| 1 | Disconnecting the complete unit of Servo Controlled voltage stabilizer of capacity 30-50 KVA, 3 phase, 50 c/s, AC supply of Make- Vintec/ Blue Line/ ITE or as per existing make and overhauling of the same by cleaning, servicing all serviceable accessories including repairing/ replacing of all defective parts such as nut-bolts, washers and all other minor accessories as required at site with making all connections at both ends including providing lugs on existing cable and testing on full load after completion of repair / overhauling work complete all as specified and directed. NOTE: - (a) Contractor shall be quote the rate including required T&P chain pully and lifting material with transportation etc (b) Supply only spare parts shall be measured and paid separately under relevant items of this schedule. |
| 2 | Supply only following spare parts of 30 to 50 KVA capacity Servo Voltage Stabilizer complete all as specified and directed: - |
| 3 | (a) AC synchronous motor single phase, 50 Hz, 240 volts (3 Kg) with RC |
| 4 | (b) Variable auto transformer (Variac). |
| 5 | (c) Sensing Transformer. |
| 6 | (d) Carbon brush with holder complete. |
| 7 | (e) Servo Digital microprocessor card (Solid state sensing circuit). |
| 8 | (f) RC Net work. |
| 9 | (g) PCB connector. |
| 10 | (h) Gear big. |
| 11 | (j) Carbon fingers. |
| 12 | (k) Variac Control CT. |
| 13 | (m) Main Bushing with brass rod (insulator & rod). |
| 14 | (n) High low cut off relay. |
| 15 | (p) Series transformer. |
| 16 | (q) Electric wiring complete with suitable gauge of copper wire for contact circuit of voltage stabilizer of any capacity. |
| 17 | (r) Servo control Box |
| 18 | (s) Thimble/Lugs of size 16 Sqmm to 50 Sqmm |
| 19 | (t) Thimble/Lugs of size 70 Sqmm to 120 Sqmm |
| 20 | M&L for re-winding to burn out linear coil of copper strip heavy cross sectional area ORroller rolling synchronous motor coils of fully automatic servo control voltage stabilizer capacity up to 50 KVA using super enameled copper wire in conventional design with 4- QPC paper layer cover resist, grade 4 lamination with thickness 0.23 mm to 27 mm on minimum load losses , better insulation electrolytic grade copper strip having current density 2 to 2.5 Amps/ mm2 in oil , for actual efficiency in running condition at 100%load for 360 to 460 volts , losses difference 1/18th of the conventional type regulator ofwith insulating material in same gauge copper purity, no of turns in coil with varnishing, heating, testing etc with all other site work required to make the transformer serviceable and fixing / replacing to following spares :- Note : Contractor shall inform to Deptt for inspection/ check burn out coil before re-winding.Make - As per sample |
| 21 | Supply and re-filling as new transformer oil having specific Di- electric strength as per IE not less than 60 MV supplying in sealed container complete. Make : Silicone /Nexton / MEI |
| 22 | De-hydration and filtration to transformer oil by oil testing machine upto specific di-electric value as per IE rule and IS at site of Servo control voltage stabilizer in 30 to 100KVA capacity/ make/ model etc all including re-filling upto indicating level, cutting welding opening bolting to top cover of stabilizer with re-assembling and making connection in all as per existed complete as directed.Note : (i)Testing report in two copy shall be submitted by contractor in this office and required oil for re-filling shall be measured and paid against respective items. |
| 23 | M&L for preparation of the steel surface of servo voltage stabilizer including cleaning, scraping of exposed surfaces and painting with one coat of synthetic enamel paint with spray painting process in approved shade with and including writing MES number and machine number with black paint (Letter size 50 mm high and minimum 15 mm wide) complete all as specified and directed. |
| 24 | Supply and fix three polepower contactor type ML-6 suitable for AC1 rating 125 Amp range, 240 voltconfirm to IS/ IEC 60947-4-1 & IEC 60947-4-1 size Fr-3, 2 NO+ 2 NC including making connection complete as specified and directed. Make : L&TModel-SS90921in equivalent Siemens/ Schneider /C&S/MDS |
