Tender For Construction Of 2×10 Mva Capacity 33/11 Kv Substation In Sector-7 Of Greater Bareilly Housing Scheme And Construction Of 33 Kv Independent Feeder From Balipur 132/33 Kv Substation. - 33/11 KV SUBSTION WORKS33KV INCOMER VCB PANEL : Supply, Installing, Tesing and Commissioning of INDOOR TYP 33KV, HT VCB Panel Board having 2 Nos. Incomers, 1 No. Bus- coupler and 2 Nos. Outgoing Vacuum Circuit Breakers with Motorized cum manual spring charging mechanism rated for 33KV, 1250Amp, 26.3kA/3s, with IAC 26.3kA/1sec panel with SCADA compatibility Floor rolling type, Horizontal Isolation & Horizontal Draw-out type design confirming to IS 13118, IEC 62271-100, Mechanical Endurance of M2 class ensuring 10000 operating sequences and E2 class Electrical Endurance. The VCB Panel Board comprising Aluminum Bus - Bar of 1250Amp, Earthing Truck of suitable making capacity along with safety interlocking for complete board and control voltage of 24V DC. The Board shall consist of following panels :1.1 33KV, 1250Amp, 26.3KA /3s with IAC AFLR 26.3kA/1sec panel with SCADA compatibility, Horizontal Isolation & Horizontal Draw- out type as per IS 13118, IEC 62271-200, IEC 62271-1:2017. Vacuum Circuit Breaker should have 3 Nos. fully encapsulated poles housing Vacuum Interrupters. The Vacuum Interrupter, Circuit breaker, Numerical relay and switchgear panel shall be of same make.1.2 Motorized spring charging mechanism (230V AC) with integral spring charging handle for manual spring charging associated Shunt Type Trip & Close Coils (24V DC). The viewing window glass shall be of same strength of the circuit breaker door and similar material, composition and thickness shall be used as done during the IAC type test. Busbar shall be self supported type without any support insulators.1.3 Current Transformers : 1 set of 3 Nos. Single Phase, 33KV,800/400/5+5A, Core 1 : Class 5P10, 7.5VA and Core 2 : Class 0.5, 7.5VA.1.4 Potential Transformers : 1 set of 3 Nos. Single Phase Fixed Type PTs having ratio 33KV/rt3/110V/rt3, Class 0.5/3P, 50VA along with associated HRC Fuses for Primary side protection.1.5 Accessories : TNC Switch, Panel Space Heater, Push Button Trip Circuit Healthy Check, Panel illumination lamp with switch, 3 Pin Plug with Socket of 15Amp., Local & Remote Switch, Emergency Trip Button, AC & DC control circuit through MCB, Auxiliary Contacts (6 NO + 6 NC), Anti Pumping Device.1.6 Indications : LED Type Indications for R - Y - B Phase, Breaker On/OFF, Spring Charged, Trip Circuit Healthy, Breaker Trip, Breaker Test / Service Position, AC & DC Healthy.1.7 Metering Instruments : 1 No. Tri-vector Meter (Acc. Cl. 0.5) of L&T/Secure make , 1 No. Digital Voltmeter (Acc. Cl. 0.5) of Rishabh, Secure & Elmeasure make, 1 No. Digital Ammeter (Acc. Cl. 0.5) of Rishabh, Secure & Elmeasure make.1.8 Protection & Auxiliary Relays : The IED (Numerical relay) shall be Complied to 61850 protocol without any external protocol converter.GOOSE signals shall be freely configurable.WEB HMI feature should be present.Inter- operability test shall preferably shall be done.Proof w.r.t Interoperability shall be submitted by the Manufacturer. The relay must support IEC 61850 Edition 1 and Edition 2(with test reports) and shall support HSR redundancy protocol. It shall comply with international standard of NERC CIP or BREW for cyber security. The Numerical relay shall have integral arc sensors (3 nos.) and shall be able to issue trip command within 10ms of detection of Internal arc inside CB,BB,Cable Compartments of the HT panel.Protections 50, 51, 50N, 51N, 27, 59, 95, 86 - Measurement for 3I,I0,3U,U0,Kw,KVA,Kwh,PF,Hz, 8 DI + 10 DO, One front RJ45Port, One Rear RJ45 Port for IEC-61850 Protocol, Draw Out with CT Shorting feature .1 No. Trip Circuit Supervision RelayAdditional Accessories and Features : Electrical Interlocking between Incomers & Bus-coupler to