 sqmm for indoor/ outdoor type complete all as specified and directed. |
| 125 | Supply, installation, testing and commissioning of factory made Type Test Assemble (TTA) APFC Panel with MPP-H capacitor and suitable capacity MCCB as incommer, indoor type floor mounted, suitable for 415 volts, 3 phase, 4 wire, 50 Hz AC supply system, having bus bar chamber duly insulated; the panel shall be dust and vermin proof, IP 65 class protection and made of 2.0 mm CRCA MS sheet and 50 x 50 x 5 mm thick MS angle iron base frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, both side openingtype, with aprons for cable entry, with double door shutter and locking arrangement having copper bus bar sizefour strips 750 Amps 415 Volts consisting of 250 KVAR with 6 steps (2 x 25 KVAR + 4 x 50 KVAR) complete all as specified and as directed.Location: Hangar |
| 126 | Supply, fabrication, installation and testing of LT Panel, factory made, Type Test Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, Outdoor type, weather proof, water proof, dust proof, vermin proof, shock proof protection made out of 3.15 mm thick CRCA sheet of suitable size to accommodate accessories/ fittings with front and back double door opening/ lockable by the key from both side with IP 65 protection and provision of suitable bus bar chamber and switch gear compartments for MCCB incoming and outgoing feeders etc. with copper extension links of suitable current carrying capacity not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC/ epoxy insulator including provision for termination with incoming and outgoing cables with cable glands. LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminous paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1 (using 20mm graded stone aggregate). All extension link/ interconnection shall be insulated with heat shrinkable colour coded sleeves to accomodate and including the following accessories:- (Pocket No. 1 Offr Md Accn Transformer LT Panel) |
| 127 | INCOMING:-(a) Copper strip busbar of 500 Amps rated capacity wrapped with PVC sleeves with maintaining the colour code and provision of making holes with copper nuts, bolts and washers for cable connections including hydrograpic insulators with nuts and bolts at both ends - 04 Nos.(b) MCCB 250 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links - 01 N - 01 No.(c) LED neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC - 01 set (set of three) (d) Digital Ammeter of range (0- 2000) Amps, flush mounting type with suitable CTs of ratio and selector switch – 01 set.(e) Digital voltmeter of range (0-500) volts, flush mounting type with selector switch - 01 No. |
| 128 | OUTGOING:-(a) MCCB 160 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No (Outgoing) (b) MCCB 125 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No (Outgoing) (c) MCCB 25 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 07 Nos (Outgoing)(d) MCCB 16 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No (Outgoing) (e) Enamelled iron danger notice plate made of 1.60 mm thick mild steel sheet of size 200 mm X 150mm, white with letters, figures and conventional skull and bones in signal red and fixed with nuts and bolts on door/ shutter of LT Panel - 01 No. |
| 129 | Supply, fabrication, installation and testing of LT Panel, factory made, Type Test Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, Outdoor type, weather proof, water proof, dust proof, vermin proof, shock proof protection made out of 3.15 mm thick CRCA sheet of suitable size to accommodate accessories/ fittings with front and back double door opening/ lockable by the key from both side with IP 65 protection and provision of suitable bus bar chamber and switch gear compartments for MCCB incoming and outgoing feeders etc. with copper extension links of suitable current carrying capacity not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC/ epoxy insulator including provision for termination with incoming and outgoing cables with cable glands. LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminous paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1 (using 20mm graded stone aggregate). All extension link/ interconnection shall be insulated with heat shrinkable colour coded sleeves to accomodate and including the following accessories:- (Pocket No 2 Offr Mess & Single living Accn Transformer LT Panel) |
| 130 | INCOMING:-(a) Copper strip busbar of 300 Amps rated capacity wrapped with PVC sleeves with maintaining the colour code and provision of making holes with copper nuts, bolts and washers for cable connections including hydrograpic insulators with nuts and bolts at both ends - 04 Nos.(b) MCCB 160 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links - 01 No. (Incoming)(c) LED neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC - 01 set (set of three) (d) Digital Ammeter of range (0- 1000) Amps, flush mounting type with suitable CTs of ratio and selector switch – 01 set.(e) Digital voltmeter of range (0-500) volts, flush mounting type with selector switch - 01 No. |
| 131 | OUTGOING:-(a) MCCB 100 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No (Outgoing) (b) MCCB 63 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing) (c) MCCB 25 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 02 Nos (Outgoing)(d) MCCB 16 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 03 Nos. (Outgoing) (e) Enamelled iron danger notice plate made of 1.60 mm thick mild steel sheet of size 200 mm X 150mm, white with letters, figures and conventional skull and bones in signal red and fixed with nuts and bolts on door/ shutter of LT Panel - 01 No. |
| 132 | Supply, fabrication, installation and testing of LT Panel, factory made, Type Test Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, Outdoor type, weather proof, water proof, dust proof, vermin proof, shock proof protection made out of 3.15 mm thick CRCA sheet of suitable size to accommodate accessories/ fittings with front and back double door opening/ lockable by the key from both side with IP 65 protection and provision of suitable bus bar chamber and switch gear compartments for MCCB incoming and outgoing feeders etc. with copper extension links of suitable current carrying capacity not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC/ epoxy insulator including provision for termination with incoming and outgoing cables with cable glands. LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminous paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1 (using 20mm graded stone aggregate). All extension link/ interconnection shall be insulated with heat shrinkable colour coded sleeves to accomodate and including the following accessories:- (Pocket No 3 Stn HQ Transformer LT panel) |
| 133 | INCOMING:-(a) Copper strip busbar of 500 Amps rated capacity wrapped with PVC sleeves with maintaining the colour code and provision of making holes with copper nuts, bolts and washers for cable connections including hydrograpic insulators with nuts and bolts at both ends - 04 Nos.(b) MCCB 250 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links - 01 No. (Incoming)(c) LED neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC - 01 set (set of three) (d) Digital Ammeter of range (0- 1000) Amps, flush mounting type with suitable CTs of ratio and selector switch – 01 set.(e) Digital voltmeter of range (0-500) volts, flush mounting type with selector switch - 01 No. |
| 134 | OUTGOING:-(a) MCCB 100 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 03 Nos. (Outgoing) (b) MCCB 63 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing) (c) MCCB 16 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing)(d) Enamelled iron danger notice plate made of 1.60 mm thick mild steel sheet of size 200 mm X 150mm, white with letters, figures and conventional skull and bones in signal red and fixed with nuts and bolts on door/ shutter of LT Panel - 01 No. |
| 135 | Supply, fabrication, installation and testing of LT Panel, factory made, Type Test Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, Outdoor type, weather proof, water proof, dust proof, vermin proof, shock proof protection made out of 3.15 mm thick CRCA sheet of suitable size to accommodate accessories/ fittings with front and back double door opening/ lockable by the key from both side with IP 65 protection and provision of suitable bus bar chamber and switch gear compartments for MCCB incoming and outgoing feeders etc. with copper extension links of suitable current carrying capacity not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC/ epoxy insulator including provision for termination with incoming and outgoing cables with cable glands. LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminous paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1 (using 20mm graded stone aggregate). All extension link/ interconnection shall be insulated with heat shrinkable colour coded sleeves to accomodate and including the following accessories:- (Pocket No 4 at SMC Area Transformer LT Panel) |
| 136 | INCOMING:-(a) Copper strip busbar of 1000 Amps rated capacity wrapped with PVC sleeves with maintaining the colour code and provision of making holes with copper nuts, bolts and washers for cable connections including hydrograpic insulators with nuts and bolts at both ends - 04 Nos.(b) MCCB 500 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links - 01 No. (Incoming)(c) LED neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC - 01 set (set of three) (d) Digital Ammeter of range (0- 1000) Amps, flush mounting type with suitable CTs of ratio and selector switch – 01 set.(e) Digital voltmeter of range (0-500) volts, flush mounting type with selector switch - 01 No. |
| 137 | OUTGOING:-(a) MCCB 320 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing) (b) MCCB 160 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing) (c) MCCB 32 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing)(d) MCCB 16 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing)(e) Enamelled iron danger notice plate made of 1.60 mm thick mild steel sheet of size 200 mm X 150mm, white with letters, figures and conventional skull and bones in signal red and fixed with nuts and bolts on door/ shutter of LT Panel - 01 No. |
| 138 | Supply, fabrication, installation and testing of LT Panel, factory made, Type Test Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, Outdoor type, weather proof, water proof, dust proof, vermin proof, shock proof protection made out of 3.15 mm thick CRCA sheet of suitable size to accommodate accessories/ fittings with front and back double door opening/ lockable by the key from both side with IP 65 protection and provision of suitable bus bar chamber and switch gear compartments for MCCB incoming and outgoing feeders etc. with copper extension links of suitable current carrying capacity not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC/ epoxy insulator including provision for termination with incoming and outgoing cables with cable glands. LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminous paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1 (using 20mm graded stone aggregate). All extension link/ interconnection shall be insulated with heat shrinkable colour coded sleeves to accomodate and including the following accessories:- (Pocket No 5 at DSC Single living Transformer LT Panel) |
| 139 | INCOMING:-(a) Copper strip busbar of 1000 Amps rated capacity wrapped with PVC sleeves with maintaining the colour code and provision of making holes with copper nuts, bolts and washers for cable connections including hydrograpic insulators with nuts and bolts at both ends - 04 Nos.(b) MCCB 500 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links - 01 No. (Incoming)(c) LED neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC - 01 set (set of three) (d) Digital Ammeter of range (0- 1000) Amps, flush mounting type with suitable CTs of ratio and selector switch – 01 set.(e) Digital voltmeter of range (0-500) volts, flush mounting type with selector switch - 01 No. |
| 140 | OUTGOING:-(a) MCCB 100 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 03 Nos. (Outgoing) (b) MCCB 63 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 02 Nos. (Outgoing) (c) MCCB 16 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 05 Nos. (Outgoing)(d) Enamelled iron danger notice plate made of 1.60 mm thick mild steel sheet of size 200 mm X 150mm, white with letters, figures and conventional skull and bones in signal red and fixed with nuts and bolts on door/ shutter of LT Panel - 01 No. |
| 141 | Supply, fabrication, installation and testing of LT Panel, factory made, Type Test Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, Outdoor type, weather proof, water proof, dust proof, vermin proof, shock proof protection made out of 3.15 mm thick CRCA sheet of suitable size to accommodate accessories/ fittings with front and back double door opening/ lockable by the key from both side with IP 65 protection and provision of suitable bus bar chamber and switch gear compartments for MCCB incoming and outgoing feeders etc. with copper extension links of suitable current carrying capacity not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC/ epoxy insulator including provision for termination with incoming and outgoing cables with cable glands. LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminous paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1 (using 20mm graded stone aggregate). All extension link/ interconnection shall be insulated with heat shrinkable colour coded sleeves to accomodate and including the following accessories:- (Pocket No 6 at ATC Transformer LT Panel) |
| 142 | INCOMING:-(a) Copper strip busbar of 1000 Amps rated capacity wrapped with PVC sleeves with maintaining the colour code and provision of making holes with copper nuts, bolts and washers for cable connections including hydrograpic insulators with nuts and bolts at both ends - 04 Nos.(b) MCCB 500 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links - 01 No. (Incoming)(c) LED neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC - 01 set (set of three) (d) Digital Ammeter of range (0- 1000) Amps, flush mounting type with suitable CTs of ratio and selector switch – 01 set.(e) Digital voltmeter of range (0-500) volts, flush mounting type with selector switch - 01 No. |
| 143 | OUTGOING:-(a) MCCB 320 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing) (b) MCCB 100 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing) (c) MCCB 63 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing)(d) MCCB 32 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 02 Nos. (Outgoing)(e) MCCB 16 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 06 Nos. (Outgoing)(f) Enamelled iron danger notice plate made of 1.60 mm thick mild steel sheet of size 200 mm X 150mm, white with letters, figures and conventional skull and bones in signal red and fixed with nuts and bolts on door/ shutter of LT Panel - 01 No. |
| 144 | Supply, fabrication, installation and testing of LT Panel, factory made, Type Test Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, Outdoor type, weather proof, water proof, dust proof, vermin proof, shock proof protection made out of 3.15 mm thick CRCA sheet of suitable size to accommodate accessories/ fittings with front and back double door opening/ lockable by the key from both side with IP 65 protection and provision of suitable bus bar chamber and switch gear compartments for MCCB incoming and outgoing feeders etc. with copper extension links of suitable current carrying capacity not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC/ epoxy insulator including provision for termination with incoming and outgoing cables with cable glands. LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminous paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1 (using 20mm graded stone aggregate). All extension link/ interconnection shall be insulated with heat shrinkable colour coded sleeves to accomodate and including the following accessories:- (Pocket No 7 at Scientific Lab Complex Transformer LT Panel) |
| 145 | INCOMING:-(a) Copper strip busbar of 1200 Amps rated capacity wrapped with PVC sleeves with maintaining the colour code and provision of making holes with copper nuts, bolts and washers for cable connections including hydrograpic insulators with nuts and bolts at both ends - 04 Nos.(b) MCCB 630 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links - 01 No. (Incoming)(c) LED neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC - 01 set (set of three) (d) Digital Ammeter of range (0- 1000) Amps, flush mounting type with suitable CTs of ratio and selector switch – 01 set.(e) Digital voltmeter of range (0-500) volts, flush mounting type with selector switch - 01 No. |
| 146 | OUTGOING:-(a) MCCB 250 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing) (b) MCCB 160 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing) (c) MCCB 100 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 03 Nos. (Outgoing)(d) MCCB 63 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing)(e) MCCB 32 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 02 Nos. (Outgoing)(f) MCCB 16 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 02 Nos. (Outgoing)(g) Enamelled iron danger notice plate made of 1.60 mm thick mild steel sheet of size 200 mm X 150mm, white with letters, figures and conventional skull and bones in signal red and fixed with nuts and bolts on door/ shutter of LT Panel - 01 No. |
| 147 | Supply, fabrication, installation and testing of LT Panel, factory made, Type Test Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, Outdoor type, weather proof, water proof, dust proof, vermin proof, shock proof protection made out of 3.15 mm thick CRCA sheet of suitable size to accommodate accessories/ fittings with front and back double door opening/ lockable by the key from both side with IP 65 protection and provision of suitable bus bar chamber and switch gear compartments for MCCB incoming and outgoing feeders etc. with copper extension links of suitable current carrying capacity not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC/ epoxy insulator including provision for termination with incoming and outgoing cables with cable glands. LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminous paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1 (using 20mm graded stone aggregate). All extension link/ interconnection shall be insulated with heat shrinkable colour coded sleeves to accomodate and including the following accessories:- (Pocket No 8 at Hangar Transformer LT Panel) |
| 148 | INCOMING:-(a) Copper strip busbar of 1600 Amps rated capacity wrapped with PVC sleeves with maintaining the colour code and provision of making holes with copper nuts, bolts and washers for cable connections including hydrograpic insulators with nuts and bolts at both ends - 04 Nos.(b) ACB 4 Pole 800 Amps, draw-out type circuit breaker with microprocessor based ET6L trip unit with thermal memory, fully rated neutral with in built protection, ET6L provides over load, shortcircuit, instantaneous and earth-fault protections, short circuit breaking capacity 50 KA @ 440 volts AC, conforms to IS/ IEC60947-2&3- 01 No. (Incoming)(c) LED neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC - 01 set (set of three) (d) Digital Ammeter of range (0- 1000) Amps, flush mounting type with suitable CTs of ratio and selector switch – 01 set.(e) Digital voltmeter of range (0-500) volts, flush mounting type with selector switch - 01 No. |
| 149 | OUTGOING:-(a) MCCB 400 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing) (b) MCCB 320 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing) (c) MCCB 100 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing)(d) MCCB 63 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing)(e) MCCB 16 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 02 Nos. (Outgoing)(f) Enamelled iron danger notice plate made of 1.60 mm thick mild steel sheet of size 200 mm X 150mm, white with letters, figures and conventional skull and bones in signal red and fixed with nuts and bolts on door/ shutter of LT Panel - 01 No. |
| 150 | Supply, fabrication, installation and testing of LT Panel, factory made, Type Test Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, Outdoor type, weather proof, water proof, dust proof, vermin proof, shock proof protection made out of 3.15 mm thick CRCA sheet of suitable size to accommodate accessories/ fittings with front and back double door opening/ lockable by the key from both side with IP 65 protection and provision of suitable bus bar chamber and switch gear compartments for MCCB incoming and outgoing feeders etc. with copper extension links of suitable current carrying capacity not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC/ epoxy insulator including provision for termination with incoming and outgoing cables with cable glands. LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminous paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1 (using 20mm graded stone aggregate). All extension link/ interconnection shall be insulated with heat shrinkable colour coded sleeves to accomodate and including the following accessories:- (Pocket No 9 at CEO Complex Transformer LT Panel) |
| 151 | INCOMING:-(a) Copper strip busbar of 300 Amps rated capacity wrapped with PVC sleeves with maintaining the colour code and provision of making holes with copper nuts, bolts and washers for cable connections including hydrograpic insulators with nuts and bolts at both ends - 04 Nos.(b) MCCB 160 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links - 01 No. (Incoming)(c) LED neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC - 01 set (set of three) (d) Digital Ammeter of range (0- 1000) Amps, flush mounting type with suitable CTs of ratio and selector switch – 01 set.(e) Digital voltmeter of range (0-500) volts, flush mounting type with selector switch - 01 No. |
| 152 | OUTGOING:-(a) MCCB 100 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing) (b) MCCB 63 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing)(c) MCCB 16 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing)(d) Enamelled iron danger notice plate made of 1.60 mm thick mild steel sheet of size 200 mm X 150mm, white with letters, figures and conventional skull and bones in signal red and fixed with nuts and bolts on door/ shutter of LT Panel - 01 No. |
| 153 | Supply, fabrication, installation and testing of LT Panel, factory made, Type Test Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, Outdoor type, weather proof, water proof, dust proof, vermin proof, shock proof protection made out of 3.15 mm thick CRCA sheet of suitable size to accommodate accessories/ fittings with front and back double door opening/ lockable by the key from both side with IP 65 protection and provision of suitable bus bar chamber and switch gear compartments for MCCB incoming and outgoing feeders etc. with copper extension links of suitable current carrying capacity not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC/ epoxy insulator including provision for termination with incoming and outgoing cables with cable glands. LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminous paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1 (using 20mm graded stone aggregate). All extension link/ interconnection shall be insulated with heat shrinkable colour coded sleeves to accomodate and including the following accessories:- (Pocket No 10 at Logistic Transformer LT Panel) |
| 154 | INCOMING:-(a) Copper strip busbar of 1000 Amps rated capacity wrapped with PVC sleeves with maintaining the colour code and provision of making holes with copper nuts, bolts and washers for cable connections including hydrograpic insulators with nuts and bolts at both ends - 04 Nos.(b) MCCB 500 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links - 01 No. (Incoming)(c) LED neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC - 01 set (set of three) (d) Digital Ammeter of range (0- 1000) Amps, flush mounting type with suitable CTs of ratio and selector switch – 01 set.(e) Digital voltmeter of range (0-500) volts, flush mounting type with selector switch - 01 No. |
| 155 | OUTGOING:-(a) MCCB 160 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 03 Nos. (Outgoing) (b) MCCB 40 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 02 Nos. (Outgoing) (c) MCCB 32 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing)(d) MCCB 16 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 04 Nos. (Outgoing)(e) Enamelled iron danger notice plate made of 1.60 mm thick mild steel sheet of size 200 mm X 150mm, white with letters, figures and conventional skull and bones in signal red and fixed with nuts and bolts on door/ shutter of LT Panel - 01 No. |
| 156 | Supply, fabrication, installation and testing of LT Panel, factory made, Type Test Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, Outdoor type, weather proof, water proof, dust proof, vermin proof, shock proof protection made out of 3.15 mm thick CRCA sheet of suitable size to accommodate accessories/ fittings with front and back double door opening/ lockable by the key from both side with IP 65 protection and provision of suitable bus bar chamber and switch gear compartments for MCCB incoming and outgoing feeders etc. with copper extension links of suitable current carrying capacity not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC/ epoxy insulator including provision for termination with incoming and outgoing cables with cable glands. LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminous paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1 (using 20mm graded stone aggregate). All extension link/ interconnection shall be insulated with heat shrinkable colour coded sleeves to accomodate and including the following accessories:- (Pocket No 11 at 06 End Blast Pen Panel) |
| 157 | INCOMING:-(a) Copper strip busbar of 600 Amps rated capacity wrapped with PVC sleeves with maintaining the colour code and provision of making holes with copper nuts, bolts and washers for cable connections including hydrograpic insulators with nuts and bolts at both ends - 04 Nos.(b) MCCB 320 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links - 01 No. (Incoming)(c) LED neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC - 01 set (set of three) (d) Digital Ammeter of range (0- 1000) Amps, flush mounting type with suitable CTs of ratio and selector switch – 01 set.(e) Digital voltmeter of range (0-500) volts, flush mounting type with selector switch - 01 No. |
| 158 | OUTGOING:-(a) MCCB 250 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing) (b) MCCB 40 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing) (c) MCCB 16 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 04 Nos. (Outgoing)(d) Enamelled iron danger notice plate made of 1.60 mm thick mild steel sheet of size 200 mm X 150mm, white with letters, figures and conventional skull and bones in signal red and fixed with nuts and bolts on door/ shutter of LT Panel - 01 No. |
| 159 | Supply, fabrication, installation and testing of LT Panel, factory made, Type Test Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, Outdoor type, weather proof, water proof, dust proof, vermin proof, shock proof protection made out of 3.15 mm thick CRCA sheet of suitable size to accommodate accessories/ fittings with front and back double door opening/ lockable by the key from both side with IP 65 protection and provision of suitable bus bar chamber and switch gear compartments for MCCB incoming and outgoing feeders etc. with copper extension links of suitable current carrying capacity not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC/ epoxy insulator including provision for termination with incoming and outgoing cables with cable glands. LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminous paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1 (using 20mm graded stone aggregate). All extension link/ interconnection shall be insulated with heat shrinkable colour coded sleeves to accomodate and including the following accessories:- (Pocket No 12 at Double Entry Blast Pen Transformer LT Panel) |
| 160 | INCOMING:-(a) Copper strip busbar of 500 Amps rated capacity wrapped with PVC sleeves with maintaining the colour code and provision of making holes with copper nuts, bolts and washers for cable connections including hydrograpic insulators with nuts and bolts at both ends - 04 Nos.(b) MCCB 250 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links - 01 No. (Incoming)(c) LED neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC - 01 set (set of three) (d) Digital Ammeter of range (0- 1000) Amps, flush mounting type with suitable CTs of ratio and selector switch – 01 set.(e) Digital voltmeter of range (0-500) volts, flush mounting type with selector switch - 01 No. |
| 161 | OUTGOING:-(a) MCCB 100 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing) (b) MCCB 32 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing) (c) MCCB 16 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 06 Nos. (Outgoing)(d) Enamelled iron danger notice plate made of 1.60 mm thick mild steel sheet of size 200 mm X 150mm, white with letters, figures and conventional skull and bones in signal red and fixed with nuts and bolts on door/ shutter of LT Panel - 01 No. |
| 162 | Supply, fabrication, installation and testing of LT Panel, factory made, Type Test Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, Outdoor type, weather proof, water proof, dust proof, vermin proof, shock proof protection made out of 3.15 mm thick CRCA sheet of suitable size to accommodate accessories/ fittings with front and back double door opening/ lockable by the key from both side with IP 65 protection and provision of suitable bus bar chamber and switch gear compartments for MCCB incoming and outgoing feeders etc. with copper extension links of suitable current carrying capacity not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC/ epoxy insulator including provision for termination with incoming and outgoing cables with cable glands. LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminous paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1 (using 20mm graded stone aggregate). All extension link/ interconnection shall be insulated with heat shrinkable colour coded sleeves to accomodate and including the following accessories:- (Pocket No 13 at BOCC Complex Transformer LT Panel) |
| 163 | INCOMING:-(a) Copper strip busbar of 600 Amps rated capacity wrapped with PVC sleeves with maintaining the colour code and provision of making holes with copper nuts, bolts and washers for cable connections including hydrograpic insulators with nuts and bolts at both ends - 04 Nos.(b) MCCB 320 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links - 01 No. (Incoming)(c) LED neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC - 01 set (set of three) (d) Digital Ammeter of range (0- 1000) Amps, flush mounting type with suitable CTs of ratio and selector switch – 01 set.(e) Digital voltmeter of range (0-500) volts, flush mounting type with selector switch - 01 No. |
| 164 | OUTGOING:-(a) MCCB 160 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing) (b) MCCB 100 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing) (c) MCCB 63 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing)(d) MCCB 40 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing)(e) MCCB 32 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing)(f) MCCB 16 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 02 Nos. (Outgoing)(g) Enamelled iron danger notice plate made of 1.60 mm thick mild steel sheet of size 200 mm X 150mm, white with letters, figures and conventional skull and bones in signal red and fixed with nuts and bolts on door/ shutter of LT Panel - 01 No. |