| 25 | Supply and fix three polepower contactor type MNX-32 suitable for AC1 rating 55 Amp, AC3 rating 32 Amp, range, 240 voltconfirm to IS/ IEC 60947-4-1 & IEC 60947-4-1 size Fr-2, including making connection complete as specified and directed. Make : L&TModel-CS94111in equivalent Siemens/ Schneider /C&S/MDS |
| 26 | Supply and fix three polepower contactor type MNX-40 suitable for AC1 rating 55 Amp, AC3 rating 40 Amp, range, 240 voltconfirm to IS/ IEC 60947-4-1 & IEC 60947-4-1 size Fr-2, including making connection complete as specified and directed. Make : L&TModel-CS94111in equivalent Siemens/ Schneider /C&S/MDS |
| 27 | Supply and fixing in replacement of off load change over switch open execution 4 poles, 630 Amp rated, 440 volts, 50 Hzs, confirm to IEC 60947-3, IS/IEC 60947-3alongwith extendable handle with making all connection and fixing accessories on surface of wall/panel operating handle etc complete all as directed by Engr-in-charge.Make :- L&T / Havells/ Siemens |
| 28 | Supply and fixing in replacement of off load change over switch in sheet metal enclosure 4 poles, 250 Amp rated, 440 volts, 50 Hzs, confirm to IEC 60947-3, IS/IEC 60947-3alongwith extendable handle with making all connection and fixing accessories on surface of wall/panel operating handle etc complete all as directed by Engr-in-charge.Make :- L&T / Havells/ Siemens |
| 29 | Supply and fixing three phase LED Amp meter CI 1 accuracy class 1.0,0.5, input voltage measurement range 50-520 VAC (P-P), Aux supply 80-300 VAC, CT secondary site selectable 1A/5A, flusg mounting size 96 x 96 mm, inbuilt of selector switch for 3 phase meter complete with taking down old unsv Amp meter all as directed by Engr-in-Charge. |
| 30 | Supply and fixing three phase LED Volt meter CI 1 accuracy class 1.0,0.5, input voltage measurement range 50-520 VAC (P-P), Aux supply 80-300 VAC, CT secondary site selectable 1A/5A, flusg mounting size 96 x 96 mm, inbuilt of selector switch for 3 phase meter complete with taking down old unsv Amp meter all as directed by Engr-in-Charge. |
| 31 | Excavating in trenches not exc. 1.5m wide and not exc. 1.5 metre deep and getting out in soft/loose soil complete. |
| 32 | Returning filling in foundation/trenches including spreading leveling, watering and well ramming in layers not exceeding 25cm thick in soil complete. |
| 33 | Removal of surplus excavated material to a distance n.exc. 50 metre and depositing where directed at a level n.exc. 1.5 metre above starting point complete. |
| 34 | M & L for sand cushioning for under ground cable with locally available sand for protection of cable 8cm before laying cable and 15cm deep over the cable including spreading and consolidations, complete. (Note-Punned thickness ie 180mm will be measured and paid) |
| 35 | M&L for brick protection cover over cable of old size Bricks” laid dry over LT cable width of brick shall be laid across the length of cable) complete all as specified and as directed. |
| 36 | Material & labour for cutting /boringto plinth protection/ hard standing / road etc in suitable depth to across the GI pipe size upto 80 mm dia of bore for drawn through XLPE under ground cable forgivingmechanical protection to cable complete all as directed.(Note : Quoted rate shall be included the cost of required material for repairing to disturbed surface complete all as per existing site and all as directed by Engineer-in-charge. |
| 37 | M&L in replacement to GI tubing light grade 80 mm dia of bore with all fitting laid in trenches across the road or fixed with pole/ surface of wall etc as site with required fixing accessories complete all as specified and directed. (Make: Tata or Jindal or Swastic) |
| 38 | Supply, laying, jointing and testing LT XLPE cable insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size120 sqmm 3½ core including cable lugs on both ends and fixed along walls with saddles laid in trenches/ passing through GI tubing etc. including taking out existing LT XLPE cable complete as specified and directed. |