prevent mixing of supplies.1.9 Standard features should include provision for connecting atleast one run of outgoing cables, Test Terminal Block for protection circuit. Panel fabrication shall preferably be made from sheet steel, safety shutters, continuous rated Close & Trip coils. VCB & Panel should be of same make. Control circuit shall operate on 24V DC except Spring Charging Motor & Space Heater which shall operate on 230V AC. 2 33KV OUTGOING VCB PANEL : Same description as INCOMER PANEL above except following changes :Potential Transformer, Voltmeter, R - Y - B Phase Indication, Under Voltage + Over Voltage Relay are not required in Outgoing Panels2.1 Current Transformers :1 set of 3 Nos. Single Phase, 33KV, 400/200/5+5A PS Class, Core 1 : Class 5P10, 7.5VA, Core 2 : Class 0.5, 7.5VA and Core 3 : PS Class for Transformer Differential Protection (PS Class : Vk > 200V, Imag < 30mA @ Vk/2)2.2 Protection Relays :The IED (Numerical relay) shall be Complied to 61850 protocol without any external protocol converter.GOOSE signals shall be freely configurable.WEB HMI feature should be present.Inter- operability test shall preferably shall be done.Proof w.r.t Interoperability shall be submitted by the Manufacturer. The relay must support IEC 61850 Edition 1 and Edition 2(with test reports) and shall support HSR redundancy protocol. It shall comply with international standard of NERC CIP or BREW for cyber security. The Numerical relay shall have integral arc sensors (3 nos.) and shall be able to issue trip command within 10ms of detection of Internal arc inside CB,BB,Cable Compartments of the HT panel.2.3 Relay 1: Feeder Protection and Control Relay, Protections 50,51,50N,51N,46,49,95,86 or stand alone for 64R, Measurement for 3I, I0, 10 DI + 12 DO, One front RJ45 Port, One Rear RJ45 Port for IEC-61850 Protocol, Drawout Type with CT Shorting feature, Small LCD Display.Relay 2: Transformer Protection and Control Relay, Protections 87T,64R(High Impedance),46,49,95, Measurement for 3I, I0, 8 DI + 10 DO, One front RJ45 Port, One Rear RJ45 Port for IEC-61850 Protocol, Drawout Type with CT Shorting feature, Small LCD DisplayTransformer OTI, WTI & Buchholz - Alram & Trip Protection shall be given through numerical relay1 No. Trip Circuit Supervision RelayAdditional Accessories and Features : 8 Window Annunciator along with Hooter 3 33KV BUS-COUPLER WITH RISER VCB PANEL :Same description as INCOMER PANEL above except following changes :3.1 Current Transformer, Potential Transformer, Tri-vector Meter, Ammeter, Voltmeter, R -Y - B Phase Indication, Protection & Auxiliary Relays Supply, installing, tesing and commissioning of INDOOR TYPE 11KV, HT VCB 1250Amp 26.3kA rms-3sec STC pannel with IAC AFLR 26.3kA for 1 sec with SCADA Campatidility Board having 2 Nos. Incomers, 1 No. Bus-coupler and 7 Nos. Outgoing Vacuum Circuit Breakers with Motorized cum manual spring charging mechanism rated for 11KV, 800Amp, 26.3kA/3 Sec, Floor rolling type, Horizontal Isolation & Horizontal Draw-out type design confirming to IS 13118, IEC 62271-200, Mechanical Endurance of M2 class ensuring 10000 operating sequences and E2 class Electrical Endurance. The VCB Panel Board comprising Aluminum Bus - Bar of 1250Amp, control voltage of 230V AC for spring charging motor and 24V DC for coils. The Board shall consist of following panels : 4 33 KV RMU Panel- 33KV, 630A, 25KA/1Sec, 4-Way, non extensible outdoor IP54, SF6 Gas insulated Ring Main Unit consist of : 3- Nos motor operated Vacuum Circuit Breaker (VCB), and 1- Nos motor operated load break Switch, with Suitable site replaceable bushing and full front door cover as per attached BOM. Make of Vacuum interrupter shall be same as make of RMU (Ann. II) (Configuration: 1 NosLBS, 3 nos VCB) Whose GTPApproved in MVVNL having valid CPRI/ERDA type test report] 5 11KV INCOMER VCB PANEL : Supply, installation testing and