| 1 | Taking down old unserviceable High bay, Mid Bay, Flame Proof light fittings from walls/Builings/Sheds/Ceilingheight up to 10 Meter for repairs and replacement ofburnt/worn out accessories and refixing the same in existing position including testing of fittings after repair, testing of connected wiring complete all as directed by Engineer in charge . Note :- (a) T & P, Ladder for any height etc are deemed to be included in the quoted rate.(iii) The representative of the contrcator shall report to Engineer-in-charge/JE and carry out repairs on daily basis during the contrcat period and the defect shall be rectified on the same day(iii)A penal recovery of Rs 500 Per Day Per Complaint for not attening the compalint will be recovered |
| 2 | Supply & fix in repairs LED Highbay light fittings 150 watts, Energy saving, environment friendly & robust open type vertical Highbay LED IP 66 luminaire including driver and required GI tube down road of length up to 2 meter with hoooks for hanging the fitting. The fitting including fixing arrangements and taking down old rusted bracket fittings complete etc. Make :-Crompton / Havells /Bajaj.Note : Fittings shall will be installed in Hangers/Sheds, height up to 10 Meters only and directed by Engr-in-Charge. |
| 3 | Supply & fix in repairs very high efficiency round LED Highbay light fittings 150 Watt in PDC housing, IP 66 luminaire including driver and required GI tube down road of length up to 2 meter with hoooks for hanging the fitting including fixing arrangements and taking down old rusted bracket fittings complete etc. The Make :-Crompton / Havells /Bajaj.Note : Fittings shall will be installed in Hangers/Sheds, hight up to 10 Meters only and directed by Engr-in-Charge. |
| 4 | Material and Labour for checking of panels, DB\"s, Junction Box, including cleaning with blower, clamping of lugs as per existing size and capacity complete all as specified and directed.Technician will Carry scheduled preventative maintenance checks as per details to be given by Site Executive. |
| 5 | S & F in repairs MCCB 63 Amps, 25 kA Triple Pole 415 Volts including connecting up complete in existing panel with suitable lugs/ Glands all as specified and directed.Make:- L&T/ Legrand/ Schnieder/ ABB |
| 6 | S & F in repairs MCCB 100 Amps, 25 kA Triple Pole 415 Volts including connecting up complete in existing panel with suitable lugs/ Glands all as specified and directed.Make:- L&T/ Legrand/ Schnieder/ ABB |
| 7 | S & F in repairs MCCB 200 Amps, 36 kA Triple Pole 415 Volts including connecting up complete in existing panel with lugs/ Glands all as specified and directed.Make:- L&T/ Legrand/ Schnieder/ ABB |
| 8 | S & F in repair MCCB 250 Amps, 36 kA Triple Pole 415 Volts including connecting up complete in existing panel with lugs/ Glands all as specified and directed.Make:- L&T/ Legrand/ Schnieder/ ABB |
| 9 | Excavation in trenches not exc 1.5 mtr wide and not exc 1.5 mtr in depth and getting out in in soft / lose soil complete all as specified and directed by Engineer in charge. |
| 10 | Returning filling in , excavated soil including spreading, leveling and well ramming in layers not exc 25cms each any type of soil complete all as specified and directed by Engineer in charge. |
| 11 | Removing the excavated materials not exc 50mtr and depositingwhere directed at a level not exceeding 1.5 mtr above the staring point all as directed by Engr - in- Charge. |
| 12 | M&L for sand cushioning by spreading in trenches stone crushsand by gently by punning down manually as in cable protection all as specified and as directed by EIC. |
| 13 | Supply and laying un-reinforced precast concrete cable cover class LV, type-I, flat size 250mm x 150mm x 40mm laid in trenches all as specified.. |
| 14 | Taking down existing UG cable and supply & LayXLPEinsulated,heavy duty 1100 volt grade electricarmoured LT UG cable with aluminium conductorof size 95 Sqmm 3.5 Core in trenches/along the wall/including making all connections, saddles, spacersincluding scaffolding if any required for saddling the cable in walls of building of height up to 25 meter, complete wih aluminium lugs as required at site and as directed by Engr-in-Charge |