| 165 | Supply, fabrication, installation and testing of LT Panel, factory made, Type Test Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, Outdoor type, weather proof, water proof, dust proof, vermin proof, shock proof protection made out of 3.15 mm thick CRCA sheet of suitable size to accommodate accessories/ fittings with front and back double door opening/ lockable by the key from both side with IP 65 protection and provision of suitable bus bar chamber and switch gear compartments for MCCB incoming and outgoing feeders etc. with copper extension links of suitable current carrying capacity not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC/ epoxy insulator including provision for termination with incoming and outgoing cables with cable glands. LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminous paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1 (using 20mm graded stone aggregate). All extension link/ interconnection shall be insulated with heat shrinkable colour coded sleeves to accomodate and including the following accessories:- (Pocket No 14 at Blast Pen 24 End Transformer LT Panel) |
| 166 | INCOMING:-(a) Copper strip busbar of 600 Amps rated capacity wrapped with PVC sleeves with maintaining the colour code and provision of making holes with copper nuts, bolts and washers for cable connections including hydrograpic insulators with nuts and bolts at both ends - 04 Nos.(b) MCCB 320 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links - 01 No. (Incoming)(c) LED neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC - 01 set (set of three) (d) Digital Ammeter of range (0- 1000) Amps, flush mounting type with suitable CTs of ratio and selector switch – 01 set.(e) Digital voltmeter of range (0-500) volts, flush mounting type with selector switch - 01 No. |
| 167 | OUTGOING:-(a) MCCB 250 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing) (b) MCCB 40 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing) (c) MCCB 16 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 03 Nos. (Outgoing)(d) Enamelled iron danger notice plate made of 1.60 mm thick mild steel sheet of size 200 mm X 150mm, white with letters, figures and conventional skull and bones in signal red and fixed with nuts and bolts on door/ shutter of LT Panel - 01 No. |
| 168 | Supply, fabrication, installation and testing of LT Panel, factory made, Type Test Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, Outdoor type, weather proof, water proof, dust proof, vermin proof, shock proof protection made out of 3.15 mm thick CRCA sheet of suitable size to accommodate accessories/ fittings with front and back double door opening/ lockable by the key from both side with IP 65 protection and provision of suitable bus bar chamber and switch gear compartments for MCCB incoming and outgoing feeders etc. with copper extension links of suitable current carrying capacity not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC/ epoxy insulator including provision for termination with incoming and outgoing cables with cable glands. LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminous paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1 (using 20mm graded stone aggregate). All extension link/ interconnection shall be insulated with heat shrinkable colour coded sleeves to accomodate and including the following accessories:- (Pocket No 15 at STP Transformer LT Panel and Pocket No 16 at Pump House Transformer LT Panel) |
| 169 | INCOMING:-(a) Copper strip busbar of 300 Amps rated capacity wrapped with PVC sleeves with maintaining the colour code and provision of making holes with copper nuts, bolts and washers for cable connections including hydrograpic insulators with nuts and bolts at both ends - 04 Nos.(b) MCCB 160 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links - 01 No. (Incoming)(c) LED neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC - 01 set (set of three) (d) Digital Ammeter of range (0- 1000) Amps, flush mounting type with suitable CTs of ratio and selector switch – 01 set.(e) Digital voltmeter of range (0-500) volts, flush mounting type with selector switch - 01 No. |
| 170 | OUTGOING:-(a) MCCB 100 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing) (b) MCCB 16 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing)(c) Enamelled iron danger notice plate made of 1.60 mm thick mild steel sheet of size 200 mm X 150mm, white with letters, figures and conventional skull and bones in signal red and fixed with nuts and bolts on door/ shutter of LT Panel - 01 No. |
| 171 | Supply, fabrication, installation and testing of LT Panel, factory made, Type Test Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, Outdoor type, weather proof, water proof, dust proof, vermin proof, shock proof protection made out of 3.15 mm thick CRCA sheet of suitable size to accommodate accessories/ fittings with front and back double door opening/ lockable by the key from both side with IP 65 protection and provision of suitable bus bar chamber and switch gear compartments for MCCB incoming and outgoing feeders etc. with copper extension links of suitable current carrying capacity not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC/ epoxy insulator including provision for termination with incoming and outgoing cables with cable glands. LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminous paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1 (using 20mm graded stone aggregate). All extension link/ interconnection shall be insulated with heat shrinkable colour coded sleeves to accomodate and including the following accessories:- (Pocket No 17 at MRS Transformer LT Panel) |
| 172 | INCOMING:-(a) Copper strip busbar of 300 Amps rated capacity wrapped with PVC sleeves with maintaining the colour code and provision of making holes with copper nuts, bolts and washers for cable connections including hydrograpic insulators with nuts and bolts at both ends - 04 Nos.(b) MCCB 160 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links - 01 No. (Incoming)(c) LED neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC - 01 set (set of three) (d) Digital Ammeter of range (0- 1000) Amps, flush mounting type with suitable CTs of ratio and selector switch – 01 set.(e) Digital voltmeter of range (0-500) volts, flush mounting type with selector switch - 01 No. |
| 173 | OUTGOING:-(a) MCCB 100 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing) (b) MCCB 63 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing)(c) MCCB 16 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing)(d) Enamelled iron danger notice plate made of 1.60 mm thick mild steel sheet of size 200 mm X 150mm, white with letters, figures and conventional skull and bones in signal red and fixed with nuts and bolts on door/ shutter of LT Panel - 01 No. |
| 174 | Supply, fabrication, installation and testing of LT Panel, factory made, Type Test Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, Outdoor type, weather proof, water proof, dust proof, vermin proof, shock proof protection made out of 3.15 mm thick CRCA sheet of suitable size to accommodate accessories/ fittings with front and back double door opening/ lockable by the key from both side with IP 65 protection and provision of suitable bus bar chamber and switch gear compartments for MCCB incoming and outgoing feeders etc. with copper extension links of suitable current carrying capacity not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC/ epoxy insulator including provision for termination with incoming and outgoing cables with cable glands. LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminous paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1 (using 20mm graded stone aggregate). All extension link/ interconnection shall be insulated with heat shrinkable colour coded sleeves to accomodate and including the following accessories:- (Pocket No 18 at Main Guard Room Transformer LT Panel) |
| 175 | INCOMING:-(a) Copper strip busbar of 300 Amps rated capacity wrapped with PVC sleeves with maintaining the colour code and provision of making holes with copper nuts, bolts and washers for cable connections including hydrograpic insulators with nuts and bolts at both ends - 04 Nos.(b) MCCB 160 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links - 01 No. (Incoming)(c) LED neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC - 01 set (set of three) (d) Digital Ammeter of range (0- 1000) Amps, flush mounting type with suitable CTs of ratio and selector switch – 01 set.(e) Digital voltmeter of range (0-500) volts, flush mounting type with selector switch - 01 No. |
| 176 | OUTGOING:-(a) MCCB 63 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links- 03 Nos. (Outgoing) (b) MCCB 32 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 02 Nos. (Outgoing)(c) MCCB 16 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 25 KA breaking capacity including all fixing accessories with both ends spreader links- 01 No. (Outgoing)(d) Enamelled iron danger notice plate made of 1.60 mm thick mild steel sheet of size 200 mm X 150mm, white with letters, figures and conventional skull and bones in signal red and fixed with nuts and bolts on door/ shutter of LT Panel - 01 No. |
| 177 | Note for item no 93 to 110 :-(i)Rate of earthwork and PCC work etc are deemed to be inclusive in this item.(ii)Design of LT Panel including components, layout, their design as per IEC-61439 duly certified by ASTA or other approved agency.(iii)OEM design & GA drawingshall be submitted to GE for approval before start the manufacture(iv) Requisite tests required as per IEC-61439 guidelines to be conducted and report shall be submitted by OEM to Garrison Engineer. Further Factory inspection for routine inspection/ testing shall be carried out by Rep of accepting officer along with Rep of OEM before dispatch from factory. Testing charges shall be included in the quoted rates of item.(v) Make of Factory made TTA Panel shall be limited to : ABB/ SIEMENS/ SCHNEIDER/ L&T/ C&S/ LEGRAND INFRASTRUCTURE and also their approved Channel Partner/ Authorized Partner/ Licensee Partner, which are also Approved by MESand further the following:-(a) The name of proposed channel Partner with necessary certificate from OEM which the TTA Panels shall be first got approved from Accepting Officer.(b) The invoice of LT Panel/ components of LT Panel (Switch gears & protection material) shall be from original manufacturer only & not from the channel Partner |
| 178 | Supply, installation, testing and commissioning of battery charger thyristor based controlled automatic float cum boost charger and DC distribution board in a common cubicle complete all as specified and directed. The charger shall be suitable for 230 V +/- 10% single phase AC input and the output shall be suitable to float/ boost charge 24 V with 100 AH batteries and also supply load. The output shall remain constant within +/-2% for AC voltage variation 230 V and load variation 0-100%. The unit shall comprise of following:-(a) Batteries 2 Volts 100 AH - 12 Nos VRLA cells in modular form sealed maintenance free.(b) Current Rating 15 Amps. (c) Incomer MCB DP 20 A - 01 No.(d) Input working voltage: 180 -270 Volts (e) Nominal Input Voltage - 230 V , AC, 50 Hz, 1(f) On load input power factor - > 0.8 |
