| 1 | M&L for repair/rectification of unserviceable security lights, street lights, flood lights or any kind of lights located any where in OP, RP, NP, Dilbagh, Offr Area, tech area and OBD area upto 20 metre height, complete all as specified and directed.Note: (i) The work is to be carried out upto 20 metre height by crane/Trolly mounted ladder, therefore the crane (including operator & fuel)must be capable of reaching required height as directed by Engr-in-charge including deployment of minimum one Elect and minimum one helper to carryout repair/ rectification of all kinds of lights. However Manpower shall be increased as per requirement of work and rates shall deemed to be included in quoted rates for electrician,helper, crane or any other accessories required for ensuring serviceability of lights.(ii)Minor repairs of lights like taping /proper insulation of connection, rejointing of broken wire, making good of connection or any other minor repair required to make the lights serviceable will be deemed to be included in quoted rates.(iii) Lights if any are non-functional at site to be deposited back to MES & new lights or repaired lights will be installed at site. New lights will be measured and paid under relevant item of schedule/BOQ as \"Supply only\".(iv)The unserviciable lights shall be deposited to MES store yard and repaired by the contractor at MES store yard, relevant spare parts such as surge protector, electronic driver, thimbles required for repair will be measure and paid under relevant itemsas \"supply only\". (v) Contractor shall deploy a supervisor to collect the complaints/list of unserviceable lights at 9:00 hrs at the office of Engr-in-Charge on all working days and enter the same in a register with time & date of receipt of complaints/list of unserviceable lights and deposit the concerned JE E/M at 1700 hrs on same day with time & date ofrectification of lights in all working days |
| 2 | (vi) In case of non rectification and replacement of defective lights within 72 hours of receipts of compliants, the contractor will be penalized @ Rs 500.00 per day for each light. (vii) The manpower employed by the contractor will also be liable for cleaning the area of any vegitation around every street light pole for a radius upto 1 meter (including removal of creepers from the pole) without any extra cost to Govt. (viii) The contractor shall provide insurance of all the workers before engaging them on work and same shall be submitted to Engr-in-Charge.(ix) . The quoted rates are deemed to be included for the above all provisions and nothing extra shall be admissible on this account.(x)Defects caused due to faulty cable shall be paid seperately under relevant items of this Sch \"A\"/BOQ. |
| 3 | Suply only surge protector, 10 KV, rated frequncy of existing make 48 HZ - 62 HZ, 230 V suitable for 72W LED street light fittings of existing make, complete all as specified and directed.Note :- Refixing and testing shall be carried out against item No 01 here-in-before. |
| 4 | Suply only electronic constant current LED contol driver for LED bulbs, 240V, 50HZ, PF not less than 0.95, suitable for 72 /120 Watt LED street light fitting of existing make complete all as specified and directed.Note :- Refixing and testing shall be carried out against item No 01 here-in-before. |
| 5 | Supply, installation, commissioning and testing in repairs Rectangular SMC Junction boxes of size 250 x 200 x 105 mm, IP 65, (Weather Proof , Shock proof and rust proof) with 4 Nos Aluminium busbar and 1 Nos MCB SP of 20 Amp, 230 volt with side hinged door. The junction box shall have an option for cable entry at the bottom/sides of box for Cable Size upto 35 Sq mm including all fitting such as MS clamp, Nut, Bolt, Washer etc. arrangement to pole mounting required at site, complete all as specified and directed. |
| 6 | S&F in repairs Bracket made out of 40 mm dia galvanized steel tubing medium grade 1.5 m long including bending if required, 02 nos clamps made out of MS flat iron 40X6mm of suitable size fixed with bolts, nuts and washer including drilling holes and grouting with the same for fixing bolts, complete all as specified and directed. Note :- Cost of nuts and bolts shall deemed to included in quoted rates. |
| 7 | Demolition of cement concrete of any description and in any position not otherwise specially provided for, complete all as directed and directed. |
| 8 | M&L for Plain cement concrete (1:2:4) type B-1 using 20mm graded crushed stone aggregate as in coping of pole, concrete base work, protection of cable etc, complete all as specified and directed. |
| 9 | M&L for Plain cement concrete 1:3:6 type C-2 using 40mm graded crushed stone aggregate as in foundation of pole, concrete base etc,complete all as specified and directed. |
| 10 | M&L in repairs twin core10 Sqmm size cable, flat or circular, 1100V grade heavy duty cable, PVC insulated aluminium conductor,PVC sheathed, complete all as specified and directed |