| 15 | Supply and fixing 36 Watt All in one integrated Solar Street Light fitting with complete system with Battery Lithim ion, 11.1 V, 39.6 AHincluding braket and including taking down old unserviceable fitting with fixing assembly complete all as directed by Engineer in Charge. Make : Sai Indutrial alliances pvt ltd/ Crompton/ Bajaj as approved by GE |
| 16 | S&F in Surface, hanging and wall mounted batten CRCA housing box type luminaire (Double side connection) suitablefor T8 LED tube 20/22 watts, 230 volts rated luminous flux 2400 lm/2280 lm, CCT 6500K, CRI >80, life span >50000 hrs alongwith LED tube with polycarbonate housing designed for high performance tube rod 22 watt (double side connection),including fixing mounting blocks 2 Nos, 15 mm MS conduit, 1.5 sqmm 3 core pvc insulated copper conductor cable including fixing arrangements complete all as specified and directed. Make- Bajaj Cat code no- BLRB/ 20W CW LED S (<10% THD) and BLRB- DB 218 or equivalentJaquar/ Wipro |
| 17 | S&F in repairs Surface, hanging and wall mounted batten (Single side connection) suitablefor LED tube 20/22 watts, 230 volts alongwith tube rod 22 watt (double side connection),including fixing mounting blocks 2 Nos, 15 mm MS conduit, 1.5 sqmm 3 core pvc insulated copper conductor cable including fixing arrangements complete all as specified and directed. Make :- BAJAJ/ PHILLIPS/ JAQUAR/ WIPRO |
| 18 | S&F in repair of building Security lightfitting 35 Watt made up of pressure die cast alluminium body with mid power LED as lighting sources and PC cover having Top opening separate driver compartment with IP66 protection and impact resistance of IK07including fixing arrangements and taking down old rusted bracket fittings completeall as per directed by Engr- in – charge. Make:- HAVELLS/ PHILLIPS/ JAQUAR/ WIPRO/BAJAJ |
| 19 | Supply & fix high speed Ceiling fans complete with aluminium blades, down rods, PVC Canopy and accessories white in color 230 V, 1200 mm sweep Min air delivery 210 CFM with service value min 6.00 BEE Five star rated with brushless direct current motor (BLDC) without remote complete. Make- Havell\"s (Efficiencia Neo (BLDC 26W)/ Orient (FALCON 400)/ Bajaj(ENERGOS 28)) |
| 20 | Supply and fix heavy duty Metalic body Exhuast fan high speed type of sweep 300mm, speed 1400 RPM, air delivery 1300 CMH, power 70W comprising of double ball bearing,blades,louvers complete mounting anchor fasterners aluminium louvers made of aluminium sheet of 0.5 mm thickness provision of 3 core 1.5 sqmm copper cable from ceiling rose to fan etc complete all as specified and directed.Make- Crompton/ Orient/Almonard/Bajaj.Note-The Contractor shall submit 1 year warrenty ceertificate from OEM of exhaust fan. |
| 21 | Supply and fix heavy sturdy Engineering plastic Exhuast fan high speed type of sweep 250mm, speed 1400 RPM, air delivery 1300 CMH, power 70W comprising of double ball bearing,blades,louvers complete mounting anchor fasterners aluminium louvers made of aluminium sheet of 0.5 mm thickness provision of 3 core 1.5 sqmm copper cable from ceiling rose to fan etc complete all as specified and directed.Make- Crompton/ Orient/Almonard/Bajaj.Note-The Contractor shall submit 1 year warrenty ceertificate from OEM of exhaust fan |
| 22 | Supply & fix ceiling fan complaints 2.5 Mfd operating on 230V, 50 Hz AC supply IS :1709 marked complete. MAKE:- KELTRON/EPCOS/ CAPCO/ TISCON |
| 23 | M & L forpoint wiring complete with proper colour coding with 1100 Volts grade, 1.5 Sqmm PVC insulated FRLS grade, unsheathed, wire confirming to IS-694, Part II, ISI marked with multistranded copper conductor drawn in and including PVC concealed conduit of suitable size of wall/ RCC slab/ ceiling/ colunms/ beams etc with all accessories, fittings, PVC junction boxes etc,for mounting modular switches, sockets, fan regulators etc, also including 1.5 Sqmm, PVC insulated, FRLS unsheathed, 1100 Volts multistranded copper conductor green colour as contineous earth wire connected to common earth dolly for one light point/fan/bell point controlled by one way switch, complete all as specified and directed. Note : Rates included for concealed cutting as required at site without any damage and making good in CM 1:4 and matching the surface as required 2 all screws and washer for point wiring shall be Stainless steel. Nothing is extra shall be admisible on this account.Make of Conduit- Sudhakar/ Precision/ Pressfit.Make of copper wire- KEI/ Anchor (Panasonic)/ Polycab/ Finolex. |