| 179 | (g) On load unit watt efficiencies - > 80% (h) No load losses of complete charge -< 10%(j) Ripple contents on the load (RMS) = 1% to 5% (k) Over load - 110% for 30 minutes and will give visual indication for over load condition.(l) Boost charging - 2.4 V/Cell(m) Float charging - 2.15 V/Cell(n) Float cum boost charging - Automatically changes from one state to another state as per battery condition and will give the visual indication for either float or boost based on charging mode.(o) Reverse polarity - No damage will caused. A visual indication for reverse polarity will appear with an audio alarm.(p) Short circuit- MCB protection provided |
| 180 | Supply and fix hot dipped galvanized CABLOFIL wire mesh cable tray of size 600 mm width x 54 mm height complying standard EN ISO 1461, manufactured with a longitudinal \"T- welded\" safety edge, constructed with 50 x 100 mm mesh configuration including couplers, covers with clips and wall mounting accessories as per site requirement complete all as specified and directed. Supports, brackets or hangers, covers designed loading capacities of the brackets and the hanger torques must be tested in accordance with the standard IEC 61537. |
| 181 | All as per item No. 112, but of size 450 mm width x 54 mm height. |
| 182 | All as per item No. 112, but of size 200 mm width x 54 mm height. |
| 183 | Supply and lay PVC insulated PVC sheathed cable galvanized steel strip or wire armoured electric control cables (heavy duty) with stranded copper conductor of size 16 core x 2.5 sqmm 1100 volts grade complete all as specified and directed. |
| 184 | Supply and fix horizontal double mounting siren, three phase, 3 HP, 2800 RPM, 5 km range complete with starter, necessary foundation, protection shed complete all as specified and directed. |
| 185 | Supply and fix differential sound siren system 8 to 10 sound with composite panel complete all as specified and directed. |
| 186 | Supply and lay rubber mat of size 1.0 metre x 2.0 metre x 19.0 mm thick complete all as specified and directed. |
| 187 | Supply only electrical rubber hand gloves suitable for 11 KV system complete all as specified and directed. |
| 188 | M & L for construction of brick masonary chamber for HT cable joint of size 1200 mm x 1200 mm x 800 mm internal dimension, One brick thick wall in cement mortar 1:4 on 100 mm thick PCC 1:4:8 (40mm graded aggregate) in foundation, rendering 15mm thick (1:4) internally and externally upto 150 mm below GL, providing 3.0 mm thick MS sheet valve pit cover, welded with 40 x 5mm flat iron frame alround including provision of hinges, handle and locking arrangement and 40 x 40 x 6mm angle iron frame fixed on top of valve pit by means of holdfast 150mm long, embedded in PCC 1:2:4 (20mm graded aggregate) block of size 230 x 200 x 100 mm, applying two coats of anti-corrosive paint over a coat of red oxide zinc chrome primer after preparation of all exposed to steel surfaces including necessary earth work in any type of soil complete all as specified and directed. |
| 189 | M & L for maintenance free Chemical earthing of technology with copper bonded steel rod 3 mtr long 25.0 mm dia with 250-micron Copper bonded coating and UL listed. There should be terminal for connection of 150 x 50 x 6 mm with 4 holes of 12 mm dia along with 2 bags of 25 Kgs each of earth enhancing compound. The chemical compound should be tested and certified by any NABL accredited laboratory with 95 percent carbon content. The testing laboratory should be an ISO 9001 and 14001 certified. The earth enhancing compound should be IEC 62321. The ph value of compound should be 7-8. Electrode should be duly tested and certified by CPRI, Govt of India for a min short circuit current of 25 kA rms for 1 Sec. including necessary boring of suitable dia upto required depth in any type of soil for inserting copper rod and filling of chemicals and Poly plastic pit cover of material- polymer body & cover dimensions- 308 mm (L) x 308 mm (W) x 214 mm (H) bearing capacity 7.5 Ton approved from NABL approved Lab complete all as specified and as directed. |
| 190 | Notes:- (i) Earthing is to be done infront of the Engr-in-Charge.(ii) Test results of earthing to be submitted by the contractor for all earthings. (iii) The contractor shall have to give written guarantee for maintaining earth resistance of less than 1.0 Ohm for the period of Ten (10) years after certified date of completion and shall deposit an amount of Rs. 2000/- per earthing as security deposit for a period of Ten (10) Years.(iv) Failing to maintain resistance of earthing less than 1.0 Ohm, new earthing is to be provided by the contractor without any extra cost.(v) Necessary earth work, excavation shall be carried out in any type of soil strata, retuning, filling in and making good surrounding area complete. |
| 191 | SMART STREET LIGHT |
| 192 | Supply, fixing, installing and commissioning of Octagonal Galvanised Iron street light pole 8 mtr long, top dia 70 mm, bottom dia 135 mm, made out of GIsheet thickness 3 mm and base plate dimensions 300 x 300 x16 mm thickness, the pole shall be galvanized as per IS 4759/ BSEN1461 standards/ housing with in built door locking arrangement for provision ofterminal plate consistingterminal block suitable size of \"connectwell\" copper stud teriminal (provision for socket bolting)- 04 Nosfor 3 Phase and neutral for incoming & out going cable connectios etc withMCB SP 5 Amps- 01 Noinside andjunction box complete with necessary electrical connections including 04 Nos foundation \"J\" bolts of sizeas per manufacutrer design should be hot dipped galvanised and including ornament type decorative GI single arm manufaturer bracketfixed to pole and necessary concrete foundation 1:2:4 concrete including necessary excavation, earth work, refilling etc complete all as specfied and directed. |
| 193 | Supply, fixing, installing and commissioning of Octagonal Galvanised Iron street light pole 8 mtr long, top dia 70 mm, bottom dia 135 mm, made out of GIsheet thickness 3 mm and base plate dimensions 300 x 300 x16 mm thickness, the pole shall be galvanized as per IS 4759/ BSEN1461 standards/ housing with in built door locking arrangement for provision ofterminal plate consistingterminal block suitable size of \"connectwell\" copper stud teriminal (provision for socket bolting)- 04 Nosfor 3 Phase and neutral for incoming & out going cable connectios etc withMCB SP 5 Amps- 01 Noinside andjunction box complete with necessary electrical connections including 04 Nos foundation \"J\" bolts of sizeas per manufacutrer design should be hot dipped galvanised and including ornament type decorative GI double arm manufaturer bracketfixed to pole and necessary concrete foundation 1:2:4 concrete including necessary excavation, earth work, refilling etc complete all as specfied and directed. |
| 194 | Notes for item Nos. 122 and 123:(i) Quoted rate is deemed to include necessary earth work and excavation and also all materials which are incorporating in RCC foundation, \"J\" bolts, nuts , washers etcas per drawing designed by manufracturer and standardsfor mounting light fittings on pole(ii) Writing letters for pole No. with black paint using stencil of 8 cm height complete. |
| 195 | Supply, installation, testing and commissionng of 16 metre high mast shaft in two sections suitable for 50 metre/ sec wind speed, with head frame winch mounting arm/ bracket, luminaries carriage suitable to install 10 Nos. luminaires in symmetrical arrangement, supply of raising lowering system comprising double drum winch/ pulley assembly, 6 mm diameter SS wire rope, trailing cable, connector, integral power tool motor, manual handle, juncton box, lightening finial, 3 mm section thickness, top dia 150 mm, bottom dia 360 mm including single dome aviation obstruction LED light with electrical connections, 32 Amps standard feeder pillar panel and necessary fittings and RCC foundation work as specified/ as per height by OEM complete all as specified and directed. Notes:- (i) Quoted rate shall be inclusive of all materials which are required for incorporating in RCC foundation as per drawing designed by manufracturer) (ii) LED flood light luminaire shall be measured and paid seperately. |
| 196 | Supply and fix LED flood light luminaire suitable for highmast of capacity 200 Watts, 230 Volts, AC outdoor type, energy saving, new generation, environmental friendly, long life, versatile, high performance with pressure die-cast housing, toughened glass, IP 66 protection and individual LEDs with secondary lens optics with IP66 ingress protection, 4 kV in-built and 10 kV external surge protection device, efficiency 120 lm/W with pre wired, warranty option of 5 years from date of installation and necessary provision of fixing arrangements with MS clamp, bolts and nuts and electrical connection upto fitting terminal complete all as specified and directed . |
| 197 | Supply and fix LED flood light luminaire of capacity 120 Watts, 230 Volts, AC outdoor type, energy saving, new generation, environmental friendly, long life, versatile, high performance with pressure die-cast housing, toughened glass, IP 66 protection and individual LEDs with secondary lens optics with IP66 ingress protection, 4 kV in-built and 10 kV external surge protection device, efficiency 120 lm/W with pre wired,warranty option of 5 years from date of installation and necessary provision of fixing arrangements with MS clamp, bolts and nuts and electrical connection upto fitting teriminal complete all as specified and directed . |
| 198 | Supply and fix LED flood light luminaire of capacity 80 Watts, 230 Volts, AC outdoor type, energy saving, new generation, environmental friendly, long life, versatile, high performance with pressure die-cast housing, toughened glass, IP 66 protection and individual LEDs with secondary lens optics with IP66 ingress protection, 4 kV in-built and 10 kV external surge protection device, efficiency 120 lm/W with pre wired,warranty option of 5 years from date of installation and necessary provision of fixing arrangements with MS clamp, bolts and nuts and electrical connection upto fitting teriminal complete all as specified and directed . |
| 199 | Supply and fix LED security light fitting luminaire of capacity 90 Watts, with high power LEDs as light source and electronic driver, energy saving, new generation, environmental friendly, long life, versatile, pressure die-cast aluminium IP 66 protection, 4kV inbuilt and 10kV external surge protecton, efficiency 120 lm/W with pre wired with top opening driver cover for easy maintenance with warranty option of 5 years from date of installation with pre wired and necessary mounting arrangements and provision of 4 sqmm three core copper conductor cable multi stranded from fitting terminal to street junction box complete all as specified and directed. |
