| 1 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth and not exceeding 10 sqm on plan and getting out in soft/loose soil for laying of cables, etc. complete all as specified and as directed. |
| 2 | Returning, filling in, including, spreading, levelling, watering and well ramming in layers not exceeding 25 cm deep as in hard/soft soil complete all as specified and as directed. |
| 3 | Removing excavated materials to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point in soil including spreading in low lying area and leveling complete all as specified and as directed. |
| 4 | M&L for cutting existing road/hard standing not exceeding 45x50 cm in wide & depth getting out excavated material for laying GI tube, returning filling & well rammaing watering finish suraface 10 cm from top including provision of PCC 1:3:6 for repairing, including removal of surplus soil all as directed. |
| 5 | M & L for PCC 1:3:6 in round/ square shape as per site requirement of thickness not less than 3\" suitable for fixing of cast iron tank cover complete all as specified and directed. |
| 6 | Taking up or down steel tubing and connections including cleaning and setting aside for refixing or as schedule of credit, etc complete all as specified and as directedfor the 20 mm borepipes including necessary staging/scaffolding as required. |
| 7 | Ditto all as per item No 6 above but 25 mm dia bore complete |
| 8 | Ditto all as per item No 6 above but 40 mm dia bore complete |
| 9 | Ditto all as per item No 6 above but 50 mm dia bore complete |
| 10 | Ditto all as per item No 6 above but 80 mm dia bore complete |
| 11 | Ditto all as per item No 6 above but 100 mm dia bore complete |
| 12 | Supply & Layingfixing, connecting and testingsteel water tubing, medium grade, galvanised, with screwed and socketed joints, in any length, including supply and fixing all fittings, fixed to walls or laid in trenches / floors etc complete all as specified and as directed for the 20 mm bore, ISI marked. Make-: Tata/ Jindal/ BST/ Oswal |
| 13 | Ditto all as per item No 12 above but 25 mm dia bore complete |
| 14 | Ditto all as per item No 12 above but 40 mm dia bore complete |
| 15 | Ditto all as per item No 12 above but 50 mm dia bore complete |
| 16 | Ditto all as per item No 12 above but 80 mm dia bore complete |
| 17 | Ditto all as per item No 12 above but 100 mm dia bore complete |
| 18 | Supply and fix ISI Marked UPVC Pipe size 50 mm nominal dia,pressure pipe Schedule 80 with all connected acessories like UPVC bend,Tees,Unions,Sockets etc for each 3 mtr length of Pipe & solvent to join it all as specified and as directed.Make:Supreme/Dutron/Finolex/Duplon |
| 19 | Ditto all as per item No 18 above but 40 mm dia bore complete |
| 20 | Ditto all as per item No 18 above but 25 mm dia bore complete |
| 21 | Supply, lay/fix, connect and testing DI water tubing of 80 mm bore with spigot and socket ends class K-9 conforming to IS:8329/2000 suitable for rubber tyton joint including taking out old damaged CI main with fitting burningout joints and recovering lead complete etc as specified and directed. |
| 22 | Ditto all as per item No 21 above but 100mm dia bore complete |
| 23 | Ditto all as per item No 21 above but 150mm dia bore complete |
| 24 | Ditto all as per item No 21 above but 200mm dia bore complete |
| 25 | M & L for DI fittings class K-12 conforming to IS:9523/2000 upto 200 mm dia of any type, size, such as bend, tapper, tail piece, tee piece, cross etc complete all as specified and directed. |
| 26 | S&F in repairs gunmetal gate or globe valve for 65 mm dia, conforming to IS-778, ISI marked, with iron wheel head screwed at both ends for iron pipes or ferrule and fixing including necessary fittings like unions, check nuts, etc and any addition / alteration required for fixing, complete all as specified and as directed. Make :- Kirloskar, Upadhaya , Leader, Zoloto. |
| 27 | Ditto all as per item No 26 above but 50 mm dia bore complete. Make :- Kirloskar, Upadhaya , Leader, Zoloto. |
| 28 | Ditto all as per item No 26 above but 40 mm dia bore complete. Make :- Kirloskar, Upadhaya , Leader, Zoloto. |
| 29 | Ditto all as per item No 26 above but 25 mm dia bore complete. Make :- Kirloskar, Upadhaya , Leader, Zoloto. |
| 30 | Ditto all as per item No 26 above but 20 mm dia bore complete. Make :- Kirloskar, Upadhaya , Leader, Zoloto. |
| 31 | Taking out sluice valves of size 80 mm to 100 mm and transporting to workshop for lathe work by refacing, regrinding, metalling and refixing back at site to match with standard size and refixing in position including replacing of worn out gland packing/washers /nuts/ bolts etc for the following size sluice valves.Note : Rate quoted is inclusive of cost of spare parts. |
| 32 | Ditto all as per item No 31 above but for size 150 mm to 200 mm dia bore complete. |
| 33 | S&F sluice valve 80 mm bore, cast iron body, flanged and drilled end, conforming to IS-14846, ISI marked, Class PN 1.6 including all joints with rubber or fibre board, gaskets, bolts and nuts, washers, iron wheel including taking up / down old unserviceable valves from any position and any addition / alteration for fixing required complete all as specified and as directed. Make-: Kartar/ Kirloskar/ Upadhyay |
| 34 | Ditto all as per item No 33 above but 100 mm dia bore complete. Make-: Kartar/ Kirloskar/ Upadhyay |
| 35 | Ditto all as per item No 33 above but 150 mm dia bore complete. Make-: Kartar/ Kirloskar/ Upadhyay |
| 36 | M&L for run lead joints to CI spigot and socket pipes of 80 mm bore and fittings including cleaning the joints, re-aligning the pipeline properly as required, cocking and jointing with old pig lead, including any addition / alteration for fixing required, testing pipelines for any leakage, making good any disturbed / damaged pipeline / parts etc, complete all as specified and as directed Note-: Necessary excavation and earthwork will be measured and paid separately |
| 37 | Ditto all as per item No 36 above but 100 mm dia bore complete |
| 38 | Ditto all as per item No 36 above but 150 mm dia bore complete |
| 39 | Fabricate supply and fix valve chamber covers made out of suitable size MS angle/MS plate/flat/rod,hinges, locking arrangement including painting with two coats of synthetic enamel paint over one coat of red oxide primer including removing existing unserviceable rusted cover all as directed. |