| 24 | M&Lin repairs for 24 Hrs240 V FM1 Quartz type Time switches astronomical type (Having longitude and latitude of Indian cities in memory) timer for controlling street lights contactors complete all as directed by Engr-in - Charge .Make :-Legrand/ L&T/Indo Asian as approved by GE |
| 25 | Supply and fix in replacement 8/9 Watt LED Bollard garden light fitting with efficient high output COB LED, pressue die cast powder coated housing with PC diffuser driver nut bolt ,washer base plate foundation 0.3 mtrx0.3 mtr x.40 mtr by PCC 1:2:4 type B-1 using 20mm grade stone aggegates of size including excavtion and earth work , provision of GI bend of size 50MM dia in the PCC for cable entry all as specified and directed in EIC. Make:- HAVELLS/ PHILLIPS/ JAQUAR/ WIPRO/BAJAJ. |
| 26 | Supply and fix New generation , Post-top LED warmlight 35/40 W,energy saving, environmental friendly, long life aesthetically designed with symmetrical light distribution,spun aluminium landscape luminaire with high power LEDs as light provision of GI bend of size 40 mm dia in the PCC for cable entry the fittingwith nut bolts,washerall as specified and directed in EIC. Make:- HAVELLS/ PHILLIPS/ JAQUAR/ WIPRO. |
| 27 | Supply & Fixing round shape 15 watt 220 volts AC recessed type with high efficiency PMMA diffuser soft glare free light complete with drivers, holders, LED lamp suitable for roof ceiling including connecting up with three core flexible copper conductor cable of suitable size complete. Make : Bajaj/Crompton/Jaquar |
| 28 | M&L for reinforced cement concretenominal mix M-20(using 20mm graded stone aggregate) for foundations, including rafts, footings, foundation beams, plinth beams, bases for column etc and mass concrete, complete all as specified and directed.(Note - Reinforcement and form work will be measured and paid separately). |
| 29 | M & L for TMT bars of Fe-500 D grade conforming to is:1786, 10 mm dia & over, including cutting to length, bent to shape equired, cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9 mm dia or securing with clips etc, complete all as specified and directed. |
| 30 | M & L for TMT bars of Fe-500 D grade conforming to IS: 1786, 8 mm dia bars as in binders, spacers, strippusincluding cutting to length, bent to shape required, cranking, bending spirallyfor hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9 mm dia or securing with clips etc, complete all as specified and directed. |
| 31 | M & L for use and waste of formwork to sides of concrete foundations, footings, bases of columns, raft and raft beams , side and soffits (if any) of foundation and plinth beams and similar work, vertical or to batter, for rough finished surfaces of concrete, complete all as specified and directed. |
| 32 | Dismantling of old UNSV/rusted steel tubular poles 9 mtr long necessary disconnecting cables/over head condcutor and removing unserviceable pole from site complete all as specified and directed. |
| 33 | Supply, Fixing and connection of hot dip galvanised octagonal poles of height 6 mtr with 130 mm bottom A/F & 70mm top A/F made up of 3mm thick HT sheet along with base plate of size 200 x 200 x 12mm thick including 4 nos of M20 x 600 long J type foundation bolts and 1 mtr long hot dip galvanised single arm standard bracket, including MCB of 6 Amps, with connector 4 way to be provided as termination point complete all as specified and directed. Make :- Bajaj |
| 34 | M & L for Taking down and Refixing the aluminium/copper strip of any size from any position / location ofsheds/ buildings of height up to 30 meter &laid as roof conductor, down conductor, earth contunity conductoor same after straightning the conductor/removal of bends, including replacing the old strips, insulators with new one and saddles all as directed at site Note -i)The quoted rae is deemed to inclusive of T & P/scaffolding/staging etcfor executing the work in buildings of height up to 30meter.ii) The raete is deemed to be inclusive for providing Procealin insulator, screws, Plugsiii) PCC Block required shall be measure and paid under respective items iv) Span of PCC Block support shall be kept at 70 cm.v) Span of insulation support (without block) shall be fixed at 30 cm space. |