| 200 | Supply and fix LED security light fitting luminaire of capacity 60 Watts, with high power LEDs as light source and electronic driver, energy saving, new generation, environmental friendly, long life, versatile, pressure die-cast aluminium IP 66 protection, 4kV inbuilt and 10kV external surge protecton, efficiency 120 lm/Wwith top opening driver cover for easy maintenance with warranty option of 5 years from date of installation with pre wired and necessary mounting arrangements and provision of 4 sqmm three core copper conductor cable multi stranded from fitting terminal to street junction box complete all as specified and directed. |
| 201 | S & F for LED post top lantern 20 watt light fitting made of cast aluminium spigot housing with decarative opal acrylic diffuser with IP 65 protectionand electronic driver with warranty option of 5 years from date of installation complete with all accessories fixed on GI pipe 50 mm dia including provision of4 sq mm three core copper conductor cable multi stranded from fitting terminal to street junction box complete all as specified and directed. |
| 202 | Supply and fix factory made automatic street light control panel made out of 3.15 mm thick CRCA sheet of suitable size, epoxy powder coated as per IS-8623 dust, weather and vermin proof protection class IP-54 with and including all accessories such as astronomical control switch, 3 pole power contactor, automatic control relay, pre-wired etc. fixed on fabricated angle iron channel of suitable size and grouting on floor complete all as specified and as directed and comprising the following:-(i) MCB TPN 63 Amps 10KA, 240 volt - 02 Nos ( 01 for incoming & 01 for outgoing)(ii) Power Contractor 63 Amps, 3 Pole 415 volts- 01 No(iii) Astronomical function time switch (suitable for Deesa, Gujarat area) - 01 No |
| 203 | FIRE FIGHTING SYSTEM |
| 204 | Supply, laying, jointing and testing of ductile iron (DI) pressure pipes, 150 mm nominal dia with spigot and socket ends, centrifugally cast, class K-9, with cement mortar lining in inner side as per IS:8329: 2000 (latest revision) and other relevant standards, with metallic zinc coating followed by a finishing layer of epoxy paint in outer side, suitable for push on joint (rubber gasket joint) including rubber gasket in any length with inside cement mortar lining laid in trenches/ over masonry pillar complete all as specified and directed. |
| 205 | Supply, laying, jointing and testing of ductile iron (DI) pressure pipes, 100 mm nominal dia with spigot and socket ends, centrifugally cast, class K-9, with cement mortar lining in inner side as per IS:8329: 2000 (latest revision) and other relevant standards, with metallic zinc coating followed by a finishing layer of epoxy paint in outer side, suitable for push on joint (rubber gasket joint) including rubber gasket in any length with inside cement mortar lining laid in trenches/ over masonry pillar complete all as specified and directed. |
| 206 | Notes for item Nos. 132 and 133: (i) Excavation and earthwork shall be measured and paid separately under relevant items in schedule.(ii) The quoted rate shall also be deemed to include for provision of joints and jointing material for laying pipes. For jointing of pipe fittings or taking branch connection, provision of joints and jointing material shall be measured and paid separately.(iii) Before laying of pipe line, contractor has to submit layout diagram as per level difference and ensure proper alignment of the pipe. |
| 207 | Material and labour for hosebox for hose reel 20 mm dia size of 30 metre length complete with coupling branch pipe and nozzle, using MS sheet 2 mm thick complete all as specified and directed. |
| 208 | Material and labour for hosebox for keeping 2 Nos. hose pipe of length 15 meters each, branch pipe, nozzle, coupling etc., using MS sheet 2 mm thick complete all as specified and directed. |
| 209 | Supply, fabrication, installation and testing of Motor Control LT Panel, factory made, Type Test Assemble (TTA) Panel for working on 3 phase, 4 wire, 415 Volts, AC, 50Hz, cubical, indoor type, weather proof, water proof, dust proof, vermin proof, shock proof protection, made out of 2.0 mm thick CRCA sheet of suitable size to accommodate accessories/ fittings with front and back double door opening/ lockable by the key from both side with IP 65 protection and provision of suitable bus bar chamber and switch gear compartments for MCCB incoming and outgoing feeders etc. with copper extension links of suitable current carrying capacity not less than 1.5 times the rated current carrying capacity of MCCB individual feeder supported on DMC/ Epoxy insulator including provision for termination with incoming and outgoing cables with cable glands. Motor Control LT Panel shall be mounted on 50 x 50 x 6 mm size MS angle iron frame duly painted with two coats of black bituminous paint over a coat of red oxide primer including PCC foundation of suitable size with PCC 1:2:4 type B1(using 20 mm graded stone aggregate) complete all as specified and directed and including the following accessories:-. |
| 210 | Note:-(i)Rate of earthwork and PCC work etc are deemed to be inclusive in this item.(ii)Design of LT Panel including components, layout, their design as per IEC-61439 duly certified by ASTA or other approved agency.(iii)OEM design & GA drawingshall be submitted to GE for approval before start the manufacture(iv) Requisite tests required as per IEC-61439 guidelines to be conducted and report shall be submitted by OEM to Garrison Engineer. Further Factory inspection for routine inspection/ testing shall be carried out by Rep of accepting officer along with Rep of OEM before dispatch from factory. Testing charges shall be included in the quoted rates of item.(v) Make of Factory made TTA Panel shall be limited to : ABB/ SIEMENS/ SCHNEIDER/ L&T/ C&S/ LEGRAND INFRASTRUCTURE and also their approved Channel Partner/ Authorized Partner/ Licensee Partner, which are also Approved by MESand further the following:-(a) The name of proposed channel Partner with necessary certificate from OEM which the TTA Panels shall be first got approved from Accepting Officer.(b) The invoice of LT Panel/ components of LT Panel (Switch gears & protection material) shall be from original manufacturer only & not from the channel Partner |
| 211 | INCOMING:- (a) Copper strip busbar of 320 Amps rated capacity wrapped with PVC sleeves with maintaining the colour code and provision of making holes with copper nuts, bolts and washers for cable connections including hydrographic insulators with nuts and bolts at both ends - 04 Nos.(b) On load change over switch TPN of capacity 160 Amps - 01 No.(c) 4 Pole MCCB ,160 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links - 01 No.(d) LED Neon indicator lamp (RYB) with holder and fuse holder 230/250 volts, AC - 01 set (set of three)(e) Digital multifunctional meter, flush mounting type with CTs and selector switch - 01 set. |
| 212 | OUTGOING:- (a) 4 Pole MCB 16 Amps 10 KA breaking capacity \"C\" curve - 01 No.(b) 3 Pole MCCB 63 Amps with rotary handle, adjustable thermal magnetic release type, 4 pole, 415 Volts, Ics = 100% Icu, 35 KA breaking capacity including all fixing accessories with both ends spreader links - 04 Nos.(c) Automatic star-delta starter (soft starter type) with suitable relay range conforming to IS -1347(Part IV) suitable for discharge capacity 2280 LPM (137.0 Cum/Hr) at 70 metre head, 80.0 HP, including overload relay, auto timer and single phase preventer suitable range of digital ammemeter with selector switch, voltmeter with selector, indicating lamps (LED) and bakelite fuse showing RYB phase etc. complete - 01 No. (Fire Pump) (d) DOL starter with suitable relay range conforming to IS -1347 (Part IV) suitable for discharge capacity 180 LPM, 11.80 Cumt/Hr at 70 metre head, 4.50 KW/ 6.0 HP, including overload relay and single phase preventer suitable range of digital ammemeter with selector switch, voltmeter with selector, indicating lamps (LED) and bakelite fuse showing RYB phase etc. complete - 01 No. (Jockey Pump) |
| 213 | Supply and fix 4 kg capacity dry chemical powder (ABC) type fire extinguisher, conforming to IS 15683:2006, with initial filling in brand new cylinder with powder coated finish, fitted in gunmetal union, high pressure CO2 gas cartridge, discharge hose, wall mounting bracket/ floor trolley mounting accessories along with suitable signage, etc. complete all as specified and directed. (1 No. at entry/ exit of each floor) |
| 214 | Supply and fix 9 kg capacity dry chemical powder (ABC) type fire extinguisher, conforming to IS 15683:2006, with initial filling in brand new cylinder with powder coated finish, fitted in gunmetal union, high pressure CO2 gas cartridge, discharge hose, wall mounting bracket/ floor trolley mounting accessories along with suitable signage, etc. complete all as specified and directed. (1 No. at entry/ exit of each floor) |
| 215 | Supply and fix 3 kg light-weight squeeze grip CO2 type fire extinguisher, conforming to IS 15683: 2006, with CO2 gas filled in brand new seamless cylinder with powder coated finish, made out of Manganese steel with wheel type valve, discharge nozzle, bend and horn, wall mounting bracket/ floor trolley mounting accessories along with suitable signage complete all as specified and directed. (2 Nos. at entry/ exit of each floor and 1 No. in lift machine room)Notes: (i) Operating pressure: 10 to 15 bars(ii) Operating temperature : -300C to + 550C(iii) Performance criteria: Discharge time not less than 45 sec, throw not less than 4 meters(iv) Hydro test and burst pressure test : Shall pass hydro test pressure of 35 bars 2.5 minutes and withstand a burst pressure of 55 bar |
| 216 | Supply and fix 9 litre mechanical foam type fire extinguisher, conforming to IS 15683: 2006, with initial filling in brand new cylinder with powder coated finish, fitted with gunmetal union, high pressure CO2 gas cartridge, hose and ABS type branch pipe and wall mounting bracket/ floor trolley mounting accessories along with suitable signage complete all as specified and directed. (In parking area)Notes: (i) Test Pressure: 250 kgf/ sqcm(ii) Operating temperature : -300C to + 550C(iii) Locking pin and wire seal should be provided to indicate that the extinguisher has not been used.(iv) Every Extinguisher should be supplied with an operating manual. |
| 217 | Supply and fix galvanised iron fire bucket (filled with dry sand) conforming to IS 2546: 1974 round bottom type enamel painted, white inside and red outside and letters \"FIRE\" in black outside and handle with mounting bracket complete as specified and directed. |
| 218 | Supply, fixing, testing and commissioning of single headed, ISI marked, hydrant valve as per IS: 908 with 80 mm dia flanged inlet and 63 mm dia female outlet complete with gun metal cap etc. complete all as specified and as directed. |
| 219 | SCADA SYSTEM FOR WATER SUPPLY |
