Sales : +91-777 804 8217
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 18-10-2025 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 25-10-2025 |
| 2 | 11-10-2025 | Corrigendum2 | Date | 18-10-2025 |
| 3 | 24-09-2025 | Corrigendum | BOQ | 01-10-2025 |
| Sl. No. | Item Description |
| 1 | M&L circuit wiring in repairs with two single core PVC-FRLS insulated unsheathed multi stranded copper conductor cable of size 1.5sqmm drawn in MS Steel conduitwith 1.5 Sqmm PVC-FRLS insulated unsheathed multi stranded copper conductor as a continuous earth wire complete including rigid stove enameled steel conduit ISI markedof size not less than 20 mm dia in concealed/surfacewiring inclusive all fitting such as tee, bends, reducer, elbow, bell mouth, tube ends and all fixing accessories such as couplers lock, nuts, sadles, pipe hooks etc fixed properly including taking down old unserviceable wiring complete.in Thane Area Note : 1. M S Conduit/ PVC Conduitwill be measured and paid separately. 2. wiring in shed upto height of 6 mtr. 3. Three run of 1,5 Sqmm wire will be measured & paid as one unit.Make of Wire : KEI/ Polycab/ Benlo/ FinolexMake of Conduit: Pressfit/ Sudhakar |
| 2 | Supply and fixing in replacement of LED securitylight fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection 4 kv surge in built protection completeall as per directed by Engr- in - charge.in Thane Area Make : Bajaj/Crompton/wipro/Jaquar |
| 3 | S& F in replacement of GI steel tubing medium grade 40 mm dia and length up to 1.5 meter bent to shape of offset angle upto 45 degree for fixing of security /street light fittings including MS clamps made of 32mm x5mm flat iron, nuts , bolts, etc all as directed by Engineer in charge |
| 4 | Supply and fixing in replacement of LED securitylight fitting 60 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection 4 kv surge in built protection completeall as per directed by Engr- in - charge.in Thane Area Make : Bajaj/Crompton/wipro/Jaquar |
| 5 | Supply and fixing in replacement of LED Flood light fitting 70 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection 4 kv surge in built protection completeall as per directed by Engr- in - charge.In Thane Area Make : Bajaj/Crompton/wipro/Jaquar |
| 6 | M&L in repairs for MCB SP, 240 volt, 5 to 32 Amps, 10 KA, C Curve, including taking down old u/s complete all as specified and directed.In Thane AreaMake - Indo Asian/Legrand/ ABB/Schnider/Havells |
| 7 | Renewal of broken/wornout earth pit including M & L for earthing chemical with copper plated 50 mm dia pipe 3 mtr long(100 microns) including Electrodite 50 Kg buried directly in ground including earth bore hole work (earth bore not less than 3 Mtr deep below normal ground level and connected to copper earth strip of size 20×3 mm by means of copper nuts bolts with washers and connected as per following specifications completeall as directed by Engineer-in-Charge.(a) Product Model: ASEEL 19 CP, 3 meter long (Copper Plated) – 100 microns .Fast Electrode, Model FE 80 mm 3 mtr (Pure Copper Single Pipe), Outer Dia is 80 mm with a wall thickness of 2 mm, Inner Dia is 26 mm with a wall thickness of 2.6 mm, Overall Length is 3000 mm,External Corrosion Protection: Copper Plated (100+ microns), Internal Corrosion Protection: In addition to Copper Plated (100+ microns), a ground breaking corrosion resistant Crystalline Conductive Compound is filled and compacted in the cavity within the pipes to enhance the electrodes performance. Conforms to IS: 3043 - 1987 i.e., Code Of Practice For Earthing (+ 10%) variations in dimensions applicable. (b) Electrodite backfill: Fast Electrode Earth Enhancement Compound, Manufactured using Eco - Friendly minerals, Blended homogeneously with conductive carbon(s), Resistivity: < 5 ohm-metre (In ideal moist conditions); > 5 ohm-metre (Dry Conditions), Ph Value: 7.0 - 8.5, High water retention capacity, Hygroscopic, Ionic & Electronic conduction, Swells when it comes in contact with water thereby engaging constant contact between the electrode surface & soil which is a crucial aspect in the performance of an earthing system. Packing Size : 2 Bags of 25 kilograms,Recommended for normal soil conditions. Conforms to IS : 3043 – 1987.(c)Installation of earthing with bore well machine complete for bore exceeding upto 4.5 meter below ground level complete all as specified and directed by Engr-in-Charge.In Thane Area |
| 8 | S&F in repairs 20x3mm copper stripall as directed including welding brazing and taking down of old copper strips as required at site in Thane Area |
| 9 | Supply and Fix in repairPVC insulated copper wire 1.5 Sqmm 3 core cable complete all as specified and directed.In Thane AreaMake- Havells,Polycab,KEI,Benlo |
| 10 | Supply and fixing in repair of LED Drivers for street light/garden lights/highbay lights/flood lights/post top lantern from 25 Watt to 150 Watt as per sampleused in Thane Area.Complete all as specified and directed by Engineer in Charge |
| 11 | Supply and fixing Post top lantern LED type 40 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection die cast aluminium spigot with spun aluminium top duly powder with PC diffuser & PMMA clear diffuser from outside with impact and corrosion resistant complete with driver and lamp including removing old unsv lights complete for Thane Area.Make:- Bajaj/ Havells / Benlo/ Crompton/ Jaguar/ Wipro |
| 12 | Supply and fixing Post top lantern LED type 20 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection die cast aluminium spigot with spun aluminium top duly powder with PC diffuser & PMMA clear diffuser from outside with impact and corrosion resistant complete with driver and lamp including taking down old u/s light fitting complete for Thane Area. Make:- Havell\"s/ Crompton/ Jaguar/ wipro/ Bajaj/ Benlo |
| 13 | Supply and Fix in repairs CIMFR certified LED flame proof well glass light fitting 60 watts , with driver & LED, IP 65 protection, including connecting up with three core flexible multi strand copper conductor of 1.5 Sqmm, with flexible metal conduit, including including fabricating red oxide coated brackets made out of MS angles/MS flat for fixing the fitting up to one meter below permenent ceiling, including anchor fastners, nut, bolts, hooks, chainetc including taking down old u/s fitting. The Fitting Shall Conform to standard for Thane AreaMake : Crompton/ Shyam Switch Gear /Bajaj / SudhirNote : (a) Fittings shall will be installed in Hangers/Sheds, hight up to 6 Meters only and directed by Engr-in-Charge.(b) T & P, Ladder for any height etc are deemed to be included in the quoted rate. |
| 14 | Excavation in trenches not exceeding 1.50 m wide and n.exc 1.5 m in depth for foundation of poles, cable etc, not exc 10 sqm on plan and getting out in soft/loose soil including taking out brick protection etc complete all as specified and directed. |
| 15 | Returning, filling in, including spreading, leveling, wateringand well ramming in layers not exc 25cm thick complete all as specified and directed. |
| 16 | Removing excavated materials (soils) not exc. 50m and depositing where directed at a level not exc. 1.5m above the starting point complete all as specified and directed. |
| 17 | M & L for sand cushioning by spreading in trenches fine crush sand by gently by punning down manually as in cable protection all as specified and as directed by Engineer -in-charge. |
| 18 | Supply and laying in repairs un-reinforced precast concrete cable cover class LV, type-I, flat size 250mm x 150mm x 40mm laid in trenches all as specified. Make: MEHTAB /NATIONAL TILES |
| 19 | Laying only un-reinforced precast concrete cable cover class LV, type-I, flat size 250mm x 150mm x 40mm laid in trenches all as specified. Note :- Serviceable cable cover obtained here-in-after shall be reused. |
| 20 | Supply and Laying in repairs or fixing or passing through pipe, XLPE insulated ISI marked, armoured heavy duty electric cable with aluminium conductor 1100 volts grade cross sectional area 16 Sqmm 4 core including necessary connection and providing cable lugs as required includingdisconnection/taking down of existing cable all as specified.for Thane Area Make: Polycab/ Havell\"s/ KEI/ Gloster |
