| 1 | Part-A- E.I WorksSITC of L.T. hooder type Feeder Pillar board of size should be suitable for the bellow descriptions and approved by EIC, with canopy Floor mounted with maple arrangement having rigid & self supporting structure fabricated from 3mm. thick CRCA sheet steel with M/S angle frame,75mm base channel for floor mounted or necessary fixing arrangement for fixing the panel on wall. The Feeder Pillar should be double door accessible both front and rare access operated with locking arrangements. Inside Feeder Pillar Box here Supply, fixing & Commissioning of cubical type L.T. Distribution panel board of size/ Dimensions should be approved by EIC. The panel board consisting of the following switches.A) Incoming Arrangement.1.Supplying and fixing of 415V, 630 A, 36kA FP MCCB With Thermal - Magnetic Release with 4 pole spreader Terminals with rotary handle--- (Make- L&T/SIEMENS/Schneider) -- 1 No.2. Digital multifunction meter with selector push button switch (up/down) with V,A,F,PF,KW,KVA,Old energy,On and Run Hours,site selectable KWh/KVAh, Cl:0.5 (MakeL&T/Siemens/ Schneider/ABB/Legrand) 3. 600/5 A CT - 3nos. 4. R,Y,B indication Lamp -- 3nos 5. S & F 6 Amp SPMCB for auxiliary supply to meters-1 nos6. Necessary Control wiring (of required size cu. wire)7. EI Danger Board - 1 nosB) Out going having1.Supplying and fixing of 415V, 400 A, 36kA FP MCCB With Thermal - Magnetic Release with 4 pole spreader terminal with rotary handle-- 4 pole (Make- L&T/SIEMENS/Schneider) -- 2 Nos.2. Digital multifunction meter with selector push button switch (up/down) with V,A,F,PF,KW,KVA,Old energy,On and Run Hours,site selectable KWh/KVAh, Cl:0.5 (Make-L&T/Siemens/Schneider/ABB/Legrand)3. 400/5 A CT - 6 nos. 4. R,Y,B indication Lamp -- 6 nos 5. S & F 6 Amp SPMCB for auxiliary supply to meters-2 nos 6. Necessary Control wiring (of required size cu. wire) |
| 2 | C) Bus Section:S & F 415 volt, 1000 Amp. Capacity of size 4x (2x80 x 5) mm. 4 nos. copper bar of required size porcelain chairs incl. Hylum sheet behind copper bar. Interconnection between main bus and outgoing switchgears should be done by Copper Bus Bar/ Equivalent ratting of Copper Wire should be approved by EIC. Bar for earth 25x6 Al. A bus bar shall be fixed with FRP chair & the entire bars are insulated with PVC heat Sinkable sleeve of suitable size & color as per direction of E.I.C.Paint will be powder coated, After cleaning, the surface shall be given a phosphate coating, nine tank process system.Constructural Details:All incoming & outgoing panel mounted cubical Switch disconnector fuse shall be housed in Respective compartment with hinged & gasketted Door at front. All doors shall have Panel lock Arrangement. Degree of Protection will be IP-54 .The panel shall be properly Gasketted to prevent ingress of dust & moisture & Remain. Busbar will be properly arrange & all Switches shall be fixed by M.S. nuts & bolts On angle /flat iron frame base.as per direction of E.I.C.The PANEL will be fabricated by 3 mm CRCA Sheet. The sheet steel thickness will be 3mm & Gland plate shall be 3mm thick.Individual compartment door will be interlocked with respective breaker. Panel must have with Bus Alley and Cabe Alley with proper termination by 3/4 WAY Stud Type Power Terminal for every outgoing and incoming feeder. Individual nake plate should have on repective feeder. |
| 3 | Supplying and fixing double door 8 way 200 amp Incomer Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment suitable for 160A incoming.INCOMING –Supplying and fixing 415 V, 200A Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in DBs and necessary connection - 1 No.OUTGOING-Supplying and fixing 415 V, 32A TP MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection- 8 Nos. (Make: Legrand / L&T /Crabtree ) |
| 4 | Supply and fixing VTPN cable end box for MCCB Incomer(Make: Legrand / L&T / Crabtree) |
| 5 | Supply of 7.5 HP DOL Starter, having relay range of 9-14A, Coil voltage-200V-400V, Complete set with all the necessary accessories for the same. Make:- L&T, Type—MK-1 (code no-SS96210SOAO)/ Havells/ GIC |