| 220 | Supply, installation, testing and commissioning of Gateway for RTU Power Supply 24VDC, 5A, MCB, 2 Pole, DC, MCB, 125 A, 65 V, Power Mechanism: battery- based or power supply based networking: Cellular (2G/4G) RF range – 400m – 1000m (for LoRa based RTU) complete all as specified and directed with the following specifications:(i) Body Type: IP67/ IP68 Certifications: CE / FCC / CISPER Communication Protocol: Secured transmission of telemetry via MQTT / AMQP / HTTPS using TLS/ DTLS/ AES standard(ii) Data Transmission: 15 min data transmission for power-supply based RTU / 2-times a day for battery powered RTUs IoT based Edge Gateway Features: 32 MHz Ref Clock: TCXO(iii) Frequency Band: ISM Tx Out Power: 5 - 22 dBm (Based on Power input) Output: Wi-Fi, Ethernet and GSM(iv) Antenna: 5dB to 22 dB, Hardware support for precise timestamping, Hardware-accelerated Data Encryption Standard (DES), 3DES, Advanced Encryption Standard (AES) 128, AES 192, and AES 256 Protective Casing: IP 68(v) Power Mechanism: Power supply or solar (with batteries) Certifications:CE / FCC / CISPER(vi) Networking: RF (e.g., LoRa) / Wi-Fi / or other networking technologies (eg., Sigfox, Zigbee) for connecting with nodes; Cellular (GSM/GPRS, 4G/LTE, 5G, NB-IoT) or Wi-Fi / Ethernet for connecting to cloud/ server(vii) Communication Protocol: Secured transmission of telemetry via MQTT / AMQP / HTTPS using TLS/DTLS/AES standards(viii) Data transmission: 15 min or continuous data transmission for power-supply based RTU / 4-hour data transmission for solar powered RTUs |
| 221 | Supply, installation, testing and commissioning of RTU for Bulk Flow Electro magnetic meter IoT based Control Unit: 32 MHz Ref Clock: TCXO Frequency Band: ISM complete all as specified and directed with the following specifications:(i) Tx Out Power: 5 - 22 dBm (Based on Power input) Output: Wi-Fi, Ethernet, and GSM(ii) Antenna: 5dB to 22 dBm(iii) Hardware support for precise timestamping, Hardware-accelerated Data Encryption Standard (DES), 3DES, Advanced Encryption, Standard (AES) 128, AES 192 and AES 256 Protective Casing: IP 68(iv) Power Mechanism: Power supply or solar (with batteries) Certifications: CE / FCC / CISPER(v) Networking: RF (e.g., LoRa) / Wi-Fi / or other networking technologies (e.g., Sigfox, Zigbee) for connecting with nodes; Cellular (GSM/GPRS, 4G/LTE, 5G, NB-IoT) or Wi-Fi / Ethernet for connecting to cloud/ server |
| 222 | Supply, installation, testing and commissioning of RTU for Water Level Sensor IoT based Control Unit: 32 MHz Ref Clock: TCXO Frequency Band: ISM complete all as specified and directed with the following specifications:(i) Tx Out Power: 5 - 22 dBm (Based on Power input) Output: Wi-Fi, Ethernet, and GSM(ii) Antenna: 5dB to 22 dBm(iii) Hardware support for precise timestamping, Hardware-accelerated Data Encryption Standard (DES), 3DES, Advanced Encryption, Standard (AES) 128, AES 192, and AES 256 Protective Casing: IP 68(iv) Power Mechanism: Power supply or solar (with batteries) Certifications: CE / FCC / CISPER(v) Networking: RF (e.g., LoRa) / Wi-Fi / or other networking technologies (e.g., Sigfox, Zigbee) for connecting with nodes; Cellular (GSM/GPRS, 4G/LTE, 5G, NB-IoT) or Wi-Fi / Ethernet for connecting to cloud/ server |
| 223 | Supply, installation, testing and commissioning of RTU for Pressure sensor IoT based Control Unit : 32 MHz Ref Clock: TCXO Frequency Band: ISM complete all as specified and directed with the following specifications:(i) Tx Out Power: 5 - 22 dBm (Based on Power input) Output: Wi-Fi, Ethernet, and GSM(ii) Antenna: 5dB to 22 dBm(iii) Hardware support for precise timestamping, Hardware-accelerated Data Encryption Standard (DES), 3DES, Advanced Encryption,Standard (AES) 128, AES 192, and AES 256 Protective Casing: IP 68(iv) Power Mechanism: Power supply or solar (with batteries) Certifications: CE / FCC / CISPER(v) Networking:RF (e.g., LoRa) / Wi-Fi / or other networking technologies (e.g., Sigfox, Zigbee) for connecting with nodes; Cellular (GSM/GPRS, 4G/LTE, 5G, NB-IoT) or Wi-Fi / Ethernet for connecting to cloud/ server |
| 224 | Supply, installation, testing and commissioning of Centralised web and mobile monitoring including wifi, LAN, WAN for flow, level, pressure and RTU\"s complete all as specified and directed with the following specifications:(i) Application for Monitoring the Sensor based Data(ii) The Solution provider shall ensure functioning of all deployed components smoothly and collaboratively to run 24*7 basis. Platform would serve as the focal point to serve as a decision support engine for administrators in day to day operations as well as during exigency situations(iii) Onprim platform(iv) Cloud base Infrastrucutre to be provided by solutions provider(v) Should have Data integration platform (vi) GIS capabilities of the Platform and Ability to plot various field devices on GIS maps with different layers(vii) Should have built in capability to integrate and automatically trigger notifications to users (Email). The required Gateway of EMAIL will be procured by the bidder which will be paid extra as per actuals. The users shall have flexibility to add and modify the conditions to trigger the notifications(viii) Should have mechanisms for Alerts, Notifications generated by other systems and IoT devices. This will improve the efficiency of the water supply scheme (manpower, electricity, water consumption) by supporting the utility and its human resources. The alerts from different IoT can be Water level in source, alert related related to the quantity of water supplied, water quality, Non-Revenue water |
| 225 | (ix) Should have options to visualize geo-spatial, operational and metrics data like Maps, Graphs, KPI, Tables, etc.(x) Should provide an ability to create KPI’s, Graphs and Maps from different sources of the data Should have Data and Analytics engine (xi) Should have API repository to integrate with different systems(xii) Integrate IoT devices in to the platform (xiii)System shall generate Notification, Alert and Alarm messages that shall be visible within the Dashboard/GIS Platform and the Officer Mobile App if required(xiv) The Analytics Engine shall support multiple Data Sources. Min below standard data sources shall be supported – CSV, TSV, MS Excel , NOSQL, RDBMS (xv) Capability for Integration with enterprise |
| 226 | Supply, installation, testing and commissioning of Pump control unit IoT based Pump Control Unit: 32 MHz Ref Clock: TCXO; Frequency Band: ISM complete all as specified and directed with the following specifications:(i) Tx Out Power: 5 - 22 dBm (Based on Power input) Output: Wi-Fi, Ethernet, and GSM Antenna: 5dB to 22 dBm(ii) Hardware support for precise timestamping, Hardware-accelerated Data Encryption Standard (DES), 3DES, Advanced Encryption Standard (AES) 128, AES 192, and AES 256 Protective Casing: IP 68(iii) Power Mechanism: Power supply or solar (with batteries) Certifications: CE / FCC / CISPER(iv) Networking: RF (e.g., LoRa) / Wi-Fi / or other networking technologies (eg. Sigfox, Zigbee) for connecting with nodes; Cellular (GSM/GPRS, 4G/LTE, 5G, NB-IoT) or Wi-Fi / Ethernet for connecting to cloud/ server(v) This will indicate the value of ampere, voltage, energy consumed by the pump assembly meant for supplying water to the village. Any variation beyond the prescribed limit is to be immediately analyzed and addressed to avoid any breakdown of the pumping machinery which may result in disruption of water supply. |
| 227 | Travelling and Logging |
| 228 | Panel protection of RTU + Gateway + Sensor |
| 229 | Electrical and Plumbing |
| 230 | 1 year IOT base data 2G, 4G network sim plan |
| 231 | Installation + Commisioning |
| 232 | 4 core Cabling + wiring |
| 233 | Diplay Unit:32 inch display unit to showcase web information system |
| 234 | Supply, installation, testing and commissioning of Electro Magnetic Flow meter sensor with one year warranty, IoT based Mechanical Flow Meter water quantity and flow measurement with paddel wheel and remote communication to cloud (server) using separate RTU Accuracy +/-2% or better over typical operating range and temperatures, minimum Class B Multi-jet Operating Conditions, Temperature -20 to 60°C / Humidity 5 to 95% non-condensing; Working pressure shall be 6/ 10/ 16 bar as per local requirement, Output Pulse output / m-Bus, Body Type Water Meter: Ip68, Communication Module: IP67 (should support field replacement of batteries if attached with flowmeter), Calibration and Testing, Calibration certification required at the time of supply (e.g., FCRI) Certifications ISO 4064 B / IS: 779:1994 / MID (Directive 2004/22/EC) / OIML R 49 Ancillaries : Enclosures etc. complete all as specified and directed. |
| 235 | Supply, installation, testing and commissioning of IoT based Water Level Sensors, Principle of measurement, Hydrostatic Accuracy ±0.25%, Output Analog output: 4 - 20 mA/ RS485 (Modbus RTU) Protection Clause:IP-68 or Better Pressure Range :0-10 Bar, Operating temperature: 5 Deg C to 60 Deg C, Certifications: CE / ISO / MID / ECEN complete all as specified and directed. |
| 236 | Supply, installation, testing and commissioning of IoT based Pressure Sensor along with Performance certificate, with features like Pressure transmitter Output: Analog output: 4 - 20 mA Digital outputs: RS485 (Modbus RTU); Body type: Rated IP67 or better for protection from most harsh environments; Accuracy: Pressure range of 0.1 bar to 10 bar; Total Error Band (TEB) as low as 2 %FSS Compensated and operating temperature range of 10°C to 50°C, Less than 2 ms response time.+/- 0.25 % of full scale or better complete all as specified and directed. |
| 237 | Supply, installation, testing and commissioning of Ph IoT based Water Quality Sensors (PH) along with Performance and Test Certificates from International or National Authorized/ Notified Agency with Features: Principle: Reagent Free, No Waste-stream Amperometric Chlorine Analyzer; Response time: < 2mins (Electrode: Copper, Platinum, Gold) Output: Analog output: 4 - 20 mA Digital outputs: RS485 (Modbus RTU); Body type: Probe: IP68, PVC; Shell material - ABS thermoplastic polymer; Accuracy: Accuracy ±5%, Resolution: 0.05 mg/L; Measuring range: 0 to 10.0 mg/l complete all as specified and directed. |
| 238 | Supply, installation, testing and commissioning of TDS IoT based Water Quality Sensors (TDS)along with Performance and Test Certificates from International or National Authorized/ Notified Agency with Features: Principle: Reagent Free, No Waste-stream Amperometric Chlorine Analyzer; Response time: < 2mins (Electrode: Copper, Platinum, Gold) Output: Analog output: 4 - 20 mA; Digital outputs: RS485 (Modbus RTU); Body type: Probe: IP68, PVC; Shell material - ABS thermoplastic polymer; Accuracy: Accuracy ±5%, Resolution: 0.05 mg/L; Measuring range: 0 to 10.0 mg/l complete all as specified and directed. |