commissioning of INDOOR TYPE SCADA compatibility11KV, 800Amp, 26.3KA/3 Sec with IAC AFLR 26.3kA for 1 sec, Floor rolling type, Horizontal Isolation & Horizontal Draw-out type as per IS 13118, IEC 62271-200, IEC 62271-1:2017. Vacuum Circuit Breaker should have 3 Nos. fully encapsulated poles housing Vacuum Interrupters. The Vacuum Interrupter, Circuit breaker, Numerical relay and switchgear panel shall be of same make. Motorized spring charging mechanism (230V AC) with integral spring charging handle for manual spring charging associated Shunt Type Trip & Close Coils (24V DC). The viewing window glass shall be of same strength of the circuit breaker door and similar material, composition and thickness shall be used as done during the IAC type test. Busbar shall be self supported type without any support insulators.5.1 Current Transformers :1 set of 3 Nos. Single Phase, 11KV, 800/400/5+5+PS Class, Core 1 : Class 5P10, 7.5VA, Core 2 : Class 0.5, 7.5VA and Core 3 : PS Class for Transformer Differential Protection (PS Class : Vk > 200V, Imag < 30mA @ Vk/2)5.2 Potential Transformers : 1 set of 3 Nos. Fixed Type Feeder Connected PTs having ratio 11KV/rt3/110V/rt3, Class 0.5/3P, 50VA along with associated HRC Fuses for Primary side protection.5.3 Accessories : TNC Switch, Panel Space Heater, Push Button Trip Circuit Healthy Check, Panel illumination lamp with switch, 3 Pin Plug with Socket of 15Amp., Local & Remote Switch, Emergency Trip Button, AC & DC control circuit through MCB, Auxiliary Contacts (6 NO + 6 NC), Anti Pumping Device.5.4 Indications : LED Type Indications for R - Y - B Phase, Breaker On/OFF, Spring Charged, Trip Circuit Healthy, Breaker Trip, Breaker Test / Service Position, AC & DC Healthy.5.5 Metering Instruments : 1 No. Tri-vector Meter (Acc. Cl. 0.5) of L&T/Secure make , 1 No. Digital Voltmeter (Acc. Cl. 0.5) of Rishabh, Secure & Elmeasure make, 1 No. Digital Ammeter (Acc. Cl. 0.5) of Rishabh, Secure & Elmeasure make.5.6 Protection & Auxiliary Relays :The IED (Numerical relay) shall be Complied to 61850 protocol without any external protocol converter.GOOSE signals shall be freely configurable.WEB HMI feature should be present.Inter- operability test shall preferably shall be done.Proof w.r.t Interoperability shall be submitted by the Manufacturer. The relay must support IEC 61850 Edition 1 and Edition 2(with test reports) and shall support HSR redundancy protocol. It shall comply with international standard of NERC CIP or BREW for cyber security. The Numerical relay shall have integral arc sensors (3 nos.) and shall be able to issue trip command within 10ms of detection of Internal arc inside CB,BB,Cable Compartments of the HT panel.5.7 Relay 1: Feeder Protection and Control Relay, Protections 50,51,50N,51N,46,49,95,86 or stand alone for 64R, Measurement for 3I, I0, 10 DI + 12 DO, One front RJ45 Port, One Rear RJ45 Port for IEC-61850 Protocol, Drawout Type with CT Shorting feature, Small LCD Display. 1 No. Trip Circuit Supervision Relay5.8 Additional Accessories and Features : Electrical Interlocking between Incomers & Bus-coupler to prevent mixing of suppliesStandard features should include provision for connecting atleast one run of outgoing cables, Test Terminal Block for protection circuit. Panel fabrication shall preferably be made from sheet steel, safety shutters, continuous rated Close & Trip coils. VCB & Panel should be of same make. Control circuit shall operate on 24V DC except Spring Charging Motor & Space Heater which shall operate on 230V AC 6 11KV OUTGOING VCB PANEL : Same description as INCOMER PANEL above except following changes :Potential Transformer, Voltmeter, R - Y - B Phase Indication, Under Voltage + Over Voltage Relay are not required in Outgoing PanelsCurrent Transformers : 1 set of 3 Nos. Single Phase, 11KV, 200/100/1+1, Core 1 : Class 5P10, 7.5VA, Core 2 : Class 0.5, 7.5VA. 7 