| 6 | Fixing only starters (for motor control) on flat iron frame / angle iron frame on wall, Direct on Line starter for motor (upto 5 HP) |
| 7 | Supplying and fixing 415 V 32 amp FP MCB Isolator incl.S& Fof Moisture proof,water-proof (outdoor type IP-65) PVC (Hencel/sintex) looping cable box size 300x250x150mm deep including on din rail ofand necessary connection. |
| 8 | SITC of L.T. wall monted Cubical type Panel board of size should be suitable for the bellow descriptions and approved by EIC,this panel totally enclosed L.T. Distribution Panel Board comprising with the following incoming/outgoing switches with cable alley incl. B.B.C., other measuring accessories and spray painting(powder coated phosphate coating nine tank process)as per direction of the EIC. having rigid & self supporting structure fabricated from 3mm. thick CRCA sheet steel with M/S angle frame.A) Incoming Arrangement.1.Supplying and fixing 415V, 415 A 4P on load front operated Changeover switch with Sheet Steel enclosure on angle iron frame on wall with nuts bolts etc)----- 1no Digital multifunction meter with selector push button switch (up/down) with V,A,F,PF,KW,KVA,Old energy,On and Run Hours,site selectable KWh/KVAh, Cl:0.5 (Make-L&T/Siemens/Schneider/ABB/Legrand) - 2 nos. 400/5A CT -6 nos 6A SP MCB- 2nosR,Y,B indication lamp with name plate-6nos Necessary Control wiring (cu. wire of required sizeEI Danger Board.B) Out going having1. Supplying and fixing of 415V, 200 A, 36kA FP MCCB With Thermal - Magnetic Release with 4 Pole spreader terminal with rotary handle -- -4 pole-- (Make- L&T/Seimens/Schneider)-- 2 Nos.R,Y,B indication lamp with name plate-6nosDigital multifunction meter with selector push button switch (up/down) with V,A,F,PF,KW,KVA,Old energy,On and Run Hours,site selectable KWh/KVAh, Cl:0.5 (Make-L&T/Siemens/Schneider/ABB/Legrand) - 2 nos.200/5A CT -6 nos 6A SP MCB- 2nos Necessary Control wiring (cu. wire of required size) |
| 9 | C) Bus Section:S & F 415 volt, 415 Amp. Capacity of size (4x50 x 5) mm. 4 nos. copper bar of required size porcelain chairs incl. Hylum sheet behind copper bar. Interconnection between main bus and outgoing switchgears should be done by tinned Copper Bus Bar/ Equivalent ratting of Copper Wire should be approved by EIC. Bar for earth 25x6 Al. A bus bar shall be fixed with FRP chair & the entire bars are insulated with PVC heat Sinkable sleeve of suitable size & color as per direction of E.I.C.Constructural Details:All incoming & outgoing panel mounted cubical Switch disconnector fuse shall be housed in Respective compartment with hinged & gasketted Door at front. All doors shall have Panel lock Arrangement. Degree of Protection will be IP-42 .The panel shall be properly Gasketted to prevent ingress of dust & moisture & Remain. Busbar will be properly arrange & all Switches shall be fixed by M.S. nuts & bolts On angle /flat iron frame base.as per direction of E.I.C.The PANEL will be fabricated by 3mm CRCA Sheet. The sheet steel thickness will be 3mm & Gland plate shall be 3mm thick. |
| 10 | Supply of 4 core 240sqmm of 1.1 KVgrade alluminium XLPE, PVC/ armouredLT cable(Run in parallel)( Make :Havells/ Polycab/ Phinolex/ Glowstar) |
| 11 | Supply of 4 core 120sqmm of 1.1 KVgrade alluminium XLPE, PVC/ armouredLT cable(Run in single from LT Panel to VTPN and parallel from feeder pillar to LT Panel)( Make :Havells/ Polycab/ Phinolex/ Glowstar) |
| 12 | Supplying & fixing 80 mm dia medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required |
| 13 | Supplying of 80 mm dia HDPE PIPES pe 63, 4kgf/cm2Make-supreme, type-SDR-21, Make- Supreme/Hensel/ Harse or similar make |
| 14 | Excavation of soft soil and laying HDPE/GI Pipe for cable laying filling & ramming.(0.150x0.450xTotal Length of pipe laying (WxDxL) |
| 15 | Laying only Cable above 50 sqmm but not exceeding 400sqmm through existing RCC/ Hume/GI Pipe/open masonary trench for single, 2, 3, 3½and 4 core |
| 16 | Laying of one No. cable above 185 sqmm in underground trench 460mm wide x 760mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per Mtr. including filling the space between the bricks and cable and also the trenchwith shifted soil, leveling up and restoring surface duly rammed |