| 39 | Supply, laying, jointing and testing LT XLPE cable insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size70 sqmm 3½ core including cable lugs on both ends and fixed along walls with saddles laid in trenches/ passing through GI tubing etc. including taking out existing LT XLPE cable complete as specified and directed. |
| 40 | Supply, jointing, commissioning and testing in replacement heat shrinkable straight through jointing kit suitable for 1100 volt grade (Earthed) cable for outdoor type complete with jointing material and required accessories suitable for underground XLPE cable of size 4 Core x 70 to 95 Sqmm (earthed)complete all as specified and directed.Make:Dension/3M/Rahycam or make as mentioned in Appx \"B\" of PS. |
| 41 | Supply, jointing, commissioning and testing in replacement heat shrinkable straight through jointing kit suitable for 1100 volt grade (Earthed) cable for outdoor type complete with jointing material and required accessories suitable for underground XLPE cable of size 4 Core x 120 to 150 Sqmm (earthed)complete all as specified and directed.Make:Dension/3M/Rahycam or make as mentioned in Appx \"B\" of PS. |
| 42 | Supply and fixing MCCB, 4 pole, 160 Amp rating having breaking capacity of 25 KA, 415V adjustable thermal process based magnetic setting type Ics=75% Icu, confirm to IS/IEC 60947-2 complete with spreader for connection of MCCB and suitable size of thimble complete with taking down old unsv MCCB all as specified and directed by engr-in-charge. Make: L&T/Havells/Indoasian/Siemens/Schneider/Legrand |
| 43 | Supply and fixing MCCB, 4 pole, 200 Amp rating having breaking capacity of 25 KA, 415V adjustable thermal process based magnetic setting type Ics=75% Icu, confirm to IS/IEC 60947-2 complete with spreader for connection of MCCB and suitable size of thimble complete with taking down old unsv MCCB all as specified and directed by engr-in-charge. Make: L&T/Havells/Indoasian/Siemens/Schneider/Legrand |
| 44 | Supply and fixing MCCB, 4 pole, 250 Amp rating having breaking capacity of 25 KA, 415V adjustable thermal process based magnetic setting type Ics=75% Icu, confirm to IS/IEC 60947-2 complete with spreader for connection of MCCB and suitable size of thimble complete with taking down old unsv MCCB all as specified and directed by engr-in-charge. Make: L&T/Havells/Indoasian/Siemens/Schneider/Legrand |
| 45 | M&L for Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick surrounded with charcoal and salt, buried directly in ground (earth pit not less than 2.25 metre deep below ground level) with top edge of plate not less than 1.5 metre below normal ground level connected to galvanized earth leadusing GI earth strip in size 32 x6 mm means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical Plate No 3 of MES SSR Part-I connected to main switch board or main control board all as specified and testing on completion including provision of earth wire protected by galvanized iron15 mm dia light grade pipe and watering pipe shall be 20 mm bore light grade including all excavation and earth work in any type of soil, PCC pit with pre-cast RCC cover, charcoal/salt, funnel etc complete all as directed.(i) The concrete pit shall be PCC 1:3:6 type C-1, 40 mm thick pre cast cover slab of RCC (1:2:4) type B-1 using 20mm graded stone aggregate reinforced with 8mm TMT bars @ 10 cm C/C on both sides with suitable cast iron handle shall be provided in lieu of cast iron cover shown in electrical plate No 3 of MES SSR Part-I.(iv)PCC pit shall be provided at least 500 mm away from the pit and not on the earth pit itself and the extra cost of additional length of watering pipe, bends, elbow etc shall be deemed included in the unit rate. |