| 239 | SCADA SYSTEM FOR ELECTRIC SUPPLY |
| 240 | Supply, Installation, Testing, Commissioning and Programming of Master Control Station (SCADA Software). The scope shall include services for programming, configuration and customisation of the Smart Station Platform with respect to the Power Supply Module as per actual site conditions and requirement of the engineer complete all as specified and directed with the following specifications and components:(a) Landing Page to depict criritcal paramters viz.- Supply Voltage, Current / Load on Each Feeder, Power Factor, Frequency, Fault Indication due to Earth Fault / Short Circuit, KW, KWH, KVAH, KVARH, RUNHR, ONHR, Interupts, Phase Angle THD, Neutral Current, Max Demand, Operating Temperature and Oil Levels of Transformers etc.(b) Creation of drop down tabs to monitor the all Substations and Remote RTU Panel systems individually.(c) Creation of individual RTU Panel wise schematics and layouts for the Power Distribution system as per the actual site including display of all relevant parameters viz. - Supply Voltage, Current / Load on Each Feeder, Power Factor, Frequency, Fault Indication due to Earth Fault / Short Circuit, KW, KWH, KVAH, KVARH, RUNHR, ONHR, Interupts, Phase Angle THD, Neutral Current, Max Demand, Operating Temperature and Oil Levels of Transformers etc. |
| 241 | (d) Creation of Day wise Reports for:-(i) Consumption Patterns - Daily, Weekly, Monthly and Annually.(ii) Load Distribution Patterns on Feeders and Transformers.(iii) Efficiency of Transformers.(iv) Load balancing status etc. and submitting hard copies of Weekly Records and Parameters mentioned in above to Engr-in-Charge.(e) Personal Computer as central Server for development version of the scada software and reporting the software with following specifiaction:- Intel 8th Gen Core I5, 8 GB RAM, 1 TB HDD, Keyboard / Mouse, 21 inches LED monitor.(f) 600VA UPS including batteries for 1/2 Hr backup (g) A4 Size Monochrome Laser Printer. |
| 242 | Supply, Installation, Testing, Commissioning and Programming of Reporting Software with unlimited no. of user configurable reports along with selection of time period, parameters, events, alarms complete with user defined Logo user name, date and time, page no., header and footer complete all as specified and directed. |
| 243 | Supply, Installation, Testing and Commissioning of Outdoor type, having Canopy and Double Door for weather protection, Floor Mounted RTU (Remote Terminal Unit) based Automation, Protection Panel with wireless Radio Frequency based communication. The panel should be of minimum size 1000(H) X 950(W) X 300(D) mm fabricated from 3.15 mm CRCA Sheet. Control Panel should be suitable for Remote Monitoring and Controlling of one No. 5 Way RMU (Ring Main Unit) (Location:- Substation) complete all as specified and directed. The Panel shall comprise of the following items:-(a) Circuit Breaker (ON & OFF status)(b) Trip Circuit Healthy(c) Spring charged(d) Auto Tripped(e) R,Y, B - indications(f) Service Position & Test Position(g) Digital value of current for all three phases for all Modules(h) Digital value of voltage from the PT (wherever PT exists) |
| 244 | The scope of work shall include providing and installing additional hardware/ accessories in each RMU as per site requirement. The RTU based panel shall consist of the following sub systems:-(i) 05 nos. Multi Function Energy meters with LED Display having CI 1 & inbult RS 485 communication port. (Note Multi function Energy meters to be taken wherever PT are available)Parameters to be taken:- V, A, F, PF, KW, KWH, RUNHR, Interupts, Phase Angle THD, Neutral Current, Max Demand. (ii) 01 No. RTU with follwing specifications (a) Processor Industrial grade, Communication protocols IEC 61850 & Modbus.(b) Ports 1xRJ45, 1xRS485, 1xRS232, Operating Voltage: -24VDC, Protocols:- IPsec, SNTP, SFTP.(c) Non isolated RS 485 communication port or Ethernet communication port.(d) Suitable No. of digital / analog input and outputs.(e) Programming Software based on IEC to facilitate building of custom build function blocks.(f) Protocol : Master/Slave Modbus, Expandable upto 248 I/O’s and 7 expansion module |
| 245 | (iii) 01 No. HMI - 7\" Graphical Touch screen display(a) 01 nos. RS 485 and 01 no. USB port(b) Serial multilink, USB downloading port(c) Support external data storage on a USB memory stick for storing production data and backing up applications(iv) 01 No. SMPS of 6.5A rating as suitable according to panel design.(v) Suitable No. of interposing relays of 220VAC & 24 VDC coil rating and 6 A contact rating. (vi) Suitable No. of relay cards with operating voltage 24VDC, with continuous current of 5A. Card must be of 8 channel & having 8 relays. (vii) MCB rating 32A, 10A, 6A rating as suitable according to panel design. (viii) Illuminiated push button & indicator lamp rating as suitable according to panel design. (ix) Selector switches, Audio visual alarm indicator rating as suitable according to panel design. |
| 246 | Supply, Installation, Testing and Commissioning of Outdoor type, having Canopy and Double Door for weather protection, Floor Mounted RTU (Remote Terminal Unit) based Automation, Protection Panel with wireless Radio Frequency based communication. The panel should be of minimum size 1200 (H) X 1000 (W) X 300 (D) mm fabricated from 3.15 mm CRCA Sheet. Control Panel should be suitable for Remote Monitoring and Controlling of 02 Nos. Incoming VCB & 07 Nos. Outgoing VCB (Location:- Main MRS Substation) complete all as specified and directed. The Panel shall comprise of the following items:-(a) Circuit Breaker (ON & OFF status)(b) Trip Circuit Healthy(c) Spring charged(d) Auto Tripped(e) R,Y, B - indications(f) Service Position & Test Position(g) Digital value of current for all three phases for all Modules(h) Digital value of voltage from the PT (wherever PT exists) |
| 247 | The scope of work shall include providing and installing Additional hardware / accessories in each RMU as per site requirement.The RTU based Panel shall consist of the follwing sub systems:-(i) 10 nos. Multi Function Energy meters with LED Display having CI 1 & inbult RS 485 communication port. (Note Multi function Energy meters to be taken wherever PT are available)Parameters to be taken:- V, A, F, PF, KW, KWH, RUNHR, Interupts, Phase Angle THD, Neutral Current, Max Demand. (ii) 01 No. RTU with following specifications:- (a) Processor Industrial grade, Communication protocols IEC 61850 & Modbus.(b) Ports 1x RJ45, 1 x RS485, 1xRS232, Operating Voltage: -24 Volts DC, Protocols:- IPsec, SNTP, SFTP.(c) Non isolated RS 485 communication port or Ethernet communication port.(d) Suitable No. of digital / analog input and outputs.(e) Programming Software based on IEC to facilitate building of custom build function blocks.(g) Protocol : Master/Slave Modbus, Expandable upto 248 I/O’s and 7 expansion module |
| 248 | (iii) 01 No. HMI - 7\" Graphical Touch screen display (a) 01 nos. RS 485 and 01 no. USB port(b) Serial multilink, USB downloading port(c) Support external data storage on a USB memory stick for storing production data and backing up applications(iv) 01 No. SMPS of 6.5A rating as suitable according to panel design. (v) Suitable No. of interposing relays of 220VAC & 24 VDC coil rating and 6 A contact rating. (vi) Suitable No. of relay cards with operating voltage 24VDC, with continuous current of 5A. Card must be of 8 channel & having 8 relays.(vii) MCB rating 32A, 10A, 6A rating as suitable according to panel design. (viii) Illuminiated push button & indicator lamp rating as suitable according to panel design.(ix) Selector switches, Audio visual alarm indicator rating as suitable according to panel design. |
| 249 | Supply, Installation, Testing and Commissioning 2 KVA UPS / INVERTER with Sealed Lead Acid Maintenanace free Batteries for powering the panel for a minimum of 30 minutes in case of supply failure complete all as specified and directed. UPS should have following features:- Charger:- Build in solit state stage recharge; Display:- LED Display; Audible Alarm:- Main Failure Alarm, Battery Low Alarm, UPS Warning, Fault. |
| 250 | Supply, Installation, Testing and Commissioning of 5 A Current Transformers suitable for the exsiting Load on the LT feeder pillar Panel complete all as specified and directed. |
| 251 | Supply, Installation, Testing, Commissioning and Programming of Omni or Bi-Directional Parabolic antenna with control station to generate strong directional effect with WLAN network support having mast mounting arrangement complete all as specified and directed. Control station shall operate on license free frequency with necessary hardware at a suitable location to be connected to the central SCADA server so as to establish connectivity with every station of the network after conducting a frequency survey of the entire area of interest and identify suitable locations to mount the station hardware and the height of the antennas to establish clear line of sight either directly or by multi hop so as to be able to send data. Antenna type:- Omni and Bi Directional Parabolic antenna Degree of protection:- IP65; Mounting type:- Mast mounting, It should have a approval of Wi-Fi compliance, Environmentally Friendly; Use Period :- UNLIMITED = EFUP-e Note:- Rate quoted is deemed to be inclusive of making arrangemets of accessories such as mounting bracket and mast clips. |
| 252 | Supply and fix 6 core 1.5 sqmm PVC sheathed and PVC insulated copper armoured cable complete all as specified and directed. |
| 253 | Supply and fix 4 core 1.5 sqmm PVC sheathed and PVC insulated copper armoured cable complete all as specified and directed. |
| 254 | Supply and fix 2 core 1.5 sqmm PVC sheathed and PVC insulated copper armoured cable complete all as specified and directed. |
| 255 | Supply, Installation, Testing and Commissioning of 4 pair CAT 6 UTP armoured cable for communication complete all as specified and directed. |
| 256 | Supply, laying, jointing and testing of armoured optical fibre underground cable, 12 core (fiber) along with light interfacing unit laid in trenches/ ducts/ fixed on poles/ walls, laid under/ path or encased in HDPE pipe complete all as specified and directed. Note: (i) The cost of joints/splicing material is deemed to be included in the quoted rate.(ii) HDPE pipe shall be measured and paid separately under respective item of Sch \"A\" Part-VII (EXTERNAL ELECTRIFICATION AND SCADA SYSTEM). |
| 257 | Material and labour for splicing work of optical fibre cable of 6/ 12 core for end connection at fibre optic distribution box complete all as specified and directed. |
| 258 | Supply and fix patch cords having any type of connectors (SC/LC/ST/FC) at both ends as per site requirement complete all as specified and directed. |
| 259 | Supply and fix OFC 12 LIU port complete all as specified and directed. |