| 1 | Supply, install, testing and commissioning ofhigh wall split type air conditioner unit indoor/outdoor complete with cordless remote control unit and within built air ioniser and plasma filter for better indoor quality and EER 3.2 of cap 2.0 TR5 star rating complete all as specified and directed. |
| 2 | Supply, install, testing and commissioning ofhigh wall split type air conditioner unit indoor/outdoor complete with cordless remote control unit and within built air ioniser and plasma filter for better indoor quality and EER 3.2 of cap 1.5 TR5 star rating complete all as specified and directed. |
| 3 | Supply, install, testing and commissioning of Water cooler fullystainlesssteel, electric drivensingle phase havingapprox storage andnominal cooling capacity of 80/40 Ltr 5 star rating complete all as specified and directed. |
| 4 | Supply, installation,commissioning of MetalTop Deep Freezer singlephase 240 volt, 50 Hz5 star ratingof 500 Ltr capacity complete all as specified and directed. |
| 5 | S & F voltage stabiliser for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170V to 250 V with output voltage stabilised at 230 V with accuracy of + 2.5% and of capacity 5.0 KVA complete all as specified and directed. |
| 6 | M & L for concealed sub main wiring complete with PVC insulated FRLSH cable of 2 run of single core 06 Sqmm 1100 volts grade with unseathead multistranded copper coductor (for phase and neutral)drawn through and including PVC med grade conduit with accessories and 1 run of 6 sqmm 1100 volts grade with unseathead multistranded FRLSH copper coductor (for earthing) complete all as specified and directed. Note :- (a) Two run of 6 Sqmm multistranded FRLSH copper conductor and one run of 6 Sqmmmultistranded FRLSH copper conductor and one run of 20 mm dia med grade PVC conduit shall be measured adn paid as one run length. Colour coding for wiring shall be followed as per direction of Engr-in-Charge. (b) The rate quoted by contractor shall be included for chess cutting of the existing wall/surface for concealed wiring and making good the disturbed surfaces to match with the existing wall/surfaces. |
| 7 | S & F of single pole and neutral enclosure with a two pin and earth plug socket complete with one single pole MCB of 20 Amp capacity complete all as specified and directed. |
| 8 | M&L forsub main wiring of two run with 4.0 Sqmm single core PVC insulated, FRLSflexible multi stranded copper conductor cable 1100 volts grade, drawn through and including PVC conduit and accessories of suitable size and fixed on concealed surface of wall/ceiling with cutting chases where required including one run of 4.0Sqmm single core PVC insulated, FRLS,flexible copper cable as earth continuity conductor in green color complete all as specified and directed. |
| 9 | Supply and install vertical pack type units indoor/outdoor complete with cordless remote control unit, twin rotary compressor, single phase units 220V - 240V, 50 Hz of capacity as shown capacity4.5 TR complete with cordless remote control unit andauto restart facility, 100 % copper and stabilizer free operation, includingexcess copper tubing if required beyond the length supplied with AC unit and PVC conduit of 15 mm dia not exceeding 2.5 mtr long for water drain and making good to disturbed surface with cement mortar ratio of 1:3 and testing complete all as specified and directed by Engineer-in-charge. Make : Voltas, Blue star, Hitachi, Daikin or equivalent as approved by GE. |
| 10 | S&F 4 way sheet metal enclosures for flush/surface mounting distribution board double door, 240 volts factory made and tested complete, suitable for mounting MCBs with 200 Amps rated bus bar, cable lugs complete all as specified and directed. |
| 11 | S&F miniature circuit breaker (MCB) of single poles and current carrying capacity 6 to 32 AMP 240V, 10 KA \"B\" curve, in theDB Complete with connection testing and commissioning complete all as specified and directed. |
| 12 | Supply and fixing 415V 10KA \"C\" curve miniature circuit breaker (MCB) ofrating TPN 40 to 100 AMP in the DB complete all as specified and directed. |
| 13 | All as per item No. 12 here in before but SPN 32 AMP |
| 14 | All as per item No. 10 here in before but 4 way 415 volts TPN DB |
| 15 | Supply and fixing XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured electric power cable (H/D) earthed cable aluminium conductor, 1100 volts grade with standed for 16 sq. mm, 4.0 core nominal cross section in service connections including taking down complete all as specified and directed |
| 16 | Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth, for foundation, / laying of pipe / cable etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in soft loose soil completeall as specified and directed. |
| 17 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm thick using excavated soil complete all as specified and directed. |
| 18 | Removing excavated soil to distance n.exc 50 m and depositing where directed at a level n.exc 1.5m above the starting point complete all as specified and directed. |
| 19 | Material and labour for boring of holes upto 50 mm dia under road, pavement, hard standing by trenchless technology using ultra sound techinque/ manually and necessary machine complete all as specified and as directed. |
| 20 | Supply and laying of DWC HDPE pipe of SN4 category conforming to IS 14930 part I and II including accessories like HDPE snap fit coupler with neaoprene \"O\" rong of size 38 mm inner dia complete all as specified and directed. |
| 21 | Supply, testing and commissioning of single Phase 230 volt, 950 RPM ,50 Hz, evaporator type water cooled Air Cooler, pre painted steel body, with honeycomb cooling pad, aluminum fan having capacity of and water tank capacity 70 Ltr, capcity of air flow shall be 6000 CMH and product dimension 1220 x 620x 670 mm, auto louver swing with required knob complete all as specified and directed by Engr- in-charge. |