| 35 | S&F aluminium earth strip as roof/down/earth contunity conductors of size 25x3mm with saddles, Parcelain, insulators, stainless steel screws, washer etc at any position / locationofsheds/ buildings of height up to 30 meter complete all as specified and directed by the Engineer-in-charge Note -i)The quoted rate is deemed to inclusive of T & P/scaffolding/staging etcfor executing the work in buildings of height up to 30meter.ii) The rate is deemed to be inclusive of Procealin insulator, screws, Plugs etc. |
| 36 | S&F air termination, single pointed aluminium rod, 12mm dia 300mm long at any position / location including all necessary terminal base plate of thickness not less than 4 mm, scaffolding / staging required, etc. complete all as specified and directed by the Engineer-in-charge |
| 37 | M&L Test point terminal block made of gun metal or phosphorus bronze size 75x75x25 mm, drilled and screwed including 3 nos. 8mm dia 25 mm long hex. Head screw in replacement of the unserviceable. Including MS box made out of 3 mm thick shheet for fixing the block complete all as specified and directed. |
| 38 | M&L for pre-cast cement concreate block of size 0.15M x0.15M x0.15M for fixing of Aluminium striptype C1 1:3:6 using 20mm graded stone aggregate in cement motor 1:4, including fixing the coccrete block on terrace of bldgs of height up to 30 meter all as directed at site Note -i)The quoted rae is deemed to inclusive of T & P/scaffolding/staging etcfor executing the work in buildings of height up to 30meter. |
| 39 | Supply and fixing of GI pipe light grade of size 40 mm bore for laying in trenches/floors or walls including allfittings for fixing complete as required and directed by Engineer-in-Charge. |
| 40 | M&L for painting on wall with synthetic enameledpaint of black colour of 200 x 150 mm size and writing work for earth test result with date & year all as specified and directed at site by Engineer-in-Charge. |
| 41 | Supply & Fix MCB DB Double Door SPN 4 way 240 volts including connecting up with existing cable with new lugs. The DB Shall be of Make - Havells/Indoasaian/Legrand/ABB/Schnider |
| 42 | Supply & Fix MCB DB Double Door SPN 8 way 240 volts including connecting up with existing cable with new lugs. The DB Shall be of Make - Havells/Indoasaian/Legrand/ABB/Schnider. |
| 43 | S & F in repairs electronic fan regulator five stepped, operating on 230V, 50 Hz AC supply, duly IS :1979.Make:- Anchor/ legrand/ Vinay |
| 44 | Supply and fix electronic meters temper proof LCD display with polycarbonate cover 230 V, 10- 60Amp, accuracy class-I 50Hz, conforming to IS 13779, IP-54, with parameters to show data, time,current reading, load, PF, voltage and KWHMake:- L&T/ IndoAsian |
| 45 | Supply and laying in repairs cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 150 sq mm 3.5 core complete including taking down old us cable complete all as specified and directed. Make - Polycab/ KEI/ Havells |
| 46 | All as per SL Item No 45 herein before but of size 120 Sqmm 3.5 Core complete. Make - Polycab/ KEI/ Havells |
| 47 | All as per SL Item No 45 herein before but of size 70 Sqmm 3.5 Core complete. Make - Polycab/ KEI/ HavellsNote : For item Ser No.45, 46, 47 respectively :-(a) Excavation & Earth work shall be measured and paid seperately under appropriate item under this Schedule |
| 48 | Supply and fix in repair Cable jointing kit for 1.1 KV XLPE/ PVC cable for indoor termination Endjoint complete with jointing material and accessories suitable for 3.5/ 4 core armoured aluminium conductor cable of size 70 sqmm to 120 sqmm complete all as specified and directed.Make - 3M/ M-seal/ Raychem |
| 49 | Supply and fix in repair Cable jointing kit for 1.1 KV XLPE/ PVC cable for indoor termination Endjoint complete with jointing material and accessories suitable for 3.5/ 4 core armoured aluminium conductor cable of size 25 sqmm to 50 sqmm complete all as specified and directed.Make - 3M/ M-seal/ Raychem |