| 21 | Supply and fix air termination, single pointed aluminium rod 12mm dia and 300 mm long, including base plate complete with all screws, nut/bolts.Complete all as specified and directed for Thane Area |
| 22 | S & F test poing terminal block made of gun metal or phosphours bronze size 75 x75 x25 mm drilled and screwed including 3 nos . 8 mm dia 25 mm long hex. Head screw.Complete all as specified and directed at Thane Area. |
| 23 | S & F Aluminium strip 25 X 3.15 mm with saddles and supporting insulator fixed with non-corosive screw/nut, bolt etc. for roof conductors and down conductors above ground.Complete all as specified and directed by Engineer in Charge at Thane Area. |
| 24 | M&L for pre-cast cement concreate block of size 0.15M x0.15M x0.30 M for fixing of roof conductor Aluminium striptype C1 1:3:6 using 20mm graded stone aggregate in cement motor 1:4.complete all as specified and directed by Engr in Charge at Thane Area. |
| 25 | M&L for earthing complete with GI earth plate electrode 600x 600x 3 mm buried directly in ground with top edge of the plate not less than 1.5 mtrs below normal gound level and connected to earth test point by means of GI Strip of size 32x6 mm all as specified and shown in electric plate No 3 of MES SSR Part-I 2009 including earthwork, PCC chamber, CI cover, protection and watering pipe, funnel, mesh etc all as required at site and all as directed.Note: (1). 7.5 RM GI strip in deemed to be included in quoted rates beyond 7.5 RM strip shall be measured and paid separately (2) Rate quoted by the tenderer is deemed to include salt & Charcoal upto & above 450 mm top of GI earth plate.At Thane Area |
| 26 | M & L in repairs for servicing ofCentrifugal pump setof capacity 20 HP by opening end covers, greasing the bearings, replacing worn out nut, bolts, gasket, air release valve key, gland stuffing box male/ female set, Rubber bush and painting one coat ofsynthetic enamel paint, including writing/marking in 1\" size letters SM & MES No. for the following capacity of pumps:- |
| 27 | All as per Item No 26.00 above but Pump set 15 HP |
| 28 | All as per Item No 26.00 above but Pump set 5HP |
| 29 | Supply and fix in repairs/replacement of old unserviceable Cast iron tank coverwith MS strip /flat iron framework with all necessary fixing and locking arrangement nuts,bolts all as per BMC standards any required alteration to the tank for fixing ofnew CI covers all as specified and directed by the Engineer -in-Chief ofsizes:- 508mm dia. (weight of tank cover not less than 12 Kgs) |
| 30 | M&L for rewinding of electric motor 20 HP 3 phase 50 Hz 415 volt of following capacities complete all as directed and specified as under: (a) Disconnecitng, dismantling existing burnt widning from motor and rewinding complete with super enamled copper winding wire of matching gauge including all insulation material such as PVC insulated sheet, cotton tape sleeves varnish etc.(b) Transporting electric motor including loading/ unloading upto wksp and back to site. (c) Re-installing the same at the orignal locaition with proper alignmenent connecting and testing onload. (d) Replacement 2 Nos ball bearing for each motor of existing size/model. Make- SKF/NBC/TATA.(e) Replacement of winding terminal plate with brass stus,/ nut, bolt washer. |
| 31 | All as per Item No 30.00 For Motor 15 HP Cap |
| 32 | S&F in repairs the following component in existing LT Kiosks (Idoor/Outdoor) including disconnecting and taking down at different locations all as directed :-Voltmeter Digital type ,0-500 Volts of size 96x96mm. |
| 33 | All as per item No 32 but Ammeter Digital type of upto 400 amps capacity of size96X96mm. |
| 34 | M&L in repairs selector switch for voltmeter / Ammeter complete. |
| 35 | M&L in repairs Phase indicating lamp neon type complete with holder assy RYB phase complete. |
