| 1 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulted copper conductor single core cable as earth wire in existing surface / recessed steel / PVC conduit including dismantling as required.1.15.2 |
| 2 | Supply and fixing metal box of 150mm X 75mm X 60mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 3 pin 5/6 A socket outlet and 5/6 A piano type switch, connections/ painting etc. as required. 1.29 |
| 3 | Supplying and fixing metal box of 180mm X 100mm X 60mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 15/16 A socket outlet and 15/16A piano type switch, connections painting etc as required.1.30 |
| 4 | Wiring for circuit /Submain wiring along with earth wire with the following sizes of FRLS PVC insulted copper conductor, single core cable in surface/recessed medium class PVC conduit as required 2x2.5sq.mm+ 1x2.5sq.mm earth wire.1.14.2 |
| 5 | 2x4sq.mm+ 1x4 sq.mm earth wire 1.14.3 |
| 6 | Installation, testing and commissioning of pre wired, fluorescent fitting/ compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling / wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor single core cable and earthing etc. as required1.41 |
| 7 | Installation, testing and commissioning of ceiling fan, wall fan including wiring the down rods of standard length (up to 3 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. 1.44 |
| 8 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required upto 450 mm sweep 1.50.1 |
| 9 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 250 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 4 way (4 + 12), Double door. 2.5.1 |
| 10 | Supplying and fixing following rating, four pole, 415 volts, isolater in the existing MCB 100A DB complete with connections, testing and commissioning etc. As required 2.13.1 |
| 11 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7-meter-long etc. with charcoal/ coke and salt as required.5.4 |
| 12 | Supply 25 watt LED (Tube Light) decorative ultra slim square profile LED lighting fixture with extruded polycarbonate, environmental friendly, energy efficient ready to use pack.Make :- Havells / Crompton / Orient / Usha/ Bajaj |
| 13 | Supply of exhaust fan heavy duty 1440 RPM size 480 mm. Make :- Havells / Crompton / Orient / Usha/ Bajaj |
| 14 | Supply of Ceiling fan heavy duty 900 mm. Make :- Havells / Crompton / Orient / Usha/ Bajaj |