| 11 | M&L in repairEarthing with galvanised steel earth plate electrode of size 60cmX60cmX6cm thick buried directly in ground (earth pit not less than 2.25m deep below the ground level) with top edge of the plate not less than 1.5m bellow normal ground level, connected to the galvanised earth lead by means of bolts, nuts and washers of galvanised iron or steel using GI or steel wire 4 mm diaas earthing lead as shown in electrical plate No 3 of SSR Part-I connected to earthing test point all as specified or indicated including testing on complete including necessary excavation and earth work in soft/loose soil, returning filling, disposal of surplus soil, earth pit in PCC 1:2:4 type B-1 using 20mm grade stone aggregate pit , funnel, 20mm dia GI medium grade watering pipe , 15mm dia GI light grade earth lead protection pipe and pre-cast earth pit cover made of RCC (1:1.5:3) type A1 duly reinforced with 8mm dia TMT bar @ 150 c/c both ways, one lifting handle made of 10mm dia TMT bar embedded in cover slab and cover, wire, copper lugs etc mesh charcoal and common salt inalternate layer of 15cm thick, complete all as specified and as directed. |
| 12 | Taking up/down worn out/damaged/unserviceable PVC insulated underground cable armoured, heavy duty with aluminium conductors of any size, 1100V grade from trench/duct/pole/wall/pipes/rooftops etc, complete all as specified and directed. Note:- Excavation and earth work shall be measured and paid separetely. |
| 13 | M&L for LT UG cable XLPE insulated, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor laid in trenches/on poles/walls/in ducts/passing through pipes etc including jointing materials such as cable glands, lugs etc of size 35 sqmm 3.5 core, complete all as specified and directed. Note :- (i)Factory test of the cable shall be carried out in presence of the rep of accepting officer as detailed by Accepting Officer and contractor is required to submit purchase vouchers, e-way bill and test certificates while claiming payment of LT cables. The contractor will arrange the testing at factory premises and cost of the same is deemed to be included in the rates quoted. |
| 14 | All as per Sl item No 12 above but 25 Sqmm 3.5 core. |
| 15 | Excavation in trenches in soft or loose soil, not exceeding 1.5 metre deep and not exceeding 1.5 metre wide and getting out, complete all as specified and directed.Notes :Payment for excavation shall be made for one time in case the new cable laid in the same trenches. |
| 16 | Returning, filling in trenches including spreading, leveling, watering and well ramming in layers not exceeding 25 cm thick in soft / loose soil, complete all as specified and as directed. |
| 17 | Removing surplus excavated soil to a distance not exceeding 50and depositing where directed at a level not exceeding 1.5 m above the starting point, complete all as specified and as directed. |
| 18 | M&L for brick protection with sub class \"B\" bricks (old size) laid dry, flat in trenches over cable with longest dimension perpendicular to the axis of the cable including taking out old bricks, complete all as specified and directed specified . |
| 19 | M&L for sand cushioning in trenchesand well ramming in layers 8cm below and 15 cm above the cable with fine dry sand for cable protection, complete all as specified and directed.Note : Punned thickness 18 cm shall be measured for payment purpose. |
| 20 | M&L in repairs 40mm bore dia GI tubing light grade as in cable protection pipe including all fittings, complete all as specifiedand directed. |
| 21 | M&L for boring under road/path/hard standing to pass the HT / LT UG cables upto 80mm dia pipe with the own arrangement of T&P, complete all as specified and directed. |
| 22 | M&L for cleaning, scrapping , preparingthe old painted steel surface of any descriptionand applying one coat of aluminium paint to poles upto 11 metre height and accessories/fittings what ever fixed on pole and writing pole Nos with white paint on black back ground,complete all as specified and directed. |
| 23 | M&L for cleaning, scrapping, preparing of the old painted steel surface of any descriptionand applying two coats of synthetic enamel paint over one coat of red oxide primer to HT/ LT panel, complete all as specified and directed. |
| 24 | Supply only LED type security/Street Light fitting 72 watt with LED lamps, pressure die cast housing with toughned glass cover,suitable gasket and IP 65 protection including all other standard accessories as per manufactures instruction and including fixed on poles/walls with clamps, nuts, bolts & washers including connecting to fitting, complete all as specified and directed. Note :- Refixing and testing shall be carried out against item No 01. |
| 25 | Supply onlyLED floodLight fitting 120 watt , pressure die cast housing with toughned glass cover,suitable gasket and IP 65 protection including all other standard accessories as per manufactures instruction and including fixed on Hanger/Blast pen with clamps,nuts,bolts & washers including connecting to fitting,complete all as specified and directed.Note :- Refixing and testing shall be carried out against item No 01. |