| 40 | Supply and fix in replacement ladder height 10 feet max, steps on every 01 feet made of angle iron of size 50x65x5 mm thickfor sump including taking down old rusted iron ladder complete all as specified and directed. |
| 41 | Dismantling existing PVC water storage tanks and Supplying, hoisting and fixing rotational moulded polythylene water storage tanks (cylindrical vertical with closed top) of 500 Litres capacity with and including covers, hoisted and fixed in position all as specified in SSR Part-I including connecting the overflow drain out, inlet and outlet pipesetc complete all as specified and as directed Make-: Sintex/ Plasto/ Supreme |
| 42 | Ditto all as per item No.41 above but 1000 litres capacity |
| 43 | Ditto all as per item No.41 above but 2000 litres capacity |
| 44 | Ditto all as per item No.41 above but 3000 litres capacity |
| 45 | Supply and fix in repair 50 mm bore PVC Ball valve ISI markedhigh presssure of PTMT with epoxy coated aluminium rod and high density plastic ball screwed for iron pipe and fixed. Make -: Prayag/Shakti |
| 46 | Ditto all as per item No.45 above but 40mm dia bore complete. Make -: Prayag/Shakti |
| 47 | Ditto all as per item No.45 above but 25mm dia bore complete. Make -: Prayag/Shakti |
| 48 | Ditto all as per item No.45 above but 20mm dia bore complete. Make -: Prayag/Shakti |
| 49 | M& L for draining out water complete cleaning & removing accumulated sludge/ dirt, scales from bottom of walls/ ceiling /top of slab and from mouths of circulating pipes of service tanks/ PVC tanks of capacity not exceeding 500 litres, located on roof of bldgs and disinfecting the tank using bleaching powder to make the tank bacteria free and depositing the rubbish in low lying areas of defence land, writing by stencil date of cleaning of tank with white synthetic enamel paint on black ground \" cleaned on (date) due on (date) complete all as directed. |
| 50 | All as per item No 49 above but capacity of tank exceeding 500 litres but not exceeding 1000 ltrs complete. |
| 51 | All as per item No 49 above but capacity of tank exceeding 1000 ltr but not exceeding 2000 litres complete. |
| 52 | M&L for petty repair works by replacement of defective pipe fittings such as elbows, sockets, tees, unions, nipples, or other minor accessories, including any necessary additions or alterations to the existing pipeline, cutting, threading, fixing in position, testing, and making good the disturbed surfaces, complete all as specified and directed by the Engineer-in-Charge. |
| 53 | Taking out old/ unsv cast iron/ MS tank cover from RCC tank including dismatlling of RCC base support/ MS or cast iron frame and supplying & fixing cast iron tank cover in round shape of size 21 inches internal dia, with proper anchor in PCC with nut, bolts, anchor fastner etc with locking arrangement etc complete with two coats of black bituminous paint (drinking grade) for 1000 ltr/ 2000 ltr/ 3000 ltrall as specified and as directed Note-: Plastering and PCC work shall measured and paid seperately |
| 54 | Dismantling of existing PVC water storage tank covers and Supplying and fixing PVC tank cover round shape of suitable size as per ground requirement with locking arrangement and fixed in position etc complete all as specified and as directed |
| 55 | M & L for Rendering 15 mm thick on fair faces of brick work or concrete surfaces cement plaster 1:6, all as specified and directed. |
| 56 | Supply and install of installation display board of size 4\"\" x 3\" made out of ECO printing lamination and mounting on ACP sheet board with back side MS channel frame and MS 2 pole 50mm square pipe with black paint, including PCC foundation complete all as specified and directed.Note-: Detail to be writing on board shall be as per site/ installation requirement. |
| 57 | Supplying, fixing, jointingandtesting non-return valve suitable for GI tubing of size 80 mm bore size, (ISI Marked) both ends flanged and drilled for jointing including twoflangejointsandjointing material such as nuts, bolts washers rubberpackingetc including taking down complete all as specified and as directed. Make :- Kirloskar, Upadhaya , Leader, Zoloto. |
| 58 | Ditto all as per item No. 57 above but 50 mm dia bore complete all as specified & directed. |
| 59 | Supplying, fixing, jointing and testing non-return valve (Forged brass swing type check valve) suitable for GI tubing of size 40 mm bore complete all as specified & directed. Make :- Leader, Zoloto |
| 60 | Supplying, fixing, jointingandtesting non-return valve (Forged brass swing type check valve) suitable for GI tubing of size 25 mm bore complete all as specified & directed. Make :- Leader, Zoloto |
| 61 | S & F foot valve of size 65 mm dia cast iron body, ball type, with flanged and drilled ends and synthetic rubber coated MS ball, conformimg to relevant IS, ISI marked, including all joints, gaskets, bolts and nuts, washers, including taking up/down old unserviceable valves from any position and any addition/alteration for fixing required complete all as specified and directed by the engineer in charge. Make : Kirloskar or equivalant or as approved by GE. |
| 62 | M & L for dismantiling the existing valve chamber of size 900 X 900 X 900 mm including necessary earth work in any type of soil, PCC foundation D-2 1:3:6 in base concrete, brick work in CM 1:6 with 10 mm thick plaster internally and 15 mm thick externally in CM 1:4, 6 mm thick MS cover with hinges and locking arrangement fixed to angle iron frame made-out of 40 X 40 X 6 mm MS angles complete with 2 coats of synthetic enamel paint over one coat of red oxide zinc chrome primer on all metal works including necessary excavation earth workall plastered surfaces of valve chambers complete all as specified and directed by Engr-in-Charge. |
| 63 | Supply only Bleaching powder grade -I ISI marked having stable available chlorine % by mass minimum 35% as per IS 1065,1971 and packed in 25 Kg bag complete all as specified and directed. Make : Vikram or equivalent as approved by GE. |
| 64 | Lifting the submersible pump of 05 Horse Power from bore well,including flange/socket joints of delivery pipe, dismantling the flanged joints, lowering the submersible pump after repairing, by tightening the flanged/socket joints of column pipe, re-fixing of existing safety bucket with steel rope including taking down to workshop & rewinding and complete to make it operational /functional all as per specified and as directed. |