11KV BUS-COUPLER VCB PANEL : Same description as INCOMER PANEL above except following changes :7.1 Current Transformer, Potential Transformer, Tri-vector Meter, Ammeter, Voltmeter, R - Y - B Phase Indication, Protection & Auxiliary Relays 8 33/11 KV TRANSFORMER-Supply, Installation testing commissioning with loading unloading etc.33/11 K.V. Power Transformer 10MVA outdoor onload distribution Transformer, Tapping range +5% to -15% in 8 step of 1.25% each step with H.T./L.T. bushing, OTI, WTI, Buchholz, Marshalling box Having Losses-No load losses : 07KW(max) & Load losses : 50 KW(max)as per Latest Specification of U.P.P.C.L with 120 Month (10Year) Gurrenty/warrenty including construction of civil foundation andfire partition wallhaving height 3 meter between two transformer complete in all respect..[Whose GTPApproved in MVVNL having valid CPRI/ERDA type test report] 9 11/.433 KV,63 KVA Transformer- Supply Installation and Commissioning of 63 KVA, 11/0.433 KV Transformer including loading, unloading, local carriage with all material, labour,and civil foundation work .Whose GTPApproved in MVVNL having valid CPRI/ERDA type test report] 10 Providing necessary T&P and furniture for maintenance staff as per Item Given below:10.1 12 mm thick Rubber mat of size 2x 1 m (4- Nos)10.2 Brass Earth chain(2- Nos)10.3 Rubber hand gloves tested on 1100V.(4 Pair)10.4 Maximum load/ minimum load tripping board complete with all necessary equipments. (1- Nos)10.5 Single line diagram with board complete.(1- Nos)10.6 Notice board.(1- Nos)10.7 Wall clock (4- Nos)10.8 First aid box (1- Nos)10.9 Sign. board of S/S with stand. (1- Nos.)10.10 Key board (1- Nos)10.11 Table with drawer & sunmica(1- Nos)10.12 Armed chair (6- Nos)10.13 Rack (2- Nos)10.14 Bench (2- Nos) 11 Supply and Making fire fighting arrangements in the control room building as per Item Given below:11.1 Cost of Fire extinguisher 4.5 kg capacitycomplete with stand (4- Nos)11.2 Cost of Fire bucket complete (6- Nos)11.3 Cost of Fire bucket stand for 6 Nos. bucket made of M.S. Angle 45x45x6mm. (1- Nos) 12 Control Cable S/Laying of ZHFR control copper cable(4Cx2.5 Sqmm) 13 Control Cable S/Laying of ZHFR control copper cable (6Cx2.5 Sqmm) 14 Supply Installation, Testing & Commissioning of 24V, 20A Trickle cum Boost Battery Charger suitable for 24V 70AH Battery Bank and also to feed 5A Power to External Load such as Emergency Light etc.70AH, 30V Battery Bank SMF batteries with Mounting Rack & along with connecting Leads and other associated accessories. The Charger shall be suitable to operate Emergency Light Load along with 33kV HT VCB Closing / Opening and also 11kV VCB Closing & Opening having 3 years warranty period. 15 S/ Filling of 20mm stone grit in yard100mm thick complete in all respects. 16 Supply and Errection of cable stand of size 3.00x0.50m above G.L. duly grouted with cement concrete upto 50 cm. depth for laying cables made of angle iron size (65x65x6mm) having welded M.S. flat of size 50x6mm on top middle, and 45mm above ground level for fixing cable by clamping with M.S. flat of 40x4mm size as perdirection of E/I. 17 S/Laying of Al. conductor PVC insulated armoured served. sheathed cable 1100V grade at a depth of 75cm below GL over a cushion of 75mm thick sand alround & protected with bricks on side and top.On surface the cable run shall be fixed on M.S clamps of suitable size and crossing the road cable should run through 150mm dia hume pipe and in case of air like catenary it shall be hanged with the help of G.I wire climpped at several places also armouring of cable shall be properly connected with earth conductor/terminal the job include the cost of all material, labour and T & P required for proper completion of the work.