| 1 | Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required. 100 mm dia |
| 2 | Supplying and laying of following sizeHDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.120 mm dia (OD-120 mm & ID-103 mm nominal) |
| 3 | Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3½ X 35 sq. mm |
| 4 | Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required 3½ X 70 sq. mm |
| 5 | Supplying and making end termination with brass compression gland and aluminum lugs for following size of PVC insulated and PVC sheathed / XLPE aluminum conductor cable of 1.1 kV grade as required. 4C X 35 sq. mm(28 mm) |
| 6 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 7 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. wire in 15 mm dia G.I. pipefrom earth electrode including connection with GI thimble excavation and re-filling as required. |
| 8 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 9 | Providing and laying following sizes Cross linked polyethylene and XLPE insulated PVC outer sheathed armoured cable with aluminum conductor suitable for rated voltage at 1100 volts grade inthe existing RCC/ HUME/ METAL/HDPE pipe and conforming to IS: 7098 Part-1 1988 with amendment number 1 and 2 and 3 Reaffirmed 2005 make Havells/Polycab/KEI/Finolex/RR cables!4C X 35 sq. mm |
| 10 | Providing and laying following sizes Cross linked polyethylene and XLPE insulated PVC outer sheathed armoured cable with aluminum conductor suitable for rated voltage at 1100 volts grade inthe existing RCC/ HUME/ METAL/HDPE pipe and conforming to IS: 7098 Part-1 1988 with amendment number 1 and 2 and 3 Reaffirmed 2005 make Havells/Polycab/KEI/Finolex/RR cables!3.5C X 70 sq. mm |
| 11 | Providing, installation, testing and commissioning of200 watt LED floodlight made up of pressure die cast aluminum housing with toughened glass and high power LEDs and secondary lenses with IP66 protection. System efficacy ≥ 110/125LPW 10KV SPD included.Driver for operation in 140 to 270volt AC, 3000k with suitable beam angle, with suitable driver. with suitable clamp nut and boltsin existinghigh mastbreaket also connection with 1.5 sq mm 3 core copper round cable loop box to light etc as required. Make Havells/Philips/Crompton Cat No-LFLN-200-CDL/60-HPM |
| 12 | Supplying and fixing of 63 4P415 Volt 16 KA MCCB, Thermal Release Range (A) 50-60, Breaking Capacity Icu at 415V AC 50Hz. (kA) 30,with speader terminals and enclosure fixingin the existing pole suitable size nut bolt clamps including connection testing ets. as required. Make L &T/ ABB/Simence/Schneider L&T Cat No. CM97933OOH2 |
| 13 | Supplying and fixing 16 A rating, 415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of four poles in the existing panel nut bolt din rail, complete with connections, testing and commissioning etc. as required. Make L &T/ ABB/Simence/Schneider |
| 14 | Replacement of following defective electric items and control wiring, power wiring ofexisting High mast light control panel again connection with power wiring 6 Sq mm FRLS single core Copper conductor and control wiring 1.5 Sq mm FRLS single core Copper conductor, proper numbering of ferrule shuold be maintained complete with connections, testing and commissioning etc. as required, i) 01 No- Multifunction timer with digital display 20-240V AC/DC 15 functions make ABB/L&T/Schneider/ Simence Cat No. 7PV0723-1AV20, ii) 01 No- Power Contractor Rated current 45A3pole 415V AC 50 Hz, contractor coil 230 V AC Auxiliary contacts 2 NO + 2 NC makeABB/L&T/Schneider/ Simence Cat No. 3TF4602-0A, iii) 02 Nos - Power Contractor Rated current 12A3pole 415V AC 50 Hz, contractor coil 230 V AC Auxiliary contacts 2 NO + 2 NC makeABB/L&T/Schneider/ Simence Cat No. 3TF3101-0A, iv) 01 No- 40 A rating, 415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of four poles Make L &T/ ABB/Simence/Schneider |
| 15 | Providing and fixingof Industrial plug and socket 5(3P+N+E) poles IP 67 protection 415 Voltcurrent rating 32 Amp complete with connections, testing and commissioning etc. as required. Make L &T/ ABB/Simence/Schneider |
| 16 | Providing, Laying and connection 5 core 4.00 sq.mm PVC insulated and PVC Round Sheathed, Multicore Annealed Bare Copper Conductor (flexible) industrial cable for Voltage Grade 1100 Volt, Conforming to IS 694 : 2010. Cable should be run inside the 20-meter-high mast from the top CG box to the cable traillng pully to the bottom loop box, connection testing, etc. as required. make Havells/Polycab/KEI/RR cables |
| 17 | Supplying and Fixing of Weather proof junction box Minimum size 350 x 250 x 138 including 01 incomming and 08 outgoing hole with suitable gland, 32 Amp 16-20 pole connector made of Cast Aluminium shall be provided on the Carriage Assembly as required, from which the inter-connections to the designed number of the flood light luminaries and associated control gears fixed on the carriage shall be made. |
| 18 | Repairing and servicing of High Mast 1.5 HP motor, DDMFO Type Winch gear box allied equipments |
| 19 | Dismantling ofexisting Power & Control wiring in high mast pole and panel for normal operation of high mast |