Tender For Repair/Maintenance Of Internal Wiring, Submain And Fan At Sector ‘A’ & ‘B’ Under Ge (A) Baroda.; 1 Taking down carefully copper/aluminum pt wiring (light fan, socket or power) complete including fittings such as switches, sockets, c/roses, lamp holders, tube light fittings, sketch fittings, wooden boards, bell push, call bell, MCBs, & regulators etc & making good to disturbed surfaces & matching with the existing colour of wall/floor etc. 2 M&L for surfaces point wiring with 1.5 Sqmm PVC insulated FRLS, unsheathed, copper conductor stranded 1100 volt grade cable in & incl PVC Casing -n-caping /conduit of size not less than 20mm ISI marked ivory white with all accessories such as tee, bend, joint cover including anodized MS sunken boxes made out of MS sheet of thickness not less than 1.6 mm with earth dolly and PVC laminated hylem/Anchor ISI marked top cover 3.0 mm thick for mounting of switches/sockets/ regulator etc and PVC insulated & unsheathed 1100 volt grade copper conductor, stranded 1.5 sqmm. cable as continuous earth lead complete all as specified and colour coding of cables such as Phase -Red, Neutral – Black, and Earth – Green. 3 For one light point or fan point controlled by one switch all as directed by Engr-in-charge 4 For one Call Bell point controlled by one push button switch all as directed by Engr-in-charge 5 For5Amp independent socket point controlled by one switch all as directed by Engr-in-charge 6 For one 3 pin ,5 Amp socket point with other switch on the same board all as directed by Engr-in-charge 7 All as per item No 2 here in before but for power point wiring usingwith 2.5 sqmm PVC FRLS insulated ,unsheathed, copper conductor stranded 1100 volt grade cable and 2.5 sqmm PVC insulated ,unsheathed, copper conductor stranded 1100 volt grade copper conductor, stranded 2.5 sqmm. cable as continuous earth lead complete all as specified and colour coding of cables such as Phase -Red, Neutral – Black, and Earth – Green. 8 M&L for concealed point wiring with 1.5 Sqmm PVC-FRLS insulated, unsheathed, copper conductor, stranded 1100 volt grade cable in & incl PVC conduit,, including of junction and terminal boxes,all fittings such as tees, bends, elbows,etc. of External diameter 20mmall as per site requirements including anodized MS sunken boxes made out of MS sheet of thickness not less than 1.6 mm with earth dolly and PVC laminated hylem/Anchor ISI marked top cover 3.0 mm thick for mounting of switches/sockets/ regulator etc and PVC insulated & unsheathed 1100 volt grade copper conductor, stranded 1.5 sqmm. cable as continuous earth lead complete all as specified and colour coding of cables such as Phase -Red, Neutral – Black, and Earth – Green . 9 For one light point or fan point controlled by one switch all as directed by Engr-in-charge 10 For one Call Bell point controlled by one push button switch all as directed by Engr-in-charge 11 For5Amp independent socket point controlled by one switch all as directed by Engr-in-charge 12 For one 3 pin ,5 Amp socket point with other switch on the same board all as directed by Engr-in-charge 13 All as per item No 4 here in before but for power point wiring usingwith 2.5 sqmm PVC FRLS insulated ,unsheathed, copper conductor stranded 1100 volt grade copper conductor, stranded 2.5 sqmm. cable as continuous earth lead complete all as specified and colour coding of cables such as Phase -Red, Neutral – Black, and Earth – Green. 14 M&L for concealed point wiring with 1.5 Sqmm PVC-FRLS insulated, unsheathed, copper conductor, stranded 1100 volt grade cable in & incl PVC conduit of size not less than 20mm ISI marked ivory white With all accessories,includingmodular metal flush boxes & modular white cover plate of suitable module with frame as per site requirement all fittings such as tees, bends, elbows,etc. all as per site requirements PVC insulated & unsheathed 1100 volt grade copper conductor, stranded 1.5 sqmm. cable as continuous earth lead complete all as specified and colour coding of cables such as Phase -Red, Neutral – Black, and Earth – Green all as directed by Engr-in-charge . 15 For one light point or fan point controlled by one switch all as directed by Engr-in-charge 16 For one Call Bell point controlled by one push button switch all as directed by Engr-in-charge 17 For5Amp independent socket point controlled by one switch all as directed by Engr-in-charge 18 For one 3 pin ,5 Amp socket point with other switch on the same board all as directed by Engr-in-charge 19 For one light, point controlled by two wayswitch 20 All as per item No 6 here in before but for power point wiring usingwith 2.5 sqmm PVC FRLS insulated ,unsheathed, copper conductor stranded 1100 volt grade copper conductor, stranded 2.5 sqmm. cable as continuous earth lead complete all as specified and colour coding of cables such as Phase -Red, Neutral – Black, and Earth – Green. 21 S&F Modular switch, one way,6 Amp 230, 1 module . 22 S&F Modular switch, two way, 6 Amp 230, 1 module. 23 S&F modular socket 6 Amp-2/3 pin combined 2 module . 24 S&F Modular switch, one way,6 A/16 Amp 230, 1 module . 25 S&F modular socket 6 A/16-2/3 pin combined 2 module . 26 S&F Modular fan step regulator 120 Watt -2 module . 27 S&FModular bell push 6A one module . 28 S&F switch piano type flush, single pole, one way 5 A 230 V. 29 S&F socket outlet, 5 pin, 5 Amp, flush type, 230 V. 30 S&F switch piano type flush, single pole, one way 15 A 230 V . 31 S&Fsocket outlet2 in 1,6 pin, 5/15 A, flush piano type240 V. 32 S&F ceiling rose, surface backlite,three terminal. 33 S&F lamp holder insulated with back plate suitable for Angle/Batten fitting. 34 S & F in repair/replacement bell ding dong 230 V, single phase. 35 S&F bell push flush type one way 5Amp 240 Volt. 36 M&L concealed sub main wiring with two single core PVC FRLS insulated unsheathed stranded copper conductor cable FRLS, 02 runs of 01 Single core of size6 sqmm (for main current) drawn in & incl PVC conduit not less than 20mm dia ISI markedwith all accessories such as tee, bend, joint cover etc round / square blocks at junctions etc, all as per site requirements ISI marked with one run of01 Single core of size 6 Sqmm (As earth wire) PVC insulated unsheathed stranded copper conductor as a continuous earth wire complete all as specified incl. taking down old unserviceable sub main wiring and colour coding of cables such as Phase - Red, Neutral – Black, and Earth – Green complete all as directed by Engineer-in-Charge 37 M&L surface conduitsub main wiring with two single core PVC FRLSH insulated unsheathed stranded copper conductor cable FRLS, 02 runs of 01 Single core of size6 sqmm (for main current) drawn in & incl PVC casing -n-caping/pvc conduit of suitable size . ISI markedwith all accessories such as tee, bend, joint cover etc round / square blocks at junctions etc, all as per site requirements ISI marked with one run of01 Single core of size 6 Sqmm (As earth wire) PVC insulated unsheathed stranded copper conductor as a continuous earth wire complete all as specified incl. taking down old unserviceable sub main wiring and colour coding of cables such as Phase - Red, Neutral – Black, and Earth – Green complete all as directed by Engineer-in-Charge 38 M&L sub main wiring with two single core PVC FRLSH insulated unsheathed stranded copper conductor cable FRLS, 02 runs of 01 Single core of size10 sqmm (for main current and earth ) drawn in & inc PVC Casing-n-caping /pvc conduit of suitable size ISI markedwith all accessories such as tee, bend, joint cover etc round / square blocks at junctions etc, all as per site requirements ISI marked with one run of01 Single core of size 10 Sqmm (As earth wire) PVC insulated unsheathed stranded copper conductor as a continuous earth wire complete all as specified incl. taking down old unserviceable sub main wiring and colour coding of cables such as Phase - Red, Neutral – Black, and Earth – Green complete all as directed by Engineer-in-Charge 39 M&L sub main wiring with two single core PVC FRLS insulated unsheathed stranded copper conductor cable FRLS, 02 runs of01 Single core of size4 sqmm (for main current) drawn in & incl PVC Casing-n-caping of suitable size ISI markedwith all accessories such as tee, bend, joint cover etc round / square blocks at junctions etc, all as per site requirements ISI marked with one run of01 Single core of size 4 Sqmm (As earth wire) PVC insulated unsheathed stranded copper conductor as a continuous earth wire complete all as specified incl. taking down old unserviceable sub main wiring and colour coding of cables such as Phase - Red, Neutral – Black, and Earth – Green complete all as directed by Engineer-in-Charge. 40 M&L sub main wiring with two single core PVC FRLS insulated unsheathed stranded copper conductor cable FRLS, 02 runs of01 Single core of size2.5 sqmm (for main current) drawn in & incl PVC Casing-n-caping of suitable size ISI markedwith all accessories such as tee, bend, joint cover etc round / square blocks at junctions etc, all as per site requirements ISI marked with one run of01 Single core of size 2.5 Sqmm (As earth wire) PVC insulated unsheathed stranded copper conductor as a continuous earth wire complete all as specified incl. taking down old unserviceable sub main wiring and colour coding of cables such as Phase - Red, Neutral – Black, and Earth – Green complete all as directed by Engineer-in-Charge. 41 M&L sub main wiring with two single core PVC FRLS insulated unsheathed stranded copper conductor cable FRLS, 02 runs of01 Single core of size1.5 sqmm (for main current) drawn in & incl PVC Casing-n-caping of suitable size ISI markedwith all accessories such as tee, bend, joint cover etc round / square blocks at junctions etc, all as per site requirements ISI marked with one run of01 Single core of size 1.5 Sqmm (As earth wire) PVC insulated unsheathed stranded copper conductor as a continuous earth wire complete all as specified incl. taking down old unserviceable sub main wiring and colour coding of cables such as Phase - Red, Neutral – Black, and Earth – Green complete all as directed by Engineer-in-Charge 42 S&F testing and commissioning of MCB SP 240 volt 6 Amp to 40 Amp 10 KA capacity having C-curve characteristics connected with suitable lugs including taking down . 43 S&F testing and commissioning of MCB SPN 240 volt 16 Amp to 40 Amp 10 KA capacity having C-curve characteristics connected with suitable lugs including taking down. 44 S&F testing and commissioning of MCB SPN 240 volt 63 Amp10 KA capacity having C-curve characteristics connected with suitable lugs including taking down. 45 S&F testing and commissioning of MCB SP 240 volt63 Amp 10 KA capacity having C-curve characteristics connected with suitable lugs including taking down. 46 S&F double door metallic sheet metal enclosure for MCB DBdouble doorTPN 4 Way 415 Volts with 200 Amps rated bus bars including taking down.Note :- Cutting and chasing in stone masonary and making good to disturbed surfaces will be including in item rate . 47 S&F in replacement of TPN 63 Amps415 Vincluding making electrical coming/outgoing connections with lugs/thimbles,including taking down.all as specified & directed. 48 S&F sheet metal enclosure for DB double door, IP-43 when MCBs to be used SPN, 12 way, 240 V with 200 Amps rated bus bar including taking down.Note :- Cutting and chasing in stone masonary and making good to disturbed surfaces will be including in item rate . 49 S&F sheet metal enclosure for DB double door, IP-43 when MCBs to be used SPN, 8 way, 240 V with 200 Amps rated bus bar including taking down.Note :- Cutting and chasing in stone masonary and making good to disturbed surfaces will be including in item rate . 50 S&F double door metallic sheet metal enclosure for DBdouble door(IP-42/43) When MCBs to be used SPN 4 ways, 240 V with 200Amps rated bus barincluding taking down.Note :- Cutting and chasing in stone masonary and making good to disturbed surfaces will be including in item rate . 51 S&F metallic sheet metal enclosure for DBSingle door(IP-42/43) When MCBs to be used SPN 2 ways, 240 V with 200Amps rated bus bar including taking down.Note :- Cutting and chasing in stone masonary and making good to disturbed surfaces will be including in item rate . 52 S&Fin replacement of 2 X 2 ultra slip recess mountedluminaire with high brightness 36 Watt LED packageand Unique pattern acrylic de-glaring diffuser sheet for glare-free uniform light distribution suitable forarmstrong/grid ceiling all as specified and directed byEngr -in -charge. 53 S&F LED Bulk head 13/10 watt designed for modern homes availave in PIR as well as non PIR sensor with premium quality diffuser for glarefree light and easy to install snapfit installer.All as specified and directed by Engr-in-Charge 54 Supply and Fix in repair TL fitting 20watt for surface and wall mounted LED batten with ultra slim polycarbonate LED lighting fixture with high lumen output environmental friendly energy efficient..all as specified and directed byEngr -in -charge. 55 Supply and Fix in repair TL fitting 10watt for surface and wall mounted LED batten with ultra slim polycarbonate LED lighting fixture with high lumen output environmental friendly energy efficient..all as specified and directed byEngr -in -charge. 56 S&F double door metallic sheet metal enclosure for DBdouble door(DPX-125 ) VTPN4 Way 415 Volts with 200 Amps rated bus bars IP 43- IK 09 including taking down.. Note :- Cutting and chasing in stone masonary and making good to disturbed surfaces will b including in item rate . 57 S&F MCCB 63 Amps 4 pole, 415 V 16 KA including taking down. 58 S&F MCCB 100 Amps 4 pole, 415 V 16 KA including taking down.. 59 M&L for provn of Earthing complete with galvanised steel earth plateelectrode, 600x600x6mm buried directly in ground (Earth pit not less than 2.25M deep below the GL) with top edge not less than 1.5 metres below ground level connected with galvanized earth lead wire 4 mm dia by means of bolts, nuts, check nuts & washers of GI or steelall as shown in electric plate no 3 connected to earthing test point all as specified or indicated including testing on completion.Note :- (i) The rate quoted shall also deemed to include the cost of GI wire and protection pipe upto 7.5 Mtr beyond the earth plates electrode and also the costof the Test point. (ii) Joining of GI earth wire with pipe of the test point shall be done by using suitable cable lugs. 60 S&F in replacement 1100 volts grade heavy duty flat cable PVC insulated stranded aluminium conductor10 sqmm 2 coreover all PVC sheathed in service connection suspended by insulating hangers .All as per specified and directed by engineer in charge. 61 S&F metal clad box enclosure with socket plug top and MCB SP 20 Amps flush mounting enclosure with 2 pin and earth plug socketincluding taking down. complete all as directed by Engineer-in-Charge . 62 S&F Modular AC box enclosure with socket plug top and MCB SP 25 Amps flush mounting enclosure .complete all as directed by Engineer-in-Charge . 63 Supply and Fix in repair PVC insulated and unsheathed single core multi stranded copper conductor 1.5 Sqmm (Nominal Area) drawn in existing conduit / batten / surface all as specified and directed. 64 All as per Item Ser No 50.00 above but size 2.5 Sqmm 65 Supply and fix in repairs PVC insulated and unsheathed single core multi stranded copper conductor 6 Sqmm (Nominal Area) drawn in existing conduit / batten / surface all as specified and directed. 66 Supply and fix in repairs PVC insulated and unsheathed single core multi stranded copper conductor 10 Sqmm (Nominal Area) drawn in existing conduit / batten / surface all as specified and directed. 67 All as per Item Ser No 53.00 above but size 16 Sqmm 68 Supply and fix in repairs modular PVC boardcomplete of following sizes all as specified and directed by engir -in -charge. 69 3 Module 70 4 Module 71 6 Module 72 S&F36 watt LED driver in replacement of 2 X 2 ultra slip recess mountedluminaire with high brightness all as per site requirement all as specified and directed byEngr -in -charge. 73 Taking out old US laminated sheet and S & F new laminated super hylem sheet white colour 3mm thick of sizes including fixing of switches, sockets as per existing pattern. (a)Laminated hylum sheet of size 8 x 5 74 All as per Item Ser No 57.00 above but of size5x5 75 All as per Item Ser No 57.00 above but of size 8x10. 76 All as per Item Ser No 57.00 above but of size 8x12. 77 All as per Item Ser No 57.00 above but of size 9x11. 78 S&F EDGEPROSQUARE18/20 watt natural white Slim-Fit low profile downlights are engineered to driver superior light output and uniformity utilising the latest edge-lit LED technoogy Make-Havells /CG/ Wipro all as specified and directed. 79 S&F EDGEPROROUND18/20 watt natural white Slim-Fit low profile downlights are engineered to driver superior light output and uniformity utilising the latest edge-lit LED technoogyof sizeMake-BPSLR 18W LED WH RD SD of Bajaj or equivalent in Havells /CG/ Wipro all as specified and directed. 80 Supply and Fix in repair TL fitting 20watt for surface and wall mounted LED tubehigh lumen output environmental friendly energy efficient..all as specified and directed byEngr -in -charge. 81 S&F or layng in ground1100 volts grade heavy duty flat cable PVC insulated stranded aluminium conductor6 sqmm 2 coreingarden light ,lawn etc including PVC regid conduitpipeAll as per specified and directed by engineer in charge directed .(Note earthwork in garden or lawn has been included ) 82 S&F PVC conduit of size 20mm dia including fixing on wall/ceiling with suitable clamp/saddles for wiring wire all as required at site. 83 S&F PVC conduit of size 25/32 mm dia including fixing on wall/ceiling with suitable clamp/saddles for wiring wire all as required at site. 84 S&FPVC casing caping of size 1 x 1/2 including fixing on wall/ceiling with clamp/saddles for wiring wire all as required at site 85 M & L, for opening covers of ceiling fan, remove the burnt winding, cleaning the slots and rewinding the fan with supper enammeled copper wire of same wire gauge, warnishing after winding, drying, replacing unserviceable fan bearings No 6201/6202 for 1200mm/1400 sweep, greasing, soldering the copper terminal of winding with single core copper multistraded wire of 0.5 sqmm and re-assembling fan, replace of fan capacitor 2.5mfd and making connection with fan capacitor and connector block, transoporting back after repair, assembling the blades, painting and hanging the fan in its own position to existing fan clamp and down rod with necessary Nut, bolt and washer and testing for smooth functioning after complete repair all as ditrected at site. Note :Quoted rate deemed to inclusive of labour charges and items/jobs of fan rewinding, capacitor, fan bearing, servicing, painting, wire and transporatation charges. 86 M & L for opening covers of Exhaust fan up to 450mm sweep, remove the burnt winding, cleaning the slots and rewinding the fan with supper enammeled copper wire of same wire gauge, warnishing after winding, drying, replacing unserviceable fan bush/bearings, greasing, replace of armature coil with complete shaft, soldering the copper terminal of winding with single core copper multistraded wire of 0.5 sqmm and re-assembling fan and making connections, transoporting back after repair, assembling the blades, painting and fixing the E/ fan in its own position with existing clamp with necessary Nut, bolt and washer and testing for smooth functioning after complete repair all as ditrected at site. Note : Quoted rate deemed to inclusive of labour charges and items/jobs of fan rewinding, fan bearing, servicing, painting, wire and transporatation charges. 87 M & L for opening covers of Air circulation fan up to 600 mm sweep, remove the burnt winding, cleaning the slots and rewinding the fan with supper enammeled copper wire of same wire gauge, warnishing after winding, drying, replacing unserviceable fan bush/bearings, greasing, replace of armature coil with complete shaft, soldering the copper terminal of winding with single core copper multistraded wire of 0.5 sqmm and re-assembling fan and making connections, transoporting back after repair, assembling the blades, painting and fixing the E/ fan in its own position with existing clamp with necessary Nut, bolt and washer and testing for smooth functioning after complete repair all as ditrected at site. Note : Quoted rate deemed to inclusive of labour charges and items/jobs of fan rewinding, fan bearing, servicing, painting, wire and transporatation charges. 88 Taking down old existing fitting any type and Supply, fixing and Connecting of LED building security light fitting in top opening LED, highly efficient LED light made of pressure die cast aluminium housing with low power LEDs, direct modular IP lens,IP66 protection and impact resistance of IK07 with 10KV Built-in Surge Protection Device ,lumens should be ≥120 lm/