(10sqmm 4 core) 18 S/Laying of Al. conductor PVC insulated armoured served. sheathed cable 1100V grade at a depth of 75cm below GL over a cushion of 75mm thick sand alround & protected with bricks on side and top.On surface the cable run shall be fixed on M.S clamps of suitable size and crossing the road cable should run through 150mm dia hume pipe and in case of air like catenary it shall be hanged with the help of G.I wire climpped at several places also armouring of cable shall be properly connected with earth conductor/terminal the job include the cost of all material, labour and T & P required for proper completion of the work. (70 Sqmm 3½core) 19 Supply and fixing of plain or pin type copper tin plated cable socket ( lug ) to the cable leads, insulating with tape and making connection etc. complete in all respect as per direction of the Engineer-Incharge.(10 Sqmm) 20 Supply and fixing of plain or pin type copper tin plated cable socket ( lug ) to the cable leads, insulating with tape and making connection etc. complete in all respect as per direction of the Engineer-Incharge. (25 Sqmm) 21 Supply and fixing of plain or pin type copper tin plated cable socket ( lug ) to the cable leads, insulating with tape and making connection etc. complete in all respect as per direction of the Engineer-Incharge.(70 Sqmm) 22 Supply and fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc.. Complete in all respect. The armouring of the cable shall be properly connected with the earth as per directionof E/I. (10 Sqmm 4 core) 23 Supply and fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc.. Complete in all respect. The armouring of the cable shall be properly connected with the earth as per directionof E/I. (50 Sqmm 3½ core) 24 Supply and burring of Safe Earthing Electrode T-39 A-Alloy Coated, Length 3000mm, outer pipe 76.3mm x 3.2 inner pipe 42.4mm x 2.6mm, terminal Dia 12mm, coating 80-100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30 cm square C.I. frame with hinged cover & masonry housing. (From electrode terminal to switch board, cost of 25 x 3 G.I. Strip will be extra)Make: As approved in U.P. P.W.D., & C.P.R.I. Certified. 25 Supply and burring of Safe Earthing Electrode T-39 Cu Copper Coated, Length up to 3000mm, outer pipe 76.3mm x 3.2 inner pipe 42.4mm x 2.6mm, terminal Dia 12mm, coating 80-100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30 cm square C.I. frame with hinged cover & masonry housing. (From electrode terminal to switch board, cost of 25 x 3 Copper Strip will be extra).Make: As approved in U.P. P.W.D., & C.P.R.I. Certified. 26 Making suitable earth of GI pole with 2.5 Mts. long 20mm M.S rod connected with 7/16 SWGG.S. wire duly clamped & binded on pole including the cost of materials, labour and T & P required for proper completion of work as per direction of E/I. 27 Supply and laying of 32 mm x 6 mm G.I. strip from earth electrode directly in the ground as required complete in all respect. 28 Supply and laying of 50mm x6 mm Copper strip Complete 29 Supply and fixing of 2 metres high cage fabricated with 3mm thick expanded metal fixed on 50mm x 50mm x 6mm angle iron frame having vertical members spaced at 1 to 1.25 mts and horizontal members spaced at 1 mt. The vertical members shall be grouted in floor and horizontal members in the wall to a depth of 300mm with ends forked. The cage shall have 2000mm x 1000mm size one leaf door with locking device having door frame fabricated with 35mm x 35mm x 6mm angle iron and 3mm expanded metal duly fixed with the cage member with hinges etc. The cage shall be painted with red oxide primer and synthetic enamel paint. The job includes all materials, labour, T&P etc. for proper completion ofwork. 30 Supply & Fixing of 1200 mm Sweep of Ceiling Fans with fan motor ofA.C.PermanentinsulationcapacitorratingconformingBEE5 Star rating and IS:374/79 and also comply with IS: 1709/1984 with latest amendment. The rated voltage 220/240 volts, 50 Hz, I-ph AC thefanassembleshouldconsistsofdownrodblades,shackle canopiesetcanddoubleballbearingsystem.Completeinall respect. 