| 50 | Supply and fix in repair Cable jointing kit for 1.1 KV XLPE/ PVC cable for indoor termination Endjoint complete with jointing material and accessories suitable for 3.5/ 4 core armoured aluminium conductor cable of size 150 sqmm to 185 sqmm complete all as specified and directed.Make - 3M/ M-seal/ Raychem |
| 51 | M & L in repairs of Three phase 80 KVA UPS 3 phase,including servising/replacement of worn out parts like PCB, IGBT based, Diode, Capacitors,relay,cooling fan,indicators,connectors,lugs,wires,switches,fuses andto attending all brakdown calls and check all electronic component/cards,checking of rectifier/inverter logic boards,adjust battery charging current,cheking of auto transfer facility between inverter and bypass & bypass to UPS, verification/setting/ rectification of LCD mimics alarms,indications, UPS &battery changover test. Location: RUKMANI Bldg Mahul |
| 52 | M & L in repairs of Three phase 60 KVA UPS 3 phase,including servising/replacement of worn out parts like PCB, IGBT based, Diode, Capacitors,relay,cooling fan,indicators,connectors,lugs,wires,switches,fuses andto attending all brakdown calls and check all electronic component/cards,checking of rectifier/inverter logic boards,adjust battery charging current,cheking of auto transfer facility between inverter and bypass & bypass to UPS, verification/setting/ rectification of LCD mimics alarms,indications, UPS &battery changover test. Location: RUKMANI Bldg Mahul |
| 53 | M & L in repairs of Three phase 20/30 KVA UPS 3 phase,including servising/replacement of worn out parts like PCB, IGBT based, Diode, Capacitors,relay,cooling fan,indicators,connectors,lugs,wires,switches,fuses andto attending all brakdown calls and check all electronic component/cards,checking of rectifier/inverter logic boards,adjust battery charging current,cheking of auto transfer facility between inverter and bypass & bypass to UPS, verification/setting/ rectification of LCD mimics alarms,indications, UPS &battery changover test. Location: RUKMANI Bldg Mahul |
| 54 | Supply and fix in replacement battery heavy duty 12 Volts 180 AHmaintenance free complete all as specified and directed. Make : Exide/Amron/Cummins |
| 55 | Supply and fix in replacement battery heavy duty 12 Volts 130 AHmaintenance free complete all as specified and directed. Make : Exide/Amron/Cummins |
| 56 | Supply and fix in repairs Power Capacitors of Rating 10 KVAR 415 Voltin repairs Naturally air cooled Double dielectric heavy duty, MPP type440 Volt 50 HZ Watt Less Power Capacitors wattage not more than 0.5 Watt per KVAR with meter system conforming to IS 13340 and 13341 ISI Marked all as specified. |
| 57 | All as per item No 56 above but Power Capacitors of Rating 5 KVAR 415 Volt complete all as specified and directed. |
| 58 | Supply and fix in repairs power factor controller relay 8 Stage RPM 8, 415 volts, 50 cycles suitable for manual / automatic operation with indication for each stage, power factor adjustment setting knob / screw,display. Make - L&T/ Conzerv / Neptune /SCHNIDER/SYNTRON/ |
| 59 | M & Lfor testing of APFC panel for proper functioning in manual & auto mode, re-wiring theburnt outwires, replacing the wiring ducts/casing Capping, fuse units and cleaningand testing complete all as directed by engineer-in-charge. |
| 60 | M&L for wiring Submain wiring alongwith earth wire with the 6 Sqmm withFRLSis PVC insulated copper conductor, cable in surface/ recessed in PVC Conduit. Note: 3 Runs of cable and PVC Conduit measured as 1 RM. |
| 61 | M&L for wiring Submain wiring alongwith earth wire with the 4 Sqmm withFRLSis PVC insulated copper conductor, cable in surface/ recessed in PVC Conduit. Note: 3 Runs of cable and PVC Conduit measured as 1 RM. |
| 62 | M&L in repairs for MCB SP, 240 volt, 5 to 32 Amps, 10 KA, C Curve, including taking down old u/s complete all as specified and directed.Make - Indo Asian/Legrand/ ABB/Schnider/Havells |