| 22 | M&Lfor point wiring complete with 1.5 Sqmm single core PVC insulated and unsheathed multi stranded copper conductor cable 1100 volt grade, (FRLS) through and including 20X12 mm PVC casing-n- copping and its accessories, cadmium screws and including 1.5 Sqmm single core PVC insulated and unsheathed multi stranded copper conductor cable(FRLS) as earth continuity conductor and MS boxes made of 16 gauge MS sheet concealed type on walls cover 3mm thick for housing for One 5A socket/fan point controlled by one onway switch complete all as specified and directed. |
| 23 | S&FSwitch piano, single pole one way 5 Amps 240 volt capacity flush type complete all as specified and directed. |
| 24 | S& F ceiling rose, 5 Amps surface type 240 volts bakelite three terminal complete all as specified and directed. |
| 25 | Supply and fixing (BLDC) ceiling fans completeSupply and fixing ceiling fan completewith blades down rods ,with remote control unit with battery 02 Nos and accessories 230 Volt 1200 mm sweep min air delivery 240 cum/min with service value 6.00 BEE, Five star rated with brushless direct current motor complete all as specified and directed. |
| 26 | M & L for dismantling concrete pole/struts any size carefully to avoid any damage to nearby objects from area A & C and removing the old RCC poles outside MD land complete all as specified and directed by Engr In Charge. Note : Penality for Non removal of old poles @ 750/poles will be charged from contractor. |
| 27 | Supply and errecting steel tubular pole in replacement ofRCC poles with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9.0 metres long) duly painted internally complete and externally painted with two coat of aluminium paint, Incl writing of MES pole NO complete all as specified and directed.Note: Earth work /excavation / PCC shall be measured and paid separately. |
| 28 | S&F in replacement of mounting bracket single arm forming Cap type having an interior angle of 120 degree made out of GI pipe Med grade suitable dia for fixing to street light fittings on the poles not less than 1.5 meter long duly painted with aluminium paint two coats complete all as specified and directed. |
| 29 | S&F in replacement of mounting bracket double arm forming Cap type having an interior angle of 120 degree made out of GI pipe Med grade suitable dia for fixing to street light fittings on the poles not less than 1.5 meter long duly painted with aluminium paint two coats complete all as specified and directed. |
| 30 | S&F in replacement PVC wire 1.5 sqmm 3 Core PVC insulatedcable copper drawn through internally from looping box to street light fitting terminal incl all electrical connection complete all as specified and directed. |
| 31 | S&F in replacement of looping box (enclosures) of size 300 x 250 x 150 mm made of PVC comprising of 02 Nosbus bar 100 Amps rating fixed on porcelain insulators, earthing terminal and one MCB SP 6 Amp including MS bracket, nut an bolts complete all as specified and directed. |
| 32 | M & L PCC 1:3:6 type C2 using 40 mm graded stone aggregate in foundation of pole complete all as specified and directed. |
| 33 | M & L PCC 1:3:6 type C1 using 20 mm graded stone aggregate in coping of pole including necessary form work complete all as specified and directed. |
| 34 | S&F in replacement automatic Switch complete pole mounted enclosure consisting of MCBs, Power Contactor and SMC Enclosure conforming to IP 54 for encasing full 1- phase circuit board along with automatic Switch-01,Model No SWADEEP – 02EC 3kW1P or techno commercially equivalent as approved by GE (for 3-5kW load equally distributed over 1-phase) incl all electrical connection complete all as directed by Engr-in-charge. |
| 35 | M&L forearthing complete with galvanized steel earth plate electrode 600x600x6mm thick electrode, buried directly in ground (earth pit not less than 2.25m deep below ground level) with top edge of the plate not less than 1.5m below normal ground level, connected to 4 mm dia galvanized earth wire by means ofbolts, nuts, check-nuts and washers of galvanized iron or steel all as shown in electrical plate No 5 (duly protected with 15 mm dia light grade GI pipe upto 7.5m from the earth plate) and connected to GI steel earth plate including charcoal, dust, common salt, necessary excavation in soft/loose soil, returning, filling in and removal of surplus soil to a distance not exceeding 50 m from the starting point, watering pipe 20 mm bore GI tube of light grade treated with 1 No PGI funnel, pit of PCC 1:2:4 type B-1/ RCC1:2:4 type B-1, pit cover 75 mm thick reinforced with 6 mm dia bars @ 75 mm c/c both ways and with MS handle 12 mm diaconnected to earth test point including testing complete all as specified and directed. |
| 36 | Supply and fixing in replacement of 90 watt LED street light fitting230 V, AC outdoor type,CCT 5700K with high pressure die cast hosing,toughened glass and secondery lens optics with IP 66 ingress protectioneffiency 120 lm/watt complete all as specified and directed. |
| 37 | All as per item No 36 here in before but 70 watt capacity. |
| 38 | M & L for taking down ceiling fan any size/ sweepfrom different location in Air Force station dismantlingand removing fan rod to store and reassembling and refixing the fan at its original location after placing smart fan down rod & newfan clamp and rubber grommets, split pin, shackle, spindle, nut bolts, safety pin, hanger clamp complete all as specified and directed.Note- Old MS fan rod to be deposited to MES Store Yard |
| 39 | Supplying and fixing Smart fan down rod (anti sucide fan rod) 15\"\" to 18\" length incl all connection complete all as specified and directed. |
| 40 | Supplying and fixing Smart fan down rod (anti sucide fan rod) 30\" length incl all connection complete all as specified and directed. |
| 41 | S&F flexible cord of 230 volt grade, size 0.75 sqmm two core, multi stranded copper conductor complete all as specified and directed. |