31 S/F of 16 SWG M.S. drum with luvers duly painted including makinghole in the wall for exhaust fan and finishing properly complete in all respect. Complete in all respect 32 S/F of shock tretment chart (Prescribed under I.E. rules) duly framed with glass and supported from back with hard board or soft board with supply of all material labour T & P for proper competion of work. Complete in all respect 33 S/Fofrecess/Surfacemountinground10to15wattcutoutmin 125mm,heightmin40mm,LEDDownLighterhavingPowder coated die cast aluminium housing with heat sink, diffuser/Reflector and driver set suitable for 24 Hr continuous operation, complete in all respect. CAt-AAA 1100-1500 system lumens, 110lm/w, PF>0.95, THD<10% at full load, CRI>80 with 5 year warranty. 34 S/F of LED Tube Light with Batten suitable for up to 1x22 watt LED Tube Light fitting including tube on surface complete in all respect. CAt-AAA 2420 system lumens, 110lm/w, PF>0.95, THD<10% at full load,CRI>80sheetthickness0.8mm,tubewithaluminiumwith5 year warranty. 35 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, C curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. CAT-A30.1 Single pole 36 BUILDING WORK Construction of 33 / 11 KV Sub station building (RCC Frame Structure) for housing of 33 KV and 11 KV panels, maintenance rooms, staff quarters etc with supply of all civil works, labour, T&P including plumbing and electrical works, cable trenches, chequered steel plates as per standard designs of UPPCL complete in all respects. (As per drawing -area 10x20 =.150.00 sqmtr., G.F. Panel Room Hieght=4.5 Mtr (3.6+0.3 X 3=4.5). (Rs 17500+3x280.00 = Rs 18340.00/sqmt) Plinth Area Rate PWD/2020)31.1Pannel Room G.F. 37 Construction of 33/11 KV Sub station first floor building (RCC Frame Structure) for housing of 33 KV and 11 KV panels, maintenance rooms, staff quarters etc with supply of all civil works, labour. T&P including plumbing, Snatiry and electrical works, including all complete as per standared design of UPPCL complete in all respect. (10 X 20 = 200 Sqmtr) 150.00 Sqm Plinth Area Rate-PWD/2020) 38 Boundry wall work Construction of Boundry wall made with 1:2:4 RCC with 20 mm stone ballest colum Fe. Tie Beamand Top Beam including Brick Work in super structure and 12 mm thick plaster in 1:6 core sand all complite as per attach designe. (Analysis Rate) 39 Construction of 1.5 HP submersible pump motor set with 150 mm dia 30 mt depth drilling of bore well complite with 110 mm dia PVC pipe 6 kg presour, 40 mm dia Gl pipeand all spacials, 1.5 HP pump moter set,starter.copper cable, etc all complite as per direction of E/lc. (Para 33/11 KV Sub Station File) 40 External Devlopmnet work Construction of GSB by providing close graded material, mixing in machnical mixture plant at OMC carriage of mixied materials to work site, spreading in uniform layers with mortor grader on prepaired surface and compcting withvibratory power roller to achieve the desired density complite as per clause 401 Grade-II (Approved Rate) 41 S/L of 80 mm thick Rubber moulded interlocking C.C paver block manufactured by high pressure controlled vibration machin all compleate with labour, material etcc all complite as per direction of E/lc. PWD-SOR 42 Mild Steel or iron in plain work as rainforce concreet or rainforceced brick work including welding where necessary and also including Bending supply of steel, etc all complite as per direction of E/lc. (For Main Gate) PWD, SOR-504/2017-18 43 33 KV Feeder Line 33 KV CableSupply and laying of Al conductor 33 KV (E) XLPE cross linked polyethlene) over all served cable with flat galvanised steel strip armouring at existing trench/hume pipe. (i) 300Sqmm 3 core 44 Supply and laying of Al conductor 33 KV (E) XLPE cross linked polyethlene) over all served cable with flat galvanised steel strip