| 65 | Supply only Calcium hypo chlorite 65% -70% chlorine content granular based water disinfectent in sealed containerscomplete all as specified and as directed.Make:- 1.Aqufit manufactured by Sree Rayalaseema Hi strength Hypo Ltd.2. Puri chlor manufactured by Sree Rayalaseema Hi strength Hypo Ltd. / M/s Ravi Enterprises / M/s Potter & Watts (Traditional products). Brands having pan india availability, acceptability & being manufactured /processed in open market termed as traditional products .The brands /makes must have certified by All India Institute of Hygenic & Public Health. 3. Best available in the market |
| 66 | S&F in repairs chlorine testing KIT with colored sample complete with all testing fitment and OT solution in rexine finish box.Make :- Techno Aqua Tech Pvt. Ltd./ Ion Exchange India/ Thermax/ Wipro |
| 67 | S&F in repairs chloroscope (Chlorine & PH test kit) for estimation of residual chlorine in water comprises of Plastic box,two tube, Droper and colour filter for colour estimation.Make :- Techno Aqua Tech Pvt. Ltd./ Ion Exchange India/ Thermax/ Wipro |
| 68 | S&F in repairs Water Quality TDS tester with ATC, Digital and Pocket type,Range : TDS 0-999 PPM(Mg/L) Model No :- ATDS0016. Make :- Techno Aqua Tech Pvt. Ltd./ Ion Exchange India/ Thermax/ Wipro |
| 69 | Supply and replace in repairs of New water meters confirming to ISO 4064:2005,including MS flange,nut bolts,rubber packing and flange thickness conforming to IS:7322-1985 and flange dimension conforming IS: 1538-1993 of size 100 mm dia suitable for installation on MS/DI/CI pipe line, including taking out old u/s water meter complete all as directed by Engineer in Charge. Make: Chambal/Kranti/Capston/Dashmesh/Accuflow or equivalent. Note: (a) Cleaning and grinding by 3 core welding of the pipe outside welding of the joint including cost of gas oxygen acetylene,welding machines, skilled and semi skilled workers internal lighting arrangements and all other incidental and operational charges etc.(b) The scope of work is inclusive of following and rate quoted is deemed to be inclusive in the amount quoted |
| 70 | M&L for complete rewinding and overhauling of 40 HP, 3-phase, 50 Hz, 415V electric motor, including disconnecting and dismantling existing burnt winding, rewinding with super-enameled copper wire of appropriate gauge using standard insulation materials (PVC sheets, cotton tape, sleeves, varnish, etc.), transportation of motor to and from workshop including loading/unloading, replacement of 2 Nos. ball bearings (make: SKF/NBC/TATA), renewal of terminal plate with brass studs, nuts, bolts, and washers, reinstallation at site with proper alignment, connection, and load testing, along with dismantling, cleaning, and overhauling of the coupled centrifugal/monoblock pump including replacement of defective components such as impellers, bushes, thrust bearings, clutch system, bowl assembly, pump shaft, and other unserviceable parts as required, followed by reassembly, alignment, commissioning, and on-load testing to ensure full operational efficiency, complete all as specified and directed. |
| 71 | All as per Item No 70 For Motor 25 HP Cap |
| 72 | All as per Item No 70 For Motor 15 HP Cap |
| 73 | All as per Item No 70 For Motor 10 HP Cap |
| 74 | All as per item No 70 for Motor 7.5/5 HP capNOTE: Quoted rates shall be deemed to include one year warranty formotors after rewinding and commissioning. |
| 75 | M & L for preparation of existing painted steel pipes, including fire main lines, fire hydrant stand posts, and all exposed GI pipes / CI pipes/DI pipes, by removing the deteriorated paint layer through manual or mechanical scraping using wire brushes, scrapers, or sandpaper. The surface shall be thoroughly cleaned to remove dust, grease, rust, or any contaminants, ensuring an even, bare metal or sound substrate ready for painting and apply one coat of synthetic enamel paint, ensuring uniformity in thickness and adherence as per manufacturer specifications shall comply with IS standards, apply a compatible metal primer on bare metal sections before enamel application to enhance corrosion resistance and paint adhesion complete as per specifications and as directed by the engineer-in-charge. . Make :- Asian, Berger, Apex, or Nerolac |
| 76 | Material and labour for preparingold painted steel pipe surface such as Rising pipe (Red), Delivery pipe (Blue), Overflow pipe washout pipe (Yellow) etc and applying one coat of synthetic enamel paint include the removal of existing deteriorated paint layers using suitable mechanical or manual methods such as scrapers, wire brushes, or sandpaper, ensuring a clean and smooth substrate complete all as specified and as directed.Note:- (i)The arrangement of necessary equipment, such as ladders, scaffolding, or cranes, for accessing and working on pipes, shall be managed and provided by the contractor, and the cost of such arrangements is included in the quoted rate. |
| 77 | M & L for preparation of old painted / unpainted surfaces of any description,including taking out of parts / components under painting from any position / location as listed under GE (NW) Mankhurd and applying two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and as directed by Engineer-In-Charge for the following capacity of electric motor.(a) Electric motor pump set upto 40 HP capacity |
| 78 | (b) Electric motor pump set upto 15 HP capacity |
| 79 | (c) Electric motor pump set upto 10 HP capacity |
| 80 | (d) Electric motor pump set upto 7.5 HP capacity |
| 81 | Dismantling the Decrin Dozing pump, cleaning, repairing, overhaulingreplacement of all unserviceable parts, nut, bolts,impellars, bushes, thrust bearing, clutch system, bowl assembly and repairing/replacement of pump shaft and re-assembling, commissioning and testing to make it operational / functionalcomplete all as specified and asdirected. |
| 82 | M&L for electric water pump (self priming) of capacity 0.5 HP, 220V, 50 Hzhead range 06 to 24 m, insulation class B conforming to Crompton Mini force II commissioning and testing to make it operational / functionalcomplete all as specified and asdirected. |
| 83 | Maint/Cleaning ofPump house stations inside and out side area andremoving of creepers and vegetation raised along with water supply installation including surface dressing around the E/M installation not less then 3 mtrfrom out side fencing and removing the all waste material from site and Chemical spray inside and out side area of Sub station.Note:- T & P will be arreanged by contractor |
| 84 | Supply and Fixing industrial type pressure gauge made out of SS 304 material, SS sipon shall be factory insulated with closed cell elastomeric insulation in tubing form, pressure gauses shall be factory fitted with a ball valve complete upto 50mm , all as specified and directed. |
| 85 | Collecting water sample in clean bottle from location as directed for testing of physical test, chemical test, as per IS-10500-1991 from any government recognized institute and submitting test report complete. |
| 86 | M&L PVC Insulated sheathed 4 sqmm 3 core & PVC round sheathed Multicore bright eletrolytic annealed aluminium conductor flexible industrial power cables for working voltage upto and including 1100 Volts.Make :RR Kable / Polycab / Finolex / Havells |
| 87 | M&L PVC Insulated sheathed 6 sqmm 3 core & PVC round sheathed Multicore bright eletrolytic annealed aluminium copper conductor flexible industrial power cables for working voltage upto and including 1100 Volts.Make :RR Kable / Polycab / Finolex / Havells |
| 88 | Supply and laying in repairs, 2 x 1.5 sqmm PVC insulated and PVC sheathed copper cable, laid in trenches on walls / drawing through pipe, surfaces, cable ducts etc complete including taking down old unserviceable cable as required at site and as directed by the Engineer-in- charge.Make: Polycab / KEI / Anchor / Gloster / Panasonic |
| 89 | Supply and laying in repairs, 4 x 1.5 sqmm PVC insulated and PVC sheathed copper cable, laid in trenches on walls / drawing through pipe, surfaces, cable ducts etc complete including taking down old unserviceable cable as required at site and as directed by the Engineer-in- charge.Make: Polycab / KEI / Anchor / Gloster / Panasonic |
| 90 | Supply and layingin repairs, 6 x 1.5 sqmm PVC insulated and PVC sheathed copper cable, laid in trenches on walls / drawing through pipe, surfaces, cable ducts etc complete including taking down old unserviceable cable as required at site and as directed by the Engineer-in- charge.Make: Polycab / KEI / Anchor / Gloster / Panasonic |
| 91 | M&L XLPE insulated, armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross- sectional area 16sq. mm, 4 Core on walls, surfaces, cable ducts etc complete.Make :RR Kable / Polycab / Finolex / Havells |
| 92 | Supply and Laying in repairs passing through pipe, XLPE/PVC insulated, armoured heavy duty electric cable with aluminium conductor 1100 volts grade cross sectional area 35 Sqmm 3.5 core including necessary connection and providing cable lugs as required all as specified. Make :- FINOLEX/ KEI/ POLYCAB/HAVELLS |
| 93 | M&L XLPE insulated, armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross- sectional area 25 sq. mm, 3.5 Core on walls, surfaces, cable ducts etc complete.Make :RR Kable / Polycab / Finolex / Havells |
| 94 | M&L for cleaning of balancing tank of swimming pool of capacity 1,00,000 ltrs, from bottom and side walls by scrubbing with wire brush and removing mud collected at the bottom all as directed by Engr-in-charge. |
| 95 | M&L for provn of Earthing complete with M.S. galvanized earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (earth pit not less than 2.25 M deep below normal GL) with top edge of the plate not less than 1.5M below normal GL, connected to Galvanized earth strip 32x6mm upto 7.5 mtr with protection pipe by means of bolts, nuts, check nuts & washers of GI or steel incl excavation, PCC (1:3:6) type C-1 chamber with RCC cover (1:2:4) type B0, 40 mm thick reinforced with 6 mm dia bar, 3 Nos. both way, 40mm dia light grade GI protection pipe, funnel with wire mesh,watering pipe of size 20 mm dia med. grade, lugs, main Earthing lead upto 7.5 mtr incl. Charcoal dust, salt etc. all as shown in electrical plate No. 3 of SSR Pt-I 2009 specification. |
| 96 | S&F GI earth strip of size 32mm x 6mm including cutting, bending, welding, brazing, jointing, and fixing in position as required, taking down existing strip where applicable, and complete all as directed at site by Engineer-in-Charge. |
| 97 | Supply & Fix copper stripof size 20 X 3 mm duly covered,fixed on porcelain insulators along the wall / roof / ceiling etc complete all as directed.Note : (i)Cost of Porcelain insulators and screw shall be of non-corrosive type and cost is deemed to be included in the quoted rate of the job. (ii) Gap for fixing of support insulator shall not be more than 35cm from one onother. |
| 98 | M & L for earthing chemical with copper plated 50 mm dia pipe 3 mtr long(100 microns) including Electrodite 50 Kg buried directly in ground including earth bore hole work (earth bore not less than 3 Mtr deep below normal ground level and connected to copper earth strip of size 20×3 mm by means of copper nuts bolts with washers and connected as per following specifications completeall as directed by Engineer-in-Charge.(a) Product Model: ASEEL 19 CP, 3 meter long (Copper Plated) – 100 microns .Fast Electrode, Model FE 80 mm 3 mtr (Pure Copper Single Pipe), Outer Dia is 80 mm with a wall thickness of 2 mm, Inner Dia is 26 mm with a wall thickness of 2.6 mm, Overall Length is 3000 mm,External Corrosion Protection: Copper Plated (100+ microns), Internal Corrosion Protection: In addition to Copper Plated (100+ microns), a ground breaking corrosion resistant Crystalline Conductive Compound is filled and compacted in the cavity within the pipes to enhance the electrodes performance. Conforms to IS: 3043 - 1987 i.e., Code Of Practice For Earthing (+ 10%) variations in dimensions applicable. (b) Electrodite backfill: Fast Electrode Earth Enhancement Compound, Manufactured using Eco - Friendly minerals, Blended homogeneously with conductive carbon(s), Resistivity: < 5 ohm-metre (In ideal moist conditions); > 5 ohm-metre (Dry Conditions), Ph Value: 7.0 - 8.5, High water retention capacity, Hygroscopic, Ionic & Electronic conduction, Swells when it comes in contact with water thereby engaging constant contact between the electrode surface & soil which is a crucial aspect in the performance of an earthing system. Packing Size : 2 Bags of 25 kilograms,Recommended for normal soil conditions. Conforms to IS : 3043 – 1987.(c)Installation of earthing with bore well machine complete for bore exceeding upto 4.5 meter below ground level complete all as specified and directed by Engr-in-Charge. |
| 99 | Supply and Fix in replacement of Contactor Three Pole 415 volts 25 Amps AC 3 Rating,Conforming to Type MNX 25 & Cat No - CS94110 of L & T or Equivalentt from Schnider Electric, ABB including add on Blocks suitable for driving POWER Capacitors, including making addition/Alternation to existing Wiring/circuit system |
| 100 | All as per item No 100 above but Contactor Three Pole 415 volts 32 Amps AC 3 Rating Conforming to Type - MNX 32 & Cat no - CS94111 of L & T or equivalent from Schnider Electric, ABB/ C&S |
| 101 | All as per item No 100 above but Contactor Three Pole 415 volts40Amps AC 3 RatingConforming to Type- MNX - 40 & Cat no - CS94190of L & T or equivalent from Schnider Electric/ABB/ C&S |
| 102 | All as per item No 100 above but Contactor Three Pole 415 volts50 Amps AC 3 Rating Conforming to Type-MNX - 50 & Cat noCS-97075of L & T or equivalent from Schnider Electric/ABB/ C&S |
| 103 | All as per item No 100 above but Contactor Three Pole 415 volts70 Amps AC 3 Rating Conforming to Type- MNX - 70 & Cat no - CS-97076of L & T or equivalent from Schnider Electric/ABB/ C&S |
| 104 | M & L in repairs of insulating mats 2.5mm thick made of elastometer (a generic term that includes rubbers,latex and elastometric compounds that may be natural or synthetic or a mixture or a combination of both) for use as floor covering for the protection of workers on ac and dc installations with the system voltages up to 11 KV ac and 240 V dc and as per cl 5 of IS 15652 latest class B Cat II of size 1mX2m including taking out old u/s insulating mats complete with relevant test reports and fixing on floor with suitable adhesives all as specified and as directed.Note : The mat should be permanently pasted with the held of suitable adhesive/resin. All joints and corners shall be filled/covered with insulating material of matching colour. Matching colour and matching designed tapes should be used to maintain an aesthetic look of the installation. |
| 105 | S& F in repairs Electric shock treatment chart printed on AO size paper duly plastic laminated and fixed inside a wooden/PVC photo frame of 50 mm width with 3 mm sheet glass and 6 mm plywood backing and suitable hanging arrangement to wall with hooks/steel chain etc.including taking down old unserviceable one complete all as specified and directed. |
| 106 | S& F in repairs First aid chart printed on AO size pepar duly plastic laminated and fixed inside a wooden/PVC photo frame of 50 mm width with 3 mm sheet glass and 6 mm plywood backing and suitable hanging arrangement to wall with hooks/steel chain etc.including taking down old unserviceable one complete all as specified and directed. |
| 107 | Supply & Fix in repair fully automatic star delta starter suitable for 25 HP, 440 volt, 3 Ph Elect Motor with Single Phase Protection feature conforming to IS -13947 after taking down old unserviceable one anf fixed to the same location by making electrical connection properly complete all as specified and as directed. Cat No: SS91855 of Make-L&T or equivalent to C & S / Schneider / CROMPTON |
| 108 | All as per item No 107 above but for eletrical motor 10 HP,Model MK1 FASD of L& T Make, CAT Pat: SS96254 or equivalent to C & S / Schneider / CROMPTON |
| 109 | All as per item No 107 above but for eletrical motor 40 HP,Model MK1 FASD of L& T Make, CAT Pat: SS94366 or equivalent to C & S / Schneider / CROMPTON |
| 110 | S&F in repairs Direct on line (DOL) starter in sheet steel enclosure AC 3 phase 415 volt 50 Hz suitable for 5/7.5HPcomplete. |
| 111 | Cutting/clearing and removing the vegetation/bush/creepers growth any nature/type around/on the electric panel/feeder pillar box/busbar chamber so as to keep clean the area for easy access to carry out repair/maintenance works in electric panel/feeder pillar box/busbar chamber etc,removing from site and throwing out at a place where directed at distance not exceeding 250mtr away complete all as specified and as directed. |
| 112 | S & F in repair/replacementof security light fitting/Building security lightLED type 120 watts, THD<10%, Efficacy 110 Lm/w with Pressure die cast aluminium housing with hight power LED as lighting source and lens embedded PC cover having TOP OPENING seerated driver compartment with IP 66 protection and impact resistance of IK07 with 10KV built-in surge protection device etc including taking out old u/s security lights all as directed by Engineer in charge. Make:- BAJAJ/ PHILLIPS/ JAQUAR/ WIPRO/ HAVELLS. Location : TS Mahul |
| 113 | M&L for Automatic water supply system installed at \"A\" camp pump house, Nausena Baugh and Nofra Pump house under GE (NW) Mankhurd. The system comprises maintenance / servicing / repairs as required of all the sub systems viz. RTU based control panels (with all the accessories), Motorised valves, Pressure Switches, Ultrasonic Level transmisters, Pressure transmitter, Solenoid valves,GSM Modem,Trasducers, CTs, MIMIC panel etc. (with all its accessories), Personal computer, Printer, UPS, Mimic Panel and breakdown maintenance as and when required complete all as specified and directed by Engr-In- Charge. |
| 114 | Supply & fix in repairs of magnetic level sensor arrangement along with all necessary installation accessories. Make: RDS / MAHALAXMI / CRYSTAL/UNIVERSAL |
| 115 | Supply & fix in repairs of 10 mm dia Brass / SS, direct Acting / Diaphragm tpye pilot operated Solenoid Valve for air release with manual bypass arrangement along with all necessary installation accessories like gate valve, barrel piece, double nipple, elbows/bends etc suitable for line pressure of 6 kg/cm2 Make: ROTEX / AVCON / ASCO |
| 116 | Supply & fix in repairs of Pressure Switch along with all necessary installation accessories like GI barrel piece, double nipple etc. having range 0-6 kg/cm2. With Weather proof enclosure. Make: INDFOSS / DANFOSS / SWITZER |
| 117 | Supply & fix in repairs of solenoid / Motorized valve suitable for 20 mm GI pipe for priming of pump including suitable bypasswith necessary GI pipe and fittings like gate valve, barrel piece, double nipple, elbows / bends etc with following specifications: Size: 20 mmPressure rating: 6 kg/cm2Make: AVCON/ ROTEX/ ASCO/JOHNSON CONTROL |
| 118 | Supply & fix in repairs of Ultrasonic Level Transmitter at Pure Water Sump ( for measurement of level in Pure Water sump )Range : 0-5 metresAccuracy : 0.5 % minimum Supply Voltage : 24V dc Output : 4-20 mA Make :Banner / ABB/ SBEM / PEPPERL FUCH |
| 119 | Supply and fix in repairs replacement Electric motor suitable for actuator for 150 mm dia.Motorized Butterfly valve (20 Kg/N to 30 Kg/N) complete all as specified and as directed. Make :UNIVERSAL /VAT/ROTORK |
| 120 | Supply and fix in repairs replacement Electric motor suitable for actuator for 100 mm dia.Motorized Butterfly valve (20 Kg/N to 30 Kg/N) complete all as specified and as directed. Make :UNIVERSAL /VAT/ROTORK |
| 121 | Supply and fix in repairs replacement Electric motor suitable for actuator for 80 mm dia. Motorized Butterfly valve (20 Kg/N to 30 Kg/N) complete all as specified and as directed. Make :UNIVERSAL /VAT/ROTORK |
| 122 | Supply and fix in repairs replacement Printed Circuit Board (PCB) for Motorized Butterfly valve of size 50,80,100,150 mm complete all as specified and as directed. Make :UNIVERSAL / VAT / ROTORK |
| 123 | Supply and fix in repair replacement of PLC with 60 Digital Input , 30 Digital Output, 16 Analog Input , 4 Analog Output and Expandable upto 192 DI / DOs, 2 Nos. RS 485 communication port, 1 Nos. Ethernet communication port, MODBUS compatiblity, Future expandablity to HARD Communication to identify instrument fault over SCADA as smart.MAKE:- SCHNIEDER / SIEMENS / ABB |
| 124 | M&Lin repairs for 24 Hrs240 V FM1 Quartz type Time switches astronomical type (Having longitude and latitude of Indian cities in memory) timer for controlling street lights contactors complete all as directed by Engr-in - Charge .Make :-Legrand/ L&T/Indo Asian as approved by GE |
| 125 | M & L for DI fittings class K-12 conforming to IS:9523/2000 upto 200 mm dia of any type, size, such as bend, tapper, tail piece, tee piece, cross etc complete all as specified and directed. |
| 126 | M&L PVC Insulated sheathed 4 sqmm 3 core & PVC round sheathed Multicore bright eletrolytic annealed aluminium conductor flexible industrial power cables for working voltage upto and including 1100 Volts.Make :RR Kable / Polycab / Finolex / Havells |
| 127 | M&L PVC Insulated sheathed 6 sqmm 3 core & PVC round sheathed Multicore bright eletrolytic annealed aluminium copper conductor flexible industrial power cables for working voltage upto and including 1100 Volts.Make :RR Kable / Polycab / Finolex / Havells |
| 128 | M&L XLPE insulated, armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross- sectional area 16sq. mm, 4 Core on walls, surfaces, cable ducts etc complete.Make :RR Kable / Polycab / Finolex / Havells |
| 129 | Supply and Laying in repairs passing through pipe, XLPE/PVC insulated, armoured heavy duty electric cable with aluminium conductor 1100 volts grade cross sectional area 35 Sqmm 3.5 core including necessary connection and providing cable lugs as required all as specified. Make :- FINOLEX/ KEI/ POLYCAB/HAVELLS |
| 130 | M&L XLPE insulated, armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross- sectional area 25 sq. mm, 3.5 Core on walls, surfaces, cable ducts etc complete.Make :RR Kable / Polycab / Finolex / Havells |
| 131 | Supply & Fix in repair fully automatic star delta starter suitable for 25 HP, 440 volt, 3 Ph Elect Motor with Single Phase Protection feature conforming to IS -13947 after taking down old unserviceable one anf fixed to the same location by making electrical connection properly complete all as specified and as directed. Cat No: SS91855 of Make-L&T or equivalent to C & S / Schneider / CROMPTON |
| 132 | All as per item No 108 above but for eletrical motor 10 HP,Model MK1 FASD of L& T Make, CAT Pat: SS96254 or equivalent to C & S / Schneider / CROMPTON |
| 133 | S&F in repairs Direct on line (DOL) starter in sheet steel enclosure AC 3 phase 415 volt 50 Hz suitable for 5/7.5HPcomplete. |
| 134 | Cutting, clearing, and removing vegetation, bushes, creepers, or any type of growth from in, around, and over electric panels, feeder pillar boxes, busbar chambers, sumps, overhead tank staircases, and fencing to ensure unobstructed access for repair and maintenance works, including collection, removal from site, and disposal of all vegetation and debris to a location as directed at a distance not exceeding 250 metres, complete all as specified and directed by the Engineer-in-Charge. |
| 135 | M&L for comprehensive maintenance, servicing, and repair of the Automatic Water Supply System installed at ‘A’ Camp Pump House, Nausena Baugh, and Nofra Pump House under GE (NW) Mankhurd, including preventive and breakdown maintenance of all subsystems such as RTU-based control panels with all accessories, motorised valves, pressure switches, ultrasonic level transmitters, pressure transmitters, solenoid valves, GSM modem, transducers, CTs, MIMIC panel, personal computer, printer, UPS, and associated equipment. The scope shall include all labour, tools, plants, consumables, spare parts, testing, calibration, software updates, programming, and other ancillary works necessary to maintain the system in fully functional condition, complete all as specified and directed by the Engineer-in-Charge. |
| 136 | S & Fin repair LT 3 Phase Digital ammeter with built in selector switch and connecting including CT & necessary wiring if required complete all as specified. |
| 137 | S & F in repair Digiital 3 phase 440 Volts VAF PF (Voltage, Current, Frequency & Power Factor) meter with built in selector switch and connecting including CT & necessary wiring if required complete all as directed. |
| 138 | Supply and Fix in repairs Push buttons complete of colour red/ green with NO/NC elements, operating on 230 V, 50Hz, AC supply complete all as specified and directed. |
| 139 | Supply and Fix in repairs Selector Switch 3 Positionsuitable for LT panels, operating on 230 V, 50Hz, AC supply complete all as specified and directed. |
| 140 | S & F in repairs LED based complete(R Y B ) for mounting on LT panel, operating on 230 V, 50Hz, AC supply complete all as specified and directed. |
| 141 | M & L for rewiring of old burnt out copper wiring in LT Panels/LT Feeder, replacing of cable Glands, cable lugs, bus bar link, connectors, insulators, door hinges, panel door locks & scrapping of old paints & applying two coats of paint all as specified and directed. |