| 26 | Supply only Aluminium Thimbles of sizes 6 sqmmto 35 Sqmm conductor, complete all as specified and directed. |
| 27 | Supply and fixing in repairs steel tubular swaged poles completed with cast iron base plate, find taper plug, bolts and nuts and screws all as specified type 410-SP-55, 11 mtrs long complete including painting with two coats of alluminium paint over a coat of red oxide primer and making of 5 strips of 30cm width in black and white colour of alternate strip and writing pole number etc with synthetic enamel paint, complete all as specified and directed. |
| 28 | Supply only LED aviation light fittings 5 Watt with glass cover, suitable gasket and IP 55 protection including all other standard accessories as per manufactures instruction and including fixed on top of tall structures of tower and building including MAP towers, High raise buildings, High mast etc clamps, nuts, bolts & washers including connecting to fitting, complete all as specified and directed. Note :- Refixing and testing shall be carried out against item No 01. |
| 29 | Dismantling / Taking down unserviceable Flood light fittings fitted on High mast pole any type any make at various locationsat AF Stn Halwara. Opening / taking out unserviceable spare parts such as LED driver and LED surge protector etc.Complete servicing of High mast with oiling and greaseing of SWR and chain pully and all other moving parts /assembly. Checking serviceability of motor fitted inside High mast, SWR, 3 phase supply to the motor and light fittings on High mast pole from the nearest LT panel / Timer panel, if found unserviceable, repair / replacement of the same will also be deemed to be included in quoated rates.All spare parts like LED light fittings, SWR, rewinding of motor, LED driver, LED surge protector, LT cable, pully and grease will be measured and paid under relevant items as \"Supply only\" complete all as specified and directed.Note : 1.The cost of spares shall be paid as \"supply only\".Winding of motor shall be measured and paid seperately under respective items of BOQ/Schedule. 2.Cost of flexible wire of size 23/.0076 for connceting the light to conductor and PVC tape to taping the joint properly shall deemed to be included in the quoted rate. 3.Vehicle mounted Hydraulic type ladders / Cranes shall be used and will be provided by contractor for dismantling / refixing of light fittings on pole and cost for the same is deemed to be included in quoted rates. |
| 30 | Taking out of burnt winding from the unserviceable motor fixing inside of high mast of any capacity, cleaning all the limbs and rewinding with supper enamelled copper wire of same weight, gauge etc of motor winding with suitable gauge by calculating number of turns as per voltage of alternator, varnishing and drying by vaccum impregnating, replacing insulating material, nuts, bolt etc including testing as per latest IS / BS specification to make it functional,compete all as specified and as directed. |
| 31 | Supply only Grease for High Mast light as per sample provided by OEM /original manfacturers instruction, complete all as specified and directed. |
| 32 | Supply only PVC sheathed copper LT cable unarmoured 16 Sqmm 4 core suitable for High mast from LT panel to top roof of light fittings, complete all as specified and directed.Note :- Refixing and testing shall be carried out against item No 28 here-in-before. |
| 33 | Supply only LED type Flood Light fitting 200 watt with LED lamps, pressure die cast housing with toughned glass cover, suitable gasket and IP 66 protection including all other standard accessories as per manufactures instruction and including fixed on poles/walls with clamps, nuts, bolts & washers including connecting to fitting, complete all as specified and directed. Note :- Refixing and testing shall be carried out against item No 28 here-in-before. |
| 34 | Supply only SWR wire rope 8mm dia for High mast light fitting as per sample provided by OEM / original manfacturers instruction, complete all as specfied and directed.Note :- Refixing and testing shall be carried out against item No 28 here-in-before. |
| 35 | Supply only chain pully suitable for High mast light fitting as per sample provided by OEM / original manfacturers instruction, complete all as specified and directed.Note :- Refixing and testing shall be carried out against item No 28 here-in-before. |
| 36 | Repair of street lights by carryout repair of LT cable of Perimeter Security lights, under or above ground, jointing of cable, rectifying fault/replacing wires of junction box etccomplete all as specified and directed.Note : Cable of any size upto a length of 3 RM is deemed to be included in the rates quoted by the contractor. (ii)Irrespective of the number of lights get rectified after resolving of one cable issue between five poles, the same will be considered as \"One Job\". (iii)Minor repairs is included/taping/proper insulation of connection, rejointing of broken wire, making good of connection or any other minor repair required to make the lights serviceable will be deemed to be included in quoted rates. |