| 1 | Supply of PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size : 3.5 core x 185 sq.mm. Aluminium armoured Cable. |
| 2 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Above 95 sq. mm and upto 185 sq. Mm. |
| 3 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3.5 X 185 sq. mm (57mm). |
| 4 | Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3.5 X 185 sq. Mm. |
| 5 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 4X10sq.mm+ 2X6 sq. mm earth wire. |
| 6 | Wall Mounting Junction Bus Bar (Bus Bar Capacity - 800 Amp.)Based Distribution Panel with One Nos. Three Phase Incomer Tapping & Four Nos. Three Phase Outgoings Tappings(for termination of 4 no. XLPE cables) |
| 7 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 4 way (4 + 12), Double door. |
| 8 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 150 A, 16 KA,TPMCCB |
| 9 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 100 A, 16 KA,TPMCCB |
| 10 | Supply of PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size : 3.5 core x 70 sq.mm. Aluminium armoured Cable |
| 11 | Supply of PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size : 3.5 core x 35 sq.mm. Aluminium armoured Cable |
| 12 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) |
| 13 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 14 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3.5 X 70 sq. mm (38mm) |
| 15 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3.5 X 35 sq. mm (32mm) |
| 16 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required Single pole |
| 17 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required Triple pole |
| 18 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 19 | Supplying and fixing suitable size Gl box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 20 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 2.5 sq.mm + 1 X 2.5 sq. mm earth wire. |
| 21 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 4sq.mm+ 1 X 4 sq. mm earth wire. |
| 22 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 4X4sq.mm+ 2X4 sq. mm earth wire. |
| 23 | Supplying and fixing TP sheet steel enclosure on surface/ recess along with 16/25/32 A 415 V \"C\" curve TP MCB complete with connections, testing and commissioning etc. as required. |
| 24 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 4 way (4 + 12), Double door. |
| 25 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required 150 A, 16 KA, TPMCCB |
| 26 | Supply of PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size 3.5 core x 70 sq.mm. Aluminium armoured Cable |
| 27 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) |
| 28 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required 3.5 X 70 sq. mm (38mm) |
| 29 | Supplying and fixing 63 A rating, 415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole |
| 30 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 4 X 10 sq.mm + 2 X 6 sq. mm earth wire |
| 31 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powderainted including earthing etc. as required. (But without MCB/RCCB/Isolator 6 way (4 + 18), Double door |
| 32 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63A |
| 33 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required Single pole |
| 34 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor le core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and erthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group A |
| 35 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2X 2.5 sq.mm + 1 X 2.5 sq. mm earth wire |
| 36 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2X4sq.mm+ 1X4 sq. mm earth wire |
| 37 | Supplying and fixing suitable size Gl box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 38 | LED Tubelight 22Watt complete fitting (Bajaj/Havells/Philips/Crompton/Halonix) |
| 39 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 40 | Supply of 300 mm, 1400 RPM, Three / Four blade with copper winding, Exhaus tFan (Bajaj/Havells/Crompton/Orient/Atomberg/Usha/Almonard/Alstom |
| 41 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. As required. Upto 450 mm sweep |
| 42 | Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes. |
| 43 | Supply of 1200 mm, 50 Hz Ceiling Fan(Bajaj/Havells/Crompton/Orient/Atomberg/Usha/Almonard/Alstom) |
| 44 | Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. |
| 45 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 46 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 47 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 4 way (4 + 12), Double door |
| 48 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 150 A, 16 KA, TPMCCB |
| 49 | Supply of PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size3.5 core x 70 sq.mm. Aluminium armoured Cable |
| 50 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) |
| 51 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3.5 X 70 sq. mm (38mm) |
| 52 | Supplying and fixing 63 A rating, 415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole |
| 53 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 4 X 10 sq.mm + 2 X 6 sq. mm earth wire |
| 54 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powderainted including earthing etc. as required. (But without MCB/RCCB/Isolator 6 way (4 + 18), Double door |
| 55 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63A |
| 56 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required Single pole |
| 57 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor le core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and erthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group A |
| 58 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.2X 2.5 sq.mm + 1 X 2.5 sq. mm earth wire |
| 59 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2X4sq.mm+ 1X4 sq. mm earth wire |
| 60 | Supplying and fixing suitable size Gl box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 61 | LED Tubelight22Watt complete fitting (Bajaj/Havells/Philips/Crompton/Halonix) |
| 62 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 63 | Supply of 300 mm, 1400 RPM, Three / Four blade with copper winding, Exhaust Fan (Bajaj/Havells/Crompton/Orient/Atomberg/Usha/Almonard/Alstom) |
| 64 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. As required. Upto 450 mm sweep |
| 65 | Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes. |
| 66 | Supply of 1200 mm, 50 Hz Ceiling Fan(Bajaj/Havells/Crompton/Orient/Atomberg/Usha/Almonard/Alstom) |
| 67 | Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. |
| 68 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 69 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |