| 1 | Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as requiredcomplete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 2 | Supply,Installation, Testing & Commissioning of modular type VariableRefrigerantFlow/VariableRefrigerantVolumeaircooled Outdoorunitssuitable for cooling and heating,having100% hermetically sealed inverter type Scroll Compressor(s) withand minimum two compressors along with two Condensing fan,above 14/18 HPmodules,microprocessorbased Controller, Side / top discharge type condensing unit(s), with R-410 A Refrigerant,vibrationisolators,withsuitablefoundationetc. completeasrequired.Theunitshalldelivertheratedcapacityat AHRIConditions andwork evenat 50°C ambient temperature without tripping.The unit shall be suitable to work on 400V +/- 10%, 3Phase,50HzACpowersupply.Theunit shallbefilledwithfirst charge of the refrigerant and ready for use as required. The EER at 100% load with AHRI conditions shall not be less than 3.5 andIncluding OEM supplied Piping connection Kit etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 3 | Supply,installation,testingandcommissioningoffollowing minimum capacity 4-way flow VRV/VRF Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor,coilsection with DXCoppercoil,electronicexpansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolation,Cordedremotecontroletc., suitableforoperationon single phase 230 V ± 10%, 50Hz AC supply, complete, as required. The unit shall have automatic force shut down valve in case of fire on receivingsignalfromBMSSystem. Thecoolingcapacityofindoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. (Make will be same as of Outdoor). All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 4 | 2.0 TR |
| 5 | 3.2 TR |
| 6 | Supply,installation,testingandcommissioningoffollowing minimumcapacityVRV/VRFHighwalltypeIndoorunitequipped withand comfort washable synthetic media pre-filter, fan section with low noise fan/dynamicallybalancedblower,multispeedmotor,coilsection with DX copper coil, electronic expansion valve, outer cabinet, cord lessremotecontrol,drainpan,necessaryaccessoriesetc.,suitable foroperationon230V±10%,50Hz,singlephaseACsupply, complete as required.The unit shall have automatic force shut down valveincaseoffireonreceivingsignalfromBMSSystem.The coolingcapacityofindoorunitwillbeatairinletconditionsof27 Degree C DB and 19 Degree C WB temperature. (Make will be same as of Outdoor) All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 7 | 1.65 TR |
| 8 | Supply, installation, testing & commissioning of Group controller for monitoring the status and working condition of all indoor and outdoor units, The controller shall act as an advanced air conditioning management system to given complete control of VRV/VRF air conditioning equipment with Starting/stopping of air-conditioning as a zone or group of individual units. Temperature setting for each Indoor units of zone, Switching between temperature control modes, switching of the fan speed and direction of airflow, enabling/disabling of individual remote controller operation, Alarm code display in case of any problem. It shall be able to control up to 64 (max. 512 if required) number of Indoor units. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 9 | Supplying and installation of high-pressure grade required size OEM make copper connectionY or T Joints / refnet for liquid and suction line complete erected on wall/ceiling with supports/raceways, Nitrile rubber insulation, painting etc. with brazing and testing for leakages confirming the normal operation of the VRV / VRF air conditioning system. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 10 | Gas charging of VRF/VRV system with R410A refrigerant gas. Before gas charging system shall be flushed with high purity Nitrogen Gas to remove carbon content, dirt particles to make sure that there is no chance of mixing any impurity with Refrigerant Gas. Thereafter System shall be tested with Nitrogen Gas at 1.5 Times of working pressure of R410 Refrigerant Gas to ensure leakproof system. Whole system shall be Vacuumed up to 500-micron level which ensures the zero-moisture content level in piping to ensure better cooling efficiency and long life of the system. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 11 | Supply, installation, testing and comissioning ofinterconnectingcopperrefrigerant pipingof DHE Grade C12200- ASTM B68, B75, chemical composition of copper %- 99.0 Min and Phosphorus %- 0.015 to 0.040 . For Annealed copper tube :- Tensile strength = 210 Mpa wih elongation % = 40 Min . Ink MarkBrand Printing on Hard Tubes should be present. duly insulated with tubular elastomeric nitrile rubber FM/UL approved with high water vapor diffusion resistance and low thermal conductivity should be certified \"Class O\" in Fire Propagationas per BS 476 Part 6 including chase cutting andfilling with mortar, Slotted channel supports mounted on 10 mm threaded rod at suitable spacing the exposed piping shall be wrapped with glass woven cloth and lag coating for vapour barrier and weather protection. Joints shall be covered with nitrile rubber tape of 3 mm thick complete as required of following sizes. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 12 | 41.1 mm O.D., wall thinkness ≥ 1.4mm (insulation – 19 mm thick) |