| 46 | Supply, install, testing and commissioning of LT panel size enclosures cubical weather and vermin proof totally enclosed made out of 3.15 mm thick CRCA sheet machine pressed of suitable size to operate on 3 phase 4 wire system 415 Volts, 50HZ double door withfront and rear openable with locking arrangement incl inner shutters formounting switch gear etc, bottom gland plate with sufficient numbers of circular cable entry holes, including PCC work, prewired complete duly powder coated with comprising of the following :-INCOMING :-(i)MCCB 100 Amp ,415 Volt,25 KA, 50 Hz, 4 pole Rated Adjustable thermal and fixed magnetic setting Ultimate Shortcircuit Breaking Capacity Icu at 415 V (kA rms) Vac (kA rms), Rated Service short circuit Breaking Capacity Ics = % Icu at 415 V (kA rms) 100%, LS frametype,Confirms to IS/IEC60947-2 Qty - 01 No (ii) Change over switch disconnectoropen excution capacity 100 amp size Fr3,with terminal shroud ,sources seperator and phase barrier inbuilt2 C/O auxiliary contact across range with complete accessories(iii) ON/OFF indicating lamp on incomer feeder for status of feeder = 02 Nos(iv) Digital volt meter AC 0 to 500 volts with inbuilt selector switch duly providedwith suitable size of copper insulated wire with universal coloured code of size 96x96mm-01No |
| 47 | (v) Digital Amp meter AC up to 630 Amp with inbuilt selector switch and CT’sduly prewired with suitable size of copper insulated wire withuniversal colour code of size 96x96mm – 01 No.(vi) Aluminium bus bar200 Amps capacity of suitable length insulated heavy heatshrinkable sleeves etc -04 Nos. OUT GOINGMCCB 63 Amp ,415 Volt,16 KA, 50 Hz, 4 pole Rated Adjustable thermal and fixed magnetic setting Ultimate Shortcircuit Breaking Capacity Icu at 415 V (kA rms) Vac (kA rms), Rated Service short circuit Breaking Capacity Ics = % Icu at 415 V (kA rms) 100%, frametype,Confirms to IS/IEC60947-2- Qty - 02 Nos |
| 48 | Supply and fixing MCB TPN rating capacity 32 Amp four pole 415 volts 50 Hz, 10 KA \"C\" series, confirms to IEC 60947-3, with all incoming/outgoing connection with proper size lugs including taking down old unsv MCB complete all as directed by Engr-in-Charge. |
| 49 | Supply and fixing MCB TPN rating capacity 63 Amp four pole 415 volts 50 Hz, 10 KA \"C\" series, confirms to IEC 60947-3, with all incoming/outgoing connection with proper size lugs including taking down old unsv MCB complete all as directed by Engr-in-Charge. |
| 50 | Supply, installation, testing and commissioningcubical panel factory made, double door CPRI approved outdoortype, dust & vermin proof fabricated of 3.15mm thick, duly high class powder coated paint with, locking arrangement andtwo earth terminals suitable cable glands for all incoming & outgoing cables including grouting ofpanelor PCC foundation with suitable nut, bolt & washer complete all as specified and directed by Engineer-in-charge to accomodate following accessories components:-(i) Incoming MCCB 4 pole, 100Amp capacity, adjustable type with rupturing capacity 25 KA- 01 Nos.(ii)Aluminium bus bar200 Amps capacity of suitable length insulated heavy heatshrinkable sleeves etc -04 Nos.(iii) 01 No AC contractorthree phase 70 Amp capacity 25 KA, one digital Timer switch ,relay,three nos MCB 32Amp 10 KA toggle switch having both auto manual and by pass system - 01 Nos and indicating lamp,digital ammeremeter ,voltmeter mounted on panel and other necessary control accessorieswith suitable size internal wiring complete all as specified and directed. |
| 51 | Supply and fixing in replacement of off load change over switch in sheet metal enclosure 4 poles, 100 Amp rated, 440 volts, 50 Hzs, confirm to IEC 60947-3, IS/IEC 60947-3alongwith extendable handle with making all connection and fixing accessories on surface of wall/panel operating handle etc complete all as directed by Engr-in-charge.Make :- L&T / Havells/ Siemens |
| 52 | Note :- (i) Credit shown in credit schedule of tender document shall be considered by the tenderer while quoting the rates of various items. The same shall be recovered from various payment to contractor before handing over old material. The contract amount shall be arrived at after deduction of Schedule of Credit from the total quoted amount in BOQ.(ii) Make of material shall be as per mentioned in Particular specifications or Appendix \"B\" to Particular specifications as approved by AGE (I) AF manauri |