| 17 | Laying of cable above 3½ core 90 sqmm and upto 3½ core 150 sqmm on wall/surface including S & F MSclams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting |
| 18 | Bituminious Road cutting by using Jac Hamour Compressor Machine, Fuel, Mobile, Compressor Operator and Three Breaker and after that the cutting portion should be manding as same as before with necessary concrete arrangements. |
| 19 | Distribution wiring in 1.1 KV single core stranded \"FR\" PVC insulated & unsheathed copper wire (Brand approved by EIC) in 25mm size PVC rigid conduit \"FR\" (Precision make) incl. necy. fittings as required. a)4 x 84/0.3 (6 sqmm) + 2 x 56/0.3 (4 sqmm) ECC |
| 20 | Supplying and Drawing 1.1 KV single core stranded \"FR\" PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required4x126/0.4 (16 sqmm) + 2x80/0.4 (10 sqmm) as ECC |
| 21 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry ofXLPE/PVC armoured cables as below.a) 4 core 240 sqmm |
| 22 | b) 4 core 120sqmm |
| 23 | Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials . a) 4 core 240 sqmm |
| 24 | b) 4 core 120sqmm |
| 25 | Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. a) 4 sqmm |
| 26 | b) 6 sqmm |
| 27 | c) 10 sqmm |
| 28 | d) 16 sqmm |
| 29 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below:By TATA-Medium GI pipe |
| 30 | Excavation of soil for installation of Earth Electrode and filling & ramming.For Soft Soil |
| 31 | Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall includingproviding drilled holes on the busbar complete with GI bolts,nuts, washers, spacing insulators etc. as required |
| 32 | Extra for providing masoneryenclosure on the top of the earthelectrode of overall size 86.36 cm x 86.36 cm x 46 cm deep(below Ground level) complete with cemented brick work(1:6)of 25 cm width duly plastered with cement morter (inside) CIhinged inspection cover of size 36.56 cm x 35.56 cm with lockingarrangement, GI reducer including drilling of 46 nos. 12 mm diaholes on the GI pipe |
| 33 | Connecting the equipments to earth busbar including S & FGI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages 4 SWG |
| 34 | Supply & Fixing 240 V,25 A, 3 pin Modular type plug top with indicator (Brand approved by EIC) & necy. Connections |
| 35 | SITC of L.T. wall mounted Starter Control Panel board of size should be suitable for the bellow descriptions and approved by EIC, this panel totally enclosed L.T. Distribution Panel Board comprising with the following incoming/outgoing switches with cable alley incl. B.B.C., other measuring accessories and painting as per direction of the EIC. having rigid & self-supporting structure fabricated from 3mm. thick CRCA sheet steel with M/S angle frame.Incoming LT Control Panel Board fixing DOL Starter (9-14 A)(Supplied separately) --- 8 nos and its having the following items.1. Supply and fixing ON indication lamp- 24nos2. Supply and fixing Name plate for each DOL starter and ON indication Lamp – 32nos3. Necessary Control wiring (1.5/2.5/4/6 sqr mm cu. wire) -1 Lot 4. S & F 415 volt, 315 Amp. Capacity of size (4x40 x 5) mm. 4 nos. copper bar of required sizePaint will be powder coated, After cleaning, the surface shall be given a phosphate coating, nine tank process system.Constructural Details:All incoming & outgoing panel mounted cubical Switch disconnector fuse shall be housed in Respective compartment with hinged & gasketted Door at front. All doors shall have Panel lock Arrangement. Degree of Protection will be IP-42 .The panel shall be properly Gasketted to prevent ingress of dust & moisture & Remain. Busbar will be properly arrange & all Switches shall be fixed by M.S. nuts & bolts On angle /flat iron frame base.as per direction of E.I.C.The PANEL will be fabricated by 3mm CRCA Sheet. The sheet steel thickness will be 3mm & Gland plate shall be 2/3mm thick.Individual compartment door will be interlocked with respective breaker. Panel must have with Bus Alley and Cable Alley with proper termination by 3/4 WAY Stud Type Power Terminal for every outgoing and incoming feeder. Individual name plate should have on respective feeder. |