| 142 | Supply only of potable water from an approved and authorised water source, transported through water bowsers, and delivered to MES water supply installations at various locations under GE (NW) Mankhurd, complete all as specified and directed by the Engineer-in-Charge.Note:(a) The source of water supply shall be got approved prior to procurement of water. |
| 143 | Supply and fixing in replacement of Electronic Star-Delta Timer, microprocessor-based, adjustable time delay range suitable for star-to-delta changeover in motor starter panels, with LED indication for status, push-button for manual reset/test, DIN rail or panel mounting, operating voltage 230V AC, conforming to relevant IS/IEC standards, complete all as specified and directed by the Engineer-in-Charge. |
| 144 | Supply and fixing in replacement of Front Mounting Add-on Auxiliary Contact Block for use in motor control panels, compatible with standard contactor models such as L&T MNX series, Siemens 3TF series, Schneider LC1 series, or equivalent, suitable for direct front mounting on contactors/starters, snap-on/clip-on type, with 2NO+2NC (or as required) contact configuration, rated for 690V AC, designed for ease of wiring and reliable operation, conforming to relevant IS/IEC standards, complete all as specified and directed by the Engineer-in-Charge. |
| 145 | Comprehensive Repairs and maintenance of Fire alarm system installed at NAD Trombay, the system comprises of main Fire alaram Control Panelwith battery back up, Repeter panel , Motor operated Sirems, Manual call Points installed at various location complete. |
| 146 | Comprehensive Repairs and maintenance of Fire alarm system inslalled at 31 WEU Thane. The system comprises main Fire alaram Control Panel with battery back up, Manual Call Point (MCP), Electronic Hooter, Heat Cum Smoke Detector, Remote Response Indicators,installed at various locations complete, |
| 147 | Comprehensive Repairs and maintenance of Fire alarm system inslalled at Naval Station Thane. The system comprises main Fire laram Control Panel with battery back up, Manual Call Point (MCP) , Electronic Hooter, Heat/Smoke Detector, Remote Response Indicators,installed at various locations complete. |
| 148 | Comprehensive Repairs and maintenance of Fire alarm system inslalled at NCN Thane. The system comprises main Fire laram Control Panel with battery back up, Manual Call Point (MCP) , Electronic Hooter, Heat/Smoke Detector, Remote Response Indicators,installed at various locations complete. |
| 149 | Comprehensive Repairs and maintenance of Fire alarm system inslalled at TS Mahul. The system comprises main Fire laram Control Panel with battery back up, Manual Call Point (MCP) , Electronic Hooter, Heat/Smoke Detector, Remote Response Indicators,installed at various locations complete. |
| 150 | Comprehensive Repairs and maintenance of Fire alarm system inslalled at DSRV. The system comprises main Fire laram Control Panel with battery back up, Manual Call Point (MCP) , Electronic Hooter, Heat/Smoke Detector, Remote Response Indicators,installed at various locations complete. |
| 151 | Comprehensive Repairs and maintenance of Fire alarm system inslalled at T7 CMT Complex The system comprises main Fire laram Control Panel with battery back up, Manual Call Point (MCP) , Electronic Hooter, Heat/Smoke Detector, Remote Response Indicators,installed at various locations complete. |
| 152 | Comprehensive Repairs and maintenance of Fire alarm system inslalled at Single Officer accn, NOFRA. The system comprises main Fire laram Control Panel with battery back up, Manual Call Point (MCP) , Electronic Hooter, Heat/Smoke Detector, Remote Response Indicators,installed at various locations complete. |
| 153 | Comprehensive Repairs and maintenance of Fire alarm system inslalled at Relese Sailor Accn, Tanaji. The system comprises main Fire laram Control Panel with battery back up, Manual Call Point (MCP) , Electronic Hooter, Heat/Smoke Detector, Remote Response Indicators,installed at various locations complete. |
| 154 | Comprehensive Repairs and maintenance of Fire alarm system inslalled at NSD Sewri. The system comprises main Fire laram Control Panel with battery back up, Manual Call Point (MCP) , Electronic Hooter, Heat/Smoke Detector, Remote Response Indicators,installed at various locations complete. |
| 155 | Note for item ser No 145.00 to 154.00: a) The entire system shall be inspected and checked by the service engineer of the main manufacturer and recommend the replacement of spares and functional parts etc in proper inventory. The replaced parts shall be measured and paid for seperately as supply only under respective items of this schedule but fixing and testing etc is deemed to be included in the unit quoted rate against this item b) Checking of all internal & external wiring for open, Short, Damaged & loose Connections of all MCP, Main fire alaram panel, Repeater Panel, Siren motor, replacing of broken Break glass. Cleaning of Smoke detectors.c) Testing the fire alram system including checking of each MCP and maintining serviceablity records on monthly basis.d) All main fire control including battery, smoke detector, temperature heat detectors, connected control wiring etc shall be checked for normal functioning. |
| 156 | Supply & fixing in repairs flame proof manual call point (MCP) Housing with 24 Volt addressable MCP card and hammer, including making addition/alternation to existing suppors of MCP. Make - ANG FPA or , PCD Fire System, Safetech, Zicom, Apollo. |
| 157 | Supply & fixing in repairs Switch Mode Power supply operating at input volatage range 180 to 270 Volts and having maximum out put volatage of 28.5.Make - Proxymon/Omron |
| 158 | Supply & fixing in repairs maintenance free 12 Volts 15 AH battery suitable for fire alaram panel Make - Exide, Amron,Amco |
| 159 | Supply & fixing in repairs maintenance free 12 Volts 26 AH battery suitable for fire alaram panel Make - Exide, Amron,Amco |