armouring at a dept of 1.0M below ground level over a cushion of 75mm thick sand bed alroundand protect with bricks on sides and top surface 300x3x4 mm red stone the cable run shall be fixed on M.S clamp etc of suitable size and crossing the road cable shall run through 150mm dia hume pipe proper completion of work. (i) 300Sqmm 3 core 45 Supply and jointing heat shinkable kit for 33 KV 300sqmm 3core XLPE cable including cost of all material, labour, T & P etc. as per proper completion of work. Out door Type 46 Supply and jointing heat shinkable kit for 33 KV 300sqmm 3core XLPE cable including cost of all material, labour, T & P etc. as per proper completion of work. Straight through 47 Supply/laying of following type high conductivity aluminum strand compacted circular conductor XLP (E) armoured 11KV cable neutral earthed system confirming to IS 7098-Part-II(1985) with latest amendment at a depth of 1 Mtr. Below ground level over a cushion of 75mm thick sand around and protect with brick on sides and top of cable shall be properly connecting with the earth conductor by clamps etc. with the cost of all material, labour, T&P etc. required for proper completion of the work.(70 Sqmm 3 core) 48 Supply/laying of following type high conductivity aluminum strand compacted circular conductor XLP (E) armoured 11KV cable neutral earthed system confirming to IS 7098-Part-II(1985) with latest amendment at a depth of 1 Mtr. Below ground level over a cushion of 75mm thick sand around and protect with brick on sides and top of cable shall be properly connecting with the earth conductor by clamps etc. with the cost of all material, labour, T&P etc. required for proper completion of the work.(300 Sqmm 3 core) 49 S/F and jointing of following sizes out door/ Indoor type (Heat shrinkable) Jointing Kit for 11 KV grade cable (Indoor type 3X300 Sqmm) 50 S/F and jointing of following sizes out door/ Indoor type (Heat shrinkable) Jointing Kit for 11 KV grade cable (Outdoor type 3 x 300 Sqmm) 51 S/F and jointing of following sizes out door/ Indoor type (Heat shrinkable) Jointing Kit for 11 KV grade cable (Indoor type 3X70 Sqmm) 52 S/F and jointing of following sizes out door/ Indoor type (Heat shrinkable) Jointing Kit for 11 KV grade cable (Outdoor type 70 Sqmm) 53 CAMPUS LIGHTS & OTHER WORK Supply & fixing of 7 mtr GI Octagonal Pole of approved make (top dia 70mm, Bottom dia 130mm and base plate 12mm thik) having 3mm thikness with single arm bracket (1 Mtr length) on RCC foundationincluding the cost of foundation, foundation bolts, excavation & back filling and Required T&P completee in all respect. 54 Supply and fixing ofLED Street light Fittinghaving die cast aluminium body and diffuser with driver set suitable for 75 to 90 Watt. Confirming to IP 66 and aboveProtection complete in all respect. CAT- AAA 55 S/W of submain with two Nos. of 2.5 Sq.mm FRLSH PVC insulated 1100 V grade single core multistrand copper conductor cable in existing conduit complete with supply of all material Labour and T&P required for proper completion of the work as directed at site by E/I. 56 S&Fof 32 Amp. 240 V SPN metal clad rewireable type switch fuse unit on M.D.F.E.G. / Teak wood board complete in all respects. 57 S/F of 6 Amp to 32 Amp. SPMCB (10KA) C curvecompletein allrespect as perdirectionof Engineer-in-charge. 58 Supply and fixing earth rod in the switch yard/ outdoor indoor equipmentof the substation for all electrical equipments and structure by laying of MS round of 32mm dia in 750mm deep trenches and earth electrode 3M. Long of MS round bar 32mm dia 0.5M below ground level. The work including /bending/flooring of MS round bar and connections all all steel structures in switch yard with earth mat by means of M.S strip of size 50x6mm including all labour , material T&P etc. required for proper completion of the work as per details specification of UPPCL