| 63 | Supply, Fixing in reparis / replacement and connection of hot dip galvanised octagonal poles of height 6 mtr with 130mm bottom A/F & 70mm top A/F made up of 3mm thick HT sheet along with base plate of size 200 x 200 x 12mm thick including 4 nos of M20 x 600 long J type foundation bolts and 1 mtr long hot dip galvanised single arm standard bracket, including MCB of 6 Amps, with connector 4 way to be provided as termination point and including of 45w Bajaj make LED street light complete allincluding Civil works as specified and directed. Make: Bajaj |
| 64 | M&L in repairs for MCB SPN, 240 volt, 40 to 63 Amps, 10 KA, C Curve, including taking down old u/s complete all as specified and directed.Make - Indo Asian/Legrand/ABB/Schnider/Havells |
| 65 | M&L for testing any LT feeder Piller Box/LT Pannel of any size and check load of three phases in RYB and distribute equal load and load balancing certificate should be provided.Note : Load Balancing job performed by electrician other items required make it balance will be supplied by the department. |
| 66 | Supply & Fix in repair ACB 800 Amps, 4 Pole, 65 KA, with Thermal Magnetic Release (Manual Drawout type), over Load protection, Short Circuit Protection & earth Fault Protection, Metering Display including all necessary alteration required for fixing and testing complete all as specified and as directed. Make - Legrand/ L &T/ C&S/ Schneider/ ABB. |
| 67 | S&F air termination, single pointed Copper rod, 12mm dia 300mm long at any position / location including all necessary terminal base plate of thickness not less than 4 mm, scaffolding / staging required, etc. complete all as specified and directed by the Engineer-in-charge |
| 68 | Supply only PVC electrical insulation Tape of best qualityfire retardant and ISI approved width of tape is 18mm and length is 40M Make: Steel grip or equivalent |
| 69 | M & L for earthing chemical with copper plated 50 mm dia pipe 3 mtr long(100 microns) including Electrodite 50 Kg buried directly in ground including earth bore hole work (earth bore not less than 3 Mtr deep below normal ground level and connected to copper earth strip of size 20×3 mm by means of copper nuts bolts with washers and connected as per following specifications completeall as directed by Engineer-in-Charge.(a) Product Model: ASEEL 19 CP, 3 meter long (Copper Plated) – 100 micronsFast Electrode, Model FE 80 mm 3 mtr (Pure Copper Single Pipe), Outer Dia is 80 mm with a wall thickness of 2 mm, Inner Dia is 26 mm with a wall thickness of 2.6 mm, Overall Length is 3000 mm,External Corrosion Protection: Copper Plated (100+ microns), Internal Corrosion Protection: In addition to Copper Plated (100+ microns), a ground breaking corrosion resistant Crystalline Conductive Compound is filled and compacted in the cavity within the pipes to enhance the electrodes performance. Conforms to IS: 3043 - 1987 i.e., Code Of Practice For Earthing (+ 10%) variations in dimensions applicable. |
| 70 | (b) Electrodite backfill: Fast Electrode Earth Enhancement Compound, Manufactured using Eco - Friendly minerals, Blended homogeneously with conductive carbon(s), Resistivity: < 5 ohm-metre (In ideal moist conditions); > 5 ohm-metre (Dry Conditions), Ph Value: 7.0 - 8.5, High water retention capacity, Hygroscopic, Ionic & Electronic conduction, Swells when it comes in contact with water thereby engaging constant contact between the electrode surface & soil which is a crucial aspect in the performance of an earthing system. Packing Size : 2 Bags of 25 kilograms,Recommended for normal soil conditions. Conforms to IS : 3043 – 1987.(c)Installation of earthing with bore well machine complete for bore exceeding upto 4.5 meter below ground level complete all as specified and directed by Engr-in-Charge.(d)Including Taking down of existing earthing. |
| 71 | Supply & Fix copper stripof size 20 X 3 mm duly covered,fixed on porcelain insulators along the wall / roof / ceiling etc complete all as directed.Note : (i)Cost of Porcelain insulators and screw shall be of non-corrosive type and cost is deemed to be included in the quoted rate of the job. (ii) Gap for fixing of support insulator shall not be more than 35cm from one onother. |
| 72 | Note : A SUM OF RS 89025.00 TOWARDS SCHEDULE OF CREDIT SHALL BE DEDUCTED TO ARRIVE THE CONTRACT SUM |