| 36 | Supply & Fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support.With 25x25x3mm angle iron support200x50x1.25mm (18SWG) |
| 37 | Supply & Fixing of perforated GI cable tray bend with perforation not more than 17.5% suspended from ceilingwith two nos. suspenders & 25x25x3mm angle iron for supporting the cross member incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support.200x50x1.25mm (18SWG) |
| 38 | Supply & Fixing of perforated GI cable tray tee with perforation not more than 17.5% suspended from ceilingwith two nos. suspenders & 25x25x3mm angle iron for supporting the cross member incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support.200x50x1.25mm (18SWG) |
| 39 | Supply & Fixing of perforated GI cable tray cross member with perforation not more than 17.5% suspended from ceilingwith two nos. suspenders & 25x25x3mm angle iron for supporting the cross member incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support.200x50x1.25mm (18SWG) |
| 40 | Supply & Fixing of perforated GI cable tray reducer with perforation not more than 17.5% suspended from ceiling with two nos. suspenders & 25x25x3mm angle iron for supporting the reducer incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support.200x50x1.25mm (18SWG) |
| 41 | Supplying ready mixed concrete of M20 Grade with well graded stone chips of 20 mm norminal size containing designed qty of cement per Cu. M of wet concrete produce in computerised batching plant under controlled condition using approved super plastisizer , designing mix following I.S. 10262 and I.S . 456 , transporting the mix with agitation in transit mixer to work site depositeing the mix on a platform erected for the purpose at required level of concreting and then placing the mix its final location of form work , compacting and curing the same complete as per specification & direction of Engineer - in - charge including computerized batching plant transit mixer with all accessories vibrators etc. inclusive of all other incidental of platform and its supporting.Extra Conceret used in repairing of road for laying of 50mm G.I pipe on road (Bituminus)300 mm X 300 mm X 800 mm = 0.072 Cu.Mtrminus(-) 0.05mm x 0.05mm x 0.05mm = 0.000125 Cu.mtr (for GI pipe portion)Total = 0.071 Cu.Mtr. x 15 (length in mtr.) = |
| 42 | Providing and laying special type of median kerb with M-25 Ready Mixed Concrete with Size of 550 mm (H) X 300mm (L) X 150mm (thick)……. For Parking Lot area ( Considering 10.5 mtr , used kerb (sumo) 35 Nos.) N.B :- Item Narration , New concrete Kerb chanel Supply , Fitting & Fixing . |
| 43 | Protective and Decorative Acrylic exterior emulsion of approved quality , as per manufacture\"s Specification and as per direction of Engineer -in- charge to be applied over acrylic primer as required . The rate includes cost of material , labour , scaffolding and all incidental charges but excluding the cost of primer.In Ground floor (Two Coat)Premium 100% Acrylic Emulsion |
| 44 | Part-B- SITC of AC machinesSupply & delivery of 3-ph,415V, 4 Ton Non Inverter Cassette type Air-conditioner machine having cooling capacity 45,630 Btu/Hr / 13.63KW, ISEER 3.26. Non Inverter, Power consumption (Cool) : 4,200 watt,Noise level (46/43/40/36/32.5 dBA). This Cassette type air Conditioning machine should be fitted with Scroll compressors & motor output 2.4KW, LCD remote & all other accessories suitable for Refrigerant-R32. Power supply – 3Phase, Air flow- (36.5/33/29/25/21 m3/min.(Make-Daikin, model no.- FCQF48ARV16 & RGVF48BSY16 or its equivalent of Hitachi/O-General as per approved by EIC/authority).Warranty:- 1 year warrantyfor indoor and outdoor unit and 5 yrs warrantycompressor |
| 45 | Installation, testing & commissioningof new Cassette ACs incl. supply & fixing required Angle Iron Structure on wall for placing outdoor unit & mending good the damages as per direction of E.I.C. [for 4TR Cassette AC ] |
| 46 | Supply & Installation of Extra Add-on items- HVAC grade 5/8\"(for suction) & 3/8\"(for discharge) 1.15mm thicknesscopper refrigerant pipe with 9mm thick nitrile rubber insulation including shaddle,screw, insulation tape, fastner etc for above AC machine as per direction of EIC. [ for new 16 nos 4.0TR Cassette AC] |
| 47 | Supply & Laying 20 mm hard PVC pipe (heavy type) for water drainage. [ for16 nos. new 4 TR Cassette AC ] |
| 48 | Supplying and fixing PVC Rigid Conduit 20mm size including \"T\" jointing section and necessary fixing arrangement |
| 49 | S/L of 7 core 2.5sq.mm 1.1 KV insulation grade sheathed Cu cable(KEI/Polycab/Finolex) with gas line as per direction of EIC for making interconnection/ communication between Indoor to Outdoor unit of Split type AC m/c. |
| 50 | Charging for gas R32 / R410A |
| 51 | Supply & Delivery of non-inverter, fixed Speed Room Air Conditioner fitted with rotary compressor and copper condensing and cooling coil having following major specification.Refrigerant- R-32/ R410A,Capacitor Type: P2 Minimum cooling capacity (BTU/hr): 17230 or higher Maximum power consumption: 1373 wattsEER star rating: 3 Star or higher as per recent year manufactureMinimum tonnage required 1.5 TR or higher with other modern features.Minimum Room discharge Air flow(CFM) : 635 & energy efficient type, with approved make as per IS 1391, Part-I, with remote and all the necessary connection etc. as per direction of EIC(star rating : 3 star)Warranty:- 1 year warrantyfor indoor and outdoor unit and 5 yrs warrantycompressor (Make: Diakin FTL50UV16V3/ HITACHI/O- Generalas per approved by EIC/authority) |
| 52 | Installation, testing & commissioning of the above-said split ACs incl. supply & fixing required Angle Iron Structure on wall for placing outdoor unit & mending good the damages as per direction of E.I.C. |
| 53 | Supply & Laying 5/8\" heavy type PVC pipe for water drainage. (for 1.5 TR split AC) |
| 54 | Supply & Installation of HVAC grade 5/8\"(for suction) & 1/4\"(for discharge) copper refrigerant pipe with 9mm thick nitrile rubber insulation including shaddle,screw, insulation tape, fastner etc for 1.5 ton split AC machine as per direction of EIC. |
| 55 | Hiring charges for scaffolding arrangement with bambo, coir ropes & other required fixing/binding materials including dismantling at the end of work and carriage by deputing 2nos. helpers for fixing of AC machines of the outside wall of the G+2 storied building block as per GS. |
| 56 | Supply and installation of fabrication of suitable brackets having with iron frame fixing in concert wall and base structure for outdoor unit of AC machines. Making structure with welding and fittings the same by welding machines along with necessary fittings arrangements including scaffolding cutting hole as necessary as per direction of EIC. During working condition it is mandatory to wear safety belt and other necessary safety arrangement for all working of concern agency. The locking arrangement is included. |
| 57 | Erection of Outdoor unit Frame structure of above sizeon 10\" brick pedestal of 10\" size should be appropriate according to the above Feeder Pillar and dimensions of the same approved be the EIC (minimum height 600mm bellow Ground level and 600mm above G.L) incl. sand cement plastering and neat cement finishing. Inside the brick pedestal will be filled up by loose sand where the incoming & outgoing cable will be rest. |
| 58 | Cutting holes and subsequent mending good damages. Diameter upto 150 mm. In brick/PVC work |
| 59 | Annual comprehensive servicing & preventive, correctivemaintenance of 4 TR Casstte type Air conditioner machine as per attached terms & conditions. (After completion 1 year free servicing and maintenance. And after one year additional 2 years servicing and maintenance charges) |
| 60 | Annual comprehensive servicing & preventive, corrective maintenance of 1.5 TR split type Air conditioner machine as per attached terms & conditions. (After completion 1 year free servicing and maintenance. And after one year additional 2 years servicing and maintenance charges) |