| 13 | 38 mm O.D.,wall thinkness ≥ 1.4mm (insulation – 19 mm thick) |
| 14 | 34.9 mm O.D., wall thinkness ≥ 1.4mm (insulation – 19 mm thick) |
| 15 | 28.6 mm O.D., wall thinkness ≥ 1.2mm(insulation – 19 mm thick) |
| 16 | 25 mm O.D.,wall thinkness ≥ 1.2mm (insulation – 19 mm thick) |
| 17 | 22.2 mm O.D., wall thinkness ≥ 1.0mm (insulation – 19 mm thick) |
| 18 | 19.1 mm O.D., wall thinkness ≥ 1.0mm (insulation – 13 mm thick) |
| 19 | 15.9 mm O.D., wall thinkness ≥ 0.8mm (insulation – 13 mm thick) |
| 20 | 9.5 mm O.D., wall thinkness ≥ 0.8mm (insulation – 13 mm thick) |
| 21 | Supplying and drawing flexible / stranded bare copper conductor, PVC / XLPE insulated, overall aluminium mylar tape shielded ATC drain wire and outer PVC sheathed industrial Instrumentation (shielded)cables voltage grade 300/500 V as per BS /EN 50288-7 in existingsurface or recessed PVC/ MS conduit/casing capping/ Cable tray / Open Duct making connections, testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for cables. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 22 | Un Armoured |
| 23 | 2 core x 1.5 Sq.mm |
| 24 | Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Un-armoured Coppercable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV withelectrolytic gradeCopper made of copper rodsconfirming to IS 613-1964, of purity >99.7 %,Inner / outer sheath confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) includingtesting etc. as required of following size. OEM must have it\"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810 For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 25 | 3 core x 1.5 Sq.mm |
| 26 | Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain water piping withfittings (IS:7834 & 10Kgf/sqcm) like elbow, socket, Tee, solvent cement jointing,support with MS hanger on ceiling or recessed in wallwith chasing & plastering with 6 mmthickclosedcellelastomeric nitrile rubberinsulation including leakage testing etc. as required of following Nominal sizes. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 27 | 25 mm |
| 28 | 32 mm |
| 29 | Supply, Fabricating & installing following sizes of perforated Hot dipped Galvanized iron cable tray ( Galvanized thickness not less then 50 microns) with perforation not more then 17.5% in convenient section including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with GI suspenders including GI bolts & nuts , fastners, supports etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 30 | 150mm x 50mm x 1.6mm |
| 31 | 300mm x 50mm x 1.6mm |
| 32 | 450mm x 62.5mm x 2.0mm |
| 33 | 600mm x 62.5mm x 2.0mm |
| 34 | S&F following sizesof ISI marked ( IS:14927 P - II ) virgin materialUPVC trunking along with accessorieslike coupler, inner, outer, elbow, square box, tee, end cap etc. on surfacewithscrews, expansionfastenersas required. For additional technical parameters of product / work refer Annexure \"A\" attached with this BSR |
| 35 | 75 mm x 50 mm |
| 36 | Supply , Installation, Testing and Comissioning ofInverter type Air Cooled Hi Wall split type Air conditioners with latest star rating system as per BEE amended upto date complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU), R-32/R-410 Green Refrigerant, wireless Remote control, suitable for working between 230V +/- 10% with low & high voltage cutoff and50 hz , single phaseACsupply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 37 | 2.0 TR ISEER not less then 3.8 |
| 38 | Supply, Fixing and testing of following capacity ISO certified company made wall mounted stabilizer having output voltage variation from 200 V to 250 V(+/-5%) with input voltage variation from 170 V to 260 V, time delay facility from 2 to 4 minute and high cutoff at 270 V with providing of 16 Amp /20 Amp Industrialplug top making connection etc complete in all respect.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 39 | 5 kVA |
| 40 | Supply & fixing MS powder coated stand suitable for 1.0/1.5/ 2.0 Tr outdoor type of Split AC.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR . |
| 41 | Making hole in stone masonary/ RCC wall/ RCC slab with core cutter for accomodating refrigerant pipe/ drain pipe/ MS pipe/ cables etc of following dia |
| 42 | 100 mm dia per running inch length |
| 43 | Providing and making wall openings in existing stone / Brick masonary partition wall complete with all requited T & P , Scafolding and providing lintel of required size andstrength, repairing ,plastering and cleaning the sitedebrises as required. |