| 1 | Design, Fabrication, and Erection of High mast poles with RCC Foundation and other allied works for football ground: |
| 2 | Design, fabrication & SITC of 20 Mtrs, High Mast, 20 sided Polygon, Hot Dip Galvanized Iron, Heavy duty material pole, with one coat of zinc chromate primer and 2 coats of Aluminium/ epoxy painting as per the direction of Engineer-In-Charge and shall with stand wind speed of 180 Km/Hr and shall be as per IS 875 along with a suitable mounting arrangement to accommodate minimum \"20\" Numbers of fittings of 1000 Watts, and suitable beam angle for each fitting shall be planned as per the place designated for it, luminaries in Asymmetrical orientation. The mast has minimum 2 galvanized segments having suitable Dia and thickness for bottom and top portion of each segment and shall have sufficient dimensioned base plate. Support steel angles to hold the frame welded on to the mast. The lighting and fixture arrangement should be user friendly with motorized and manual up & down arrangement consisting of: |
| 3 | i. Head Frameii. Movable Lantern carriageiii. Double drum winch with suitable motor, safety and breaking arrangementiv. Minimum 6 mm 316 mm grade S.S Hoisting Ropes Of 7/19 construction.v. Lighting finial vi. Foundation Bolts & Nutsvii. Anchor plate & Template, Twin Dome Aviation Light (LED Type).Along with other necessary items to complete the job as required as per the directions of the Engineer - In - Charge. |
| 4 | Design and Drawings:1. The Concept plan, Elevation and 3D models must be approved by the Engineer in charge before the structural drawings are finalized. 2. Drawings for both the RCC foundation and detailing of the pole and other components must undergo structural proof-checking from reputable central institutions such as IITs or NITs or SERC. as per the direction of the Engineer-in-charge.RCC Foundation: The entire process, including preparation of drawings for the foundation as per IS 456, Surface dressing, Earthwork, PCC, Reinforcement (Brand: TATA/JSW/SAIL), Shuttering and centering, RCC (minimum M20 grade), Filling and required MS plate with bolt and nut (SAIL/TATA/JINDAL), Plastering and painting, etc., all as per mentioned in the foundation drawings.Note: Note: The rate inclusive of the preparation of drawings. 3D modelling, structural designing, and proof checking, this includes the preparation and detailing of drawings, vetting by central institutions (IIT/NIT/SERC) of structural drawings, execution of work with standard safety norms, and provision of men, materials, machinery & transportation etc., complete all as per the direction of the Engineer in Charge.Pole manufacturer: Crompton/ Bajaj/ Havells/ Philips/ Chennai polesMaterial make: SAIL/ TATA/ Jindal/ JSWMotor make: Kirloskar/ ABB/ Crompton/ L&T/ Siemens |
| 5 | Design, construction of complete foundation with minimum M20 grade RCC & erection of the high mast poles considering safe soil bearing capacity (SBC) at site as 10T/sqm at 2.3 Mtrs depth with all material and labour and as per soil investigation report test and furnishing shop drawing for approval by the Engineer-In-Charge before execution of work. Such details shall be as per CPWD specifications, Indian Standards, local bylaws etc., and including required accessories, fixtures, connections, crane / lifting machinery or equipment charges etc., to complete the job |
| 6 | Design, Supply, Installation, Testing & Commissioning of required weather proof thermoplastic circuit breaker box of minimum IP65 rated protection with suitable rating Male & Female Plug and Sockets, MCB, din rail, connectors, glands, knockouts as applicable including supply and termination of minimum 3 Core * 4 Sq. mm (1-Ph, N & E) flexible copper cable between JB & Fixtures (Number of runs shall be designed based on requirement) on Lantern Carriage and minimum 3.5 Core * 16 Sq. mm (3Ph, N & E) movable trailing copper cables from Feeder Pillar to High Mast JB (Number of runs shall be designed based on requirement) and mounting accessories etc., as required to complete the job as per the directions of Engineer-In-Charge.JB Make: Hensel/ Legrand/ L&K/ ABB/ SchneiderCable Make: Polycab/ Finolex/ Havells/ RR Kable |
| 7 | Design, Supply, Installation, Testing & Commissioning of 415V, 3-Phase, 50 Hz, totally enclosed, outdoor suitable, stand mounted, powder coated, dust, damp, vermin proof, hinged, lockable, minimum IP65 protected, feeder pillar box made out of 2 mm thick MS sheet as required, comprising of 4 Pole, 63 A MCCB incomer, 24 Hrs digital timer, suitable 4 pole power contactors, relays, auxiliary, NO, NC blocks, din rail, MCB\"s, fuse links, neutral links, RYB LED Indication lamps, selector switches, terminal blocks, connectors, lugs and internal wiring etc., for the lighting control and suitable rating power contactors, MCB\"s, pendent push buttons with cable for raising and lowering lantern carriage bracket along with civil cement concrete works as required etc., to complete the job as per the directions of Engineer-In-Charge.MCCB, Contactor, MCB & Timer Make: Legrand/ Schneider/ Siemens/ L&K/ ABB |
| 8 | Design, Supply, Installation, Testing & Commissioning of minimum 1000 watt, >/=120 Lumens/ watt, High mast LED high power flood light, minimum 4000K, cool day LED Flood Light Fixtures of minimum \"10\" LED fittings per pole (Total \"6\" poles) having required beam angle for each fitting and shall be fixed in such a way that it should distribute an average of 200 Lux at the entire playground area (As per SAI standard) with uniform distribution factor of not less than 0.6. The lux level shall be measured, recorded throughout the ground and adjustment of fittings shall be carried out to maintain uniform illumination as required. The LED fixtures shall have a warranty period of 5 years. Make: Havells/ Philips/ Bajaj/ Crompton/ Neri |
| 9 | Supplying of following size one number XLPE insulated and PVC Sheathed armoured aluminium conductor power cable of 1.1 KV grade conforming to IS:7098 (part 1) 1988 as required.Make: Havells/ Polycab/ Finolex |
| 10 | a) 3.5 Core * 70 sq. mm |
| 11 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc, conforming to IS 16205 Part II (Update) complete with fitting and cutting, jointing etc. direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.Make: ISI Marked |
| 12 | 90 mm dia (OD - 90 mm & ID - 76 mm nominal) |
| 13 | Laying and fixing of one number PVC insulated and PVC sheathed/ XLPE power cable of 1.1 kV grade of following size in the existing RCC/ HUME/ METAL/ DWC pipe as required. |
| 14 | Above 35 Sq.mm and up to 95 sq. mm |
| 15 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed/ XLPE aluminium conductor cable of 1.1 kv grade as required.Make: ISI Marked |
| 16 | 3.5 Core * 70 Sq.mm (38 mm) |
| 17 | Earthing with G.I. earth pipe 4.5 Mtrs long, 40 mm Dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc., with Charcoal/ coke and salt as required confirming IS 3043 & it\"s latest amendments.Make: ISI Marked |
| 18 | Providing and fixing 25 mm * 5 mm G.I. strip in 40 mm Dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.Make: ISI Marked |
| 19 | Providing and fixing of 6 SWG Dia GI wire on surface or in recess for loop earthing as required from earth pit to all poles. Make: ISI Marked |
| 20 | Design, Fabrication, supply, installation, testing & commissioning of outdoor suitable, cubical type, totally enclosed, free standing, dust, damp, vermin proof, hinged, with compartment and over all panel door, lockable, IP65 protected, LT panel suitable for 415V, 3 phase, 4 Wire, 50 Hz, AC supply system of suitable size fabricated in compartmentalized design from CRCA sheet steel of 2 mm thick for frame work and covers, 3mm thick for gland plates with stiffeners where ever required and MS angle iron with canopy on top, duly powder coated as per the approved shade, having suitable capacity extensible type TPN aluminium bus bars minimum of 40mm x 5mm, bottom base channel of MS section not less than 50 mm x 50 mm x 6 mm thick, including PCC foundation in apar with existing MV panel, plastering, complete etc., as required as per the directions of Engineer-In-Charge .TPN MCCB, MCB, Contactor, CT coils, Timer & MFM Digital metersMake: Legrand/ L&T/ Siemens/ Schneider/ ABB |
| 21 | Incoming: |
| 22 | (i) 200 Amps, 4 pole, MCCB, 36 KA breaking capacity with Microprocessor release (O/C, S/C, E/F), along with spreader links, rotary handle, etc. - 1 Set (The microprocessor based MCCB shall have inbuilt ground fault protection and adjustable neutral overload protection) |
| 23 | (ii) Multifunction Meter, 200/5 Amps CT coils - 3 No\"s, Internal wiring, Fuse links, MCB\"s, terminal blocks, Din rail, Lugs, Connectors etc., to complete |
| 24 | Outgoing: |
| 25 | (iii) Outgoing feeders of following ratings MCCB with rotary handle, spreader terminal with thermal magnetic release. |
| 26 | (iv) 63A, 25 KA, FP MCCB - 3 Nos |
| 27 | (v) 32A, 25 KA, FP MCCB - 1 Nos |
| 28 | Total |