| 160 | M & L for Removing of burnt electric motor1 HP to 3 HP, 440 Volts of fire alaram siren after dismantling of all electrical connections & transporting from site to workshop, rewinding of electric motor with super enameled copper wire after removing of old burnt coil, replacing of bearing, cleaning of slots properly, heating in heat chamber after varnishing and testing at site and including scrapping the old paint and applying one coat of red oxide primer and applying two coat of synethetic enamel paint. all as directed by Engineer-in-Charge. Note :- Cost of insulation paper, varnish and any nuts, bolts and lugs required for the job shall be deemed to be included in the quoted rate |
| 161 | Supply & fixing in repairs Detectors complying with and type certified to EN-45 type multisensor detector with heat and smoke combination photo electirc / optical with base with self built intelligence as per IS - 11360 complete. Make - Apollo/Zicom/Hochuki/Edward/PCD/Safetech, |
| 162 | Supply & fixing in repairs DOLstarter 3 Phase 440 volts suitable for2 HP fire alaram siren motor Make “Siemens / L&T /ABB ” as existing in panel board. |
| 163 | Supply & fixing in repairs response indicator complete with cable connection testing and commissioning all as specified and directed by Engr-in-Charge.Make - Apollo/Zicom/Hochuki/Edward/PCD/Safetech, |
| 164 | Supply & fixing in repairs Electronic hooter 24 Volt DC complete for fire alaram system complete with acessories all as directe by engineer-in charge Make - Safetech, Minimax, ECD, Apollo, Zicom/PCD |
| 165 | Supply & fixing in repairsconventional manual call point with pill box complete with hammer, chan and all fixtures Make - Safetech, Minimax, ECD, Apollo, Zicom/PCD |
| 166 | M&L for sand cushioning by spreading in trenches stone curshed sand by gently by punning down manually as in cable protection all as specified and as directed by EIC. |
| 167 | Supply and laying un-reinforced precast concrete cable cover class LV, type-I, flat size 250mm x 150mm x 40mm laid in trenches all as specified.. |
| 168 | Laying only un-reinforced precast concrete cable cover class LV, type-I, flat size 250mm x 150mm x 40mm laid in trenches all as specified.. |
| 169 | M & l for taking down of old sables & Supply & lay armoured XLPE Insulated 1.5Sqmm 4 core multi stranded copper conductor cable along the walls, in trenches ducts, ceiling / connection to control panel, manual call point complete with termination, testing and commissioning all as specified and directed by Engr-in-Charge. Make - Poly Cab/Havells/Plaza |
| 170 | M & l for taking down of old sables & Supply & lay armoured XLPE Insulated 1.5Sqmm 2 core multi stranded copper conductor cable along the walls, in trenches ducts, ceiling / connection to control panel, manual call point complete with termination, testing and commissioning all as specified and directed by Engr-in-Charge. Make - Poly Cab/Havells/Plaza |
| 171 | M&L for reinforced cement concretenominal mix M-20(using 20mm graded stone aggregate) for foundations, including rafts, footings, foundation beams, plinth beams, bases for column etc and mass concrete, complete all as specified and directed.(Note - Reinforcement and form work will be measured and paid separately). |
| 172 | M & L for TMT bars of Fe-500 D grade conforming to is:1786, 10 mm dia & over, including cutting to length, bent to shape equired, cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9 mm dia or securing with clips etc, complete all as specified and directed. |
| 173 | M & L for TMT bars of Fe-500 D grade conforming to IS: 1786, 8 mm dia bars as in binders, spacers, strippusincluding cutting to length, bent to shape required, cranking, bending spirallyfor hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9 mm dia or securing with clips etc, complete all as specified and directed. |
| 174 | M & L for use and waste of formwork to sides of concrete foundations, footings, bases of columns, raft and raft beams , side and soffits (if any) of foundation and plinth beams and similar work, vertical or to batter, for rough finished surfaces of concrete, complete all as specified and directed. |
| 175 | Dismantling of old UNSV/rusted steel tubular poles 9 mtr long necessary disconnecting cables/over head condcutor and removing unserviceable pole from site complete all as specified and directed. |
| 176 | Supply, Fixing and connection of hot dip galvanised octagonal poles of height 6 mtr with 130 mm bottom A/F & 70mm top A/F made up of 3mm thick HT sheet along with base plate of size 200 x 200 x 12mm thick including 4 nos of M20 x 600 long J type foundation bolts and 1 mtr long hot dip galvanised single arm standard bracket, including MCB of 6 Amps, with connector 4 way to be provided as termination point complete all as specified and directed. Make :- Bajaj |
| 177 | M&L for provn of Earthing complete with M.S. galvanized earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (earth pit not less than 2.25 M deep below normal GL) with top edge of the plate not less than 2.50 M below normal GL, connected to Galvanized earth strip 32x6mm upto 7.5 mtr with protection pipe by means of bolts, nuts, check nuts & washers of GI or steel incl excavation, PCC (1:3:6) type C-1 chamber with RCC cover (1:2:4) type B0, 40 mm thick reinforced with 6 mm dia bar, 3 Nos. both way, 40mm dia light grade GI protection pipe, funnel with wire mesh,watering pipe of size 20 mm dia med. grade, lugs, main Earthing lead upto 7.5 mtr incl. Charcoal dust, salt etc. all as shown in electrical plate No. 3 of SSR Pt-I 2009 specification. |
| 178 | Supply & fix in repair 3 core 1.5 Sqmm size multistranded FRLS copper conductor PVC unsheathed 650 / 1100 Volt cable for interconnection of cable looping box to Street Light Fitting all as Directed. |
| 179 | Supply, laying, connecting and testing XLPE insulated (Earthed) cable intrenches/or fixed on pole etc in screened PVC bedded galvanized steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor, 1100 Volt grade, cross sectional area 16 Sqmm, 4 Core Conforming to IS-7098 (Part-II)-1985 complete . |
| 180 | S & F in replacement of security light fitting/Building security lightLED type 60 watts, THD<10%, Efficacy 110 Lm/w with Pressure die cast aluminium housing with hight power LED as lighting source and lens embedded PC cover having TOP OPENING seerated driver compartment with IP 66 protection and impact resistance of IK07 with 10KV built-in surge protection device etc all as directed by Engineer in charge. Make:- BAJAJ/ PHILLIPS/ JAQUAR/ WIPRO. |
| 181 | Note : A SUM OF RS 73,692.00 TOWARDS SCHEDULE OF CREDIT SHALL BE DEDUCTED TO ARRIVE THE CONTRACT SUM |