| 36 | M&L for supplying,hoisting and fixing rotational moulded polythylene water storage tanks (cylinderical vertical with closed top) as per IS12701-1996 (refirmed 2006) 0f under mentioned capacity with virgin food grade plastic,UV stabilised tank and lid,two layers protection with black outer layer for superior UV protection and white inner layer to see water level and tank condition including covers,hoisted and fixed in position all as specified in SSR Part-I including connecting the overflow drain out,Inlet and outlet pipes etc complete all as specified and as directed following capacity:-Capacity of 2000 Ltrs |
| 37 | capacity of 1000 Ltrs |
| 38 | Capacity of 500 Ltrs |
| 39 | S&F in repair of Transciever automation for the water level Detector and controller with the feature mentioned here under comprising of following:(a) S& F Transciever must communicate at a distance of 3km -5kms range with each module must have the LORA/GSM or suitable communication module ( long range antenna) must work above 500 mhz and each module shall have a processor module connecting to the sensor,with the facility that the processor module to sense the low level (10-20%) and high level of the water level (90-100%) so as to raise the hooter and communicate with the other hardware modules with antennas (b) S&F transducer module wiring through the D sub connectors (MIL industrial grade are to be used). All the wiring must be shielded optical co-axial cable for connection to flasher and hooter. Rates quoted are deemed to be included for suitable flasher and hooter. (c) S&F Hooter 12V/5 Amp with suitable converter or hooter suitable for 230V AC Supply must be provided standard suspended rust proof stand Note: All the NPT cable glands must be used for the sensor interface and MCB controller board.(d) S&F 12V flasher with suitable converter or flasher suitable for 230V AC Supply connected with suitable 3 Core Co axial cable suitably crimped nicomatic connector. Note: All the cables to be drawn through suitable medium grade conduit suirtably fixed with clamps. (e) S &F of LED display board with superior night vision display to be provided at the receiver station. (f) S&F controller Board confirming to IP 65 protection 3D printed with EMI/EMC compatible FE 32 material for the enclosure. Note: (a) One transmitter for over Head Tank and one receiver for Pump House .(b) Contractor has to visit the site before execution. Any cable required deemed to be included in quoted rate. No extra payment will be made on this account. |
| 40 | Supply ,Laying, fixing, connecting and testing in repairs Cast iron pipes with spigot and socket ends centrifugally cast.Class B, in any length laid intrenches, including supply and fixing all fittings, fixed to walls or laid in trenches / floors etc including taking out old u/s steel water tubing for the 100 mm bore complete all as specified and as directed , ISI marked. Make: kesoram,IISCO |
| 41 | Ditto all as per item No 40.00 above but 80 mm dia bore complete |
| 42 | Supply & fixing in repairs of joining CI/DI fittings for Spigot/Socket pipes such as bends of any radius and angle,collars,tapers,tail,pieces,tee pieces,caps and plugs suitable above from 20mm bore diato 100 mm all socket and spigot or side flanged including taking out old u/s CI/DI fittings complete all as specified and directed. |
| 43 | Supply and replace in repairs aviation light LED based operations on 230V,50Hz AC one medium intensity red obstruction light for fixing on top of overhead water storage tank,red steady or flashing 2000cd+25% at least three low intensity single onstruction lights on the middle of storage tank comprising ICAO Annex 14 volume I 2018 Chapter 6 and FAA 70/7460-1L,Red obstruction lighting for water storage tanks |
| 44 | M&L for sub mainwiringconcealed with twosingle core1.5 Sqmm PVC insulated FRLS multistrandedflexible copperconductorcable 660/1100 volts grade downin throughnon metalicPVC conduitwith and includingPVC insulated 1.5 Sqmsinglecore singlestrand copperconductoras continous earth wire in greencolour connected to commonearth dollyincluding taking down old unserviceable submain wiring complete all as specified and as directed Make:Havells/Finolex/Benlo/Anchor panasonicNote : 1.Two runs ofcable, one run of earth wire, one run of PVC casing capping will be measured and paid one unit. |
| 45 | M&L in repairs CT coils any capacity suitable for 1100volts, 50Hz, AC, supply complete. |
| 46 | Drilling and taping cast iron water mains (in position) for branch connections 15 mm bore of the internal dia. |
| 47 | S&F in repairs gunmetal gate or globe valve for 50 mm diameter, conforming to IS-778, Class 2, ISI marked, Copper alloy body, Test pressure (Hydrostatic) for shell 2.4 Mpa and Seat & back seat pressure of about 1.6 Mpa with maximum working temperature of about 45 °C with iron wheel head screwed at both ends for iron pipes or ferrule and fixing including necessary fittings like unions, check nuts, etc and any addition / alteration required for fixing, complete all as specified and as directed.Make :-Leader / Zoloto / Shakti |
| 48 | -Ditto- all as per Item No 47.00 above but of size 40 mm dia |
| 49 | -Ditto- all as per Item No 47.00 above but of size 25 mm dia |
| 50 | M & L for preparation of old painted / unpainted surfaces of any description, including taking out of parts / components under painting (if required) from any position / location as listed hereinunder and applying one coat of epoxy paint (with colour code maintained as per relevant IS) including marking with flow directions (of approved colour) complete al as specified and as directed by the Engineer-In-Charge. Make:- ASIAN/BERGER/APCOLITE Note: each job consist a LT Panel or Electric Motor/Sluice Valve/AMF panel etc |
| 51 | M&L for dismantling existing unserviceable sluice valve and supply and fix new sluice valve ISI marked IS-14846 PN 1.6 with iron operating wheel, flanged type rubber gasket, nut, bolts, washers, including any addition alteration. Fixing of new sluice valve of size 100 mm bore complete. |
| 52 | All as per item No 51.00 above but of 80 mm bore complete. |
| 53 | M & L for valve chamber of size 900 X 900 X 900 mm including necessary earth work in any type of soil, PCC foundation C-2 1:3:6 in base concrete, brick work in CM 1:6 with 10 mm thick plaster internally and 15 mm thick externally in CM 1:4, 6 mm thick MS cover with hinges and locking arrangement fixed to angle iron frame made-out of 40 X 40 X 6 mm MS angles complete with 2 coats of synthetic enamel paint over one coat of red oxide zinc chrome primer on all metal works including dosmantling the existing valve chambercomplete all as specified and directed by EIC. |
| 54 | Supply and Fix led emergency lamp of 8.5 Watt inverter bulb 6500K coolday light for all EM sub stationsmake Havells,Halonix,Wipro |
| 55 | M&L for collection andtesting of Water sample from source and User ends and test it in certified lab and submit result to the department.Note: One job of sample collection and testing consist of 1 sample of source water and 1 from user end |
| 56 | Supply, lay/fix, connect and testing steel water tubing, 25 MM medium grade, galvanised with screwed and socketed joints, in any length, including supply and fixing all fittings, ISI marked conforming to IS-1239 and fixed to wall/ceiling or laid in trenches/floors including taking up/down existy tubinging and connections complete all as specified and directed by the Engineer-in-Charge. |
| 57 | All as per item No 56.00 above but of 40 mm bore. |
| 58 | All as per item No 56.00 above but of 50 mm bore. |
| 59 | All as per item No 56.00 above but of 80mm bore. |
| 60 | All as per item No 56.00 above but of 100mm bore. |
| 61 | M & L for laying of LT XLPEinsulated, armoured heavy duty 1100 volt grade electric cable with aluminium conductorof size 2 Core 10 Sqmm in wall/Roof/steel Structures of buildings/Storgae Sheds etc complete all as specified and directed by Enginner incharge includingof cable glands, lugs & making all connections complete as required at site and as directed by Engr-in-Charge. Make - KEI/ Polycab/ Gloster/ Havells |
| 62 | M&L for sub mainwiring with twosingle core 6.0 Sqmm PVC insulated FRLS multistrandedflexible copperconductorcable 660/1100 volts grade downin throughnon metalicPVC casing capingwith and includingPVC insulated 6 Sqmmsinglecore singlestrand copperconductoras continous earth wire in greencolour connected to commonearth dolly all as specified and as directed.(Make :- PRESFIT/ PRECISION - Casing caping), (Make :- FINOLEX/ KEI/ POLYCAB - PVC Copper wire)Note : 1.Two runs ofcable, one run of earth wire, one run of PVC casing capping will be measured and paid one unit. |
| 63 | S&F in repairs electronic timers for star-delta starter three phase 415 volts including taking down old unserviceable starters complete. |
| 64 | M& L for load balancing of a LT Panel job consist of checking the load in three phases in different time period as 9.00 am,2.00 PM and 9.00 PM and distribute load to make load balance as possible |
| 65 | M&L in replacement from PVC to GI metal for fabricating a tank of GI metal sheet of 6mm thickness and to be stored 300 ltrs storage capacity for diesel and fitting inside DG Set room at thane station including pipe fittings for diesel tank. And painting with primer and synthetic enamel paint of 2 coats. |
| 66 | Supply and fix to make it portable type a 1 HP residential water pump self priming regenerative for pumping waterin case of emergency for supply of water in md accn and use in heavy rains to pump out water from EM sub station and plants.Complete all asspecified and directed. |
| 67 | Supply and Fix in repair strip rope of 50 metre for indoor/outdoor usedled light bright & even illumination with 270 lm/m light output and easy to cut after every 1 metre which helps better customization as per requirement IP65 rating to make rope weatherproof & More durable rated input voltage 220V AC-240 V ACof different colours WW,CDL,NW & blue. Make Havells LREHDCPFTN6W325,Wipro KED-03-07-65,Philips 582161-ww |
| 68 | Supply and Fix in repairPVC insulated copper wire 1.5 Sqmm 3 core cable complete all as specified and directed. Make- Havells,Polycab,KEI,Benlo |
| 69 | Supply and Fix in repairPVC insulated copper wire 2.5 Sqmm 3 core cable complete all as specified and directed. Make- Havells,Polycab,KEI,Benlo |
| 70 | Excavation in trenches not exceeding 1.50 m wide and n.exc 1.5 m in depth for foundation of poles, cable etc, not exc 10 sqm on plan and getting out in soft/loose soil including taking out brick protection etc complete all as specified and directed. |
| 71 | Returning, filling in, including spreading, leveling, wateringand well ramming in layers not exc 25cm thick complete all as specified and directed. |
| 72 | Removing excavated materials (soils) not exc. 50m and depositing where directed at a level not exc. 1.5m above the starting point complete all as specified and directed. |
| 73 | Supply and fix outdoortype vermin and weatherproof totally inclosed cubical type front operated, sufficient ventilation on sides cubicle type fabricated out of 3.15 mm thick CRCA sheet duly treated with seven tank process and painted epoxy powder coated siemens greycolour and with industrial type built in locking arrangement. The Panel indoor type cubical panel board IP 52 free standing floor mounted(CPRI approved manufacturers).The panel to be prewired with PVC insulated copper conductors appropriate current carrying capacity for connecting the incoming and out going MCCBs and MCBs. including disconnecting the LT panel and taking down the unserviceable cables and including MCBs.. Disconnecting the incoming and out going cable connection and dismantling the unserviceable conventional type industrial meter board and removing from site for further disposal and making LT UG cable connectioncomplete consist of following items:- Location Near OC Residence and Near Offrs Qtrs at Thane |
| 74 | (a)INCOMER (i)MCCB 160 Amps 415V 16 KA 4 pole - 1 No. Make: Havells/Legrand/indoasian(b) OUTGOING(i)MCCB 63 Amps \"C\" Series - 1 No. Make: Havells/Legrand/indoasian(ii)MCCB 63 Amps \"B\" Series - 2 No.Make: Havells/Legrand/indoasian(iii)MCB SPN 40Amps (B Series) - 02 Nos Make: Havells/Legrand/Indoasian (c) Electrolytic copper bus bar 125 Amps TPN with colour coded heat shrinkable sleeve(d) METERING & INDICATIONi) Digital VAF meter with selector switch & 3 Nos ofCT\"s -1 Setii) Indication lamps for R,Y,B phases -1 Set (Set of Three)(e) Internal wiring with suitable size of PVC insulated stranded copper conductor cable duly crimped with copper lugs & ferruled.(f)Manufacturer Name plate and Danger notice board writtenin regional language Hindi and English. Note 1. Layout & specification of panels shall be got approved by GE before placing the order. |
| 75 | Taking down copper/ aluminum point wiring surface type, concealed type, flame proof type(Light/Fan/Socket or power) complete including fixtures and fittings such as switches, ceiling roses, pendants, regulators, socket, light fitting etc.Removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces to walls floors etc. |
| 76 | Taking down of OldMCB DB of any size |
| 77 | M & L forpoint wiring with PVCinsulated unsheathed 1100 Volts grade single core multistranded copper conductorcable 1.5 Sqmm drawn in and including PVC casing-caping and accessories, fixed on wall / ceiling etc with neccessary fixing accessories andearth continuity conductor cable of 1.5 Sqmm size connected to common earth and earth dolly including 2 mm thick pressedsteel terminal boxes concealed in wall covered withlaminated sheet top cover 3 mm thick for mounting switches / sockets / fan regulators fixed with Cadmium platedmachine screwsall as specified for the following:(a)One light / fan / bellpoint controlled by one switch. |
| 78 | (b)One 5A 2pin/3pin socket out let multipurpose on the same board with other switches. |
| 79 | (c)One 5A 2pin/3pin switch socket out let multipurpose on independent Board. |
| 80 | All as per item No. 76above but wiring complete with 2.5Sqmm for 3 pin 15A socket multipurpose on independent board Note : A penalty of Rs 100 /- per point will be recovered from the contractor for not matching the disturbed surface with original. |
| 81 | Supply & Fix switch piano single poleflush type 5A,240 V one way. |
| 82 | Supply & Fix Bell push flush type 5 amp, 230 Volts |
| 83 | Supply & Fix switch socket combination 2 in 1 ,5Amps multipurpose flush type. |
| 84 | Supply & Fix switch socket combination 2 in 1,3 pin, 5 and 15 Ampsflush type universal. |
| 85 | Supply & Fix Ceiling rose surface bakelite three terminal, 240 V. |
| 86 | S & F in repairs Ceiling fan regulator electronic stepped type, AC, 230 Volts, flush type. |
| 87 | Supply and fix bell ding dong AC 230 V single pole. |
| 88 | S&F in repairs Surface, hanging and wall mounted batten (Double side connection) suitablefor LED tube 20/22 watts, 230 volts alongwith tube rod 22 watt (double side connection),including fixing mounting blocks 2 Nos, 15 mm MS conduit, 1.5 sqmm 3 core pvc insulated copper conductor cable including fixing arrangements complete all as specified and directed. Make :- BAJAJ/ PHILLIPS/ JAQUAR/ WIPRO |
| 89 | S&F in Repairs/Replacement Ultra brightglass LED tube rod 20 Watts(Single/Double side connection), 230 volts with very high efficacy with G13 lamp holder including fixing arrangements and taking down old unserviceable tube rod complete. Make :- BAJAJ/ PHILLIPS/ JAQUAR/ WIPRO |
| 90 | Supply and fixing in replacement of LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including provision with three core flexible copper conductor cable of suitable size and PVC square blocks complete all as specified and directed. Make :- BAJAJ/ PHILLIPS/ JAQUAR/ WIPRO |
| 91 | S&F in repair of building Security lightfitting 35 Watt made up of pressure die cast alluminium body with mid power LED as lighting sources and PC cover having Top opening separate driver compartment with IP66 protection and impact resistance of IK07including fixing arrangements and taking down old rusted bracket fittings completeall as per directed by Engr- in – charge.Make :- BAJAJ/ PHILLIPS/ JAQUAR/ WIPRO/ CROMPTON |
| 92 | M & L for GI steel tubing medium grade 40mm dia and length up to 1.5 meter bent to shape of offset angle upto 45degree for fixing of security /street light fittings including MS clamps made of 32mm x5mm flat iron, nuts , bolts, etc all as directed by Engineer in charge |
| 93 | Taking down carefully and Re-fixing of the same ceiling fan 1200mm sweepincluding provision of cable from ceiling nose/ conductor to fan and spray painting of ceiling fan with two coats of synthetic enamel paint, after preparation of surfaces, complete all as specified and directed. |
| 94 | Supply And Fix in repairs MCCB DB TPN 4Way double door125 Amps prewired suitable for Triple Pole 125 A MCCB as incomer with the following acessories, a) MCCB TP 125 A 25 KA 415 Volt - 1 Nosb) Bus bar, Din rail , Neutral linkMake -Havells/Indoasaian/Legrand/ABB/Schnider |
| 95 | Supply & Fix MCB DB SPN 2 way 240 volts Single door, including connecting up with existing cable with new lugs The DB Shall be of Make -Havells/Indoasaian/Legrand/ABB/Schnider |
| 96 | Supply & Fix MCB DB Double Door SPN 4 way 240 volts including connecting up with existing cable with new lugs. The DB Shall be of Make - Havells/Indoasaian/Legrand/ABB/Schnider |
| 97 | Supply & Fix MCB DB Double Door SPN 8 way 240 volts including connecting up with existing cable with new lugs. The DB Shall be of Make - Havells/Indoasaian/Legrand/ABB/Schnider |
| 98 | Supply & Fix MCB DB TPN 4 way 415 V double door with busbar including connecting up with existing cable with new lugs The DB Shall be of Make -Havells/Indoasaian/Legrand/ABB/Schnider |
| 99 | M&L for MCB SP, 240 volt, 5 to 32 Amps, 10 KA, C Curve, Make -Havells/Indoasaian/Legrand/ABB/Schnider |
| 100 | M&L for MCB SPN, 240 volt, 6 to 63 Amps, 10 KA, C Curve, Make -Havells/Indoasaian/Legrand/ABB/Schnider |
| 101 | M&L for MCB TPN, 240 volt, 40 to 100 Amps, 10 KA, C Curve,Make -Havells/Indoasaian/Legrand/ABB/Schnider |
| 102 | S&F single pole and neutral enclosure with a two pin and earthand metal cladplug socket complete with one single pole MCB 20 Amp 240 Volts complete all as specified and directed. Make - indoasain/Legrand/Havells |
| 103 | M&L for earthing complete with M.S. galvanized earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (earth pit not less than 2.25 M deep below normal GL) with top edge of the earth plate not less than 1.5M below normal GL, connected to galvanized earth lead wire 4 mm dia by means of bolts, nuts, check nuts & washers of GI or steel incl excavation, PCC (1:3:6) type C-1 chamber with RCC cover (1:2:4) type B0, 40 mm thick reinforced with 6 mm dia bar, 3 Nos. both way, 15 mm dia light grade GI protection pipe, funnel with wire mesh,watering pipe of size 20 mm dia med. grade, lugs, main Earthing lead upto 7.5 mtr incl. Charcoal dust, salt etc. all as shown in electrical plate No. 3 of SSR Pt-I, 2009 specification. |
| 104 | M&L for provn of Earthing complete with M.S. galvanized earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (earth pit not less than 4.25 M deep below normal GL) with top edge of the plate not less than 3.5M below normal GL, connected to Galvanized earth strip 32x6mm upto 7.5 mtr with protection pipe by means of bolts, nuts, check nuts & washers of GI or steel incl excavation, PCC (1:3:6) type C-1 chamber with RCC cover (1:2:4) type B0, 40 mm thick reinforced with 6 mm dia bar, 3 Nos. both way, 40mm dia light grade GI protection pipe, funnel with wire mesh,watering pipe of size 20 mm dia med. grade, lugs, main Earthing lead upto 7.5 mtr incl. Charcoal dust, salt etc. all as shown in electrical plate No. 5 of SSR Pt-I 2009 specification. |
| 105 | S&F GI strip size 25 x 4 mmall as directed including welding brazing and taking down of old copper strips as required at site |
| 106 | Note : A SUM OF RS 63,556.00 TOWARDS SCHEDULE OF CREDIT SHALL BE DEDUCTED TO ARRIVE THE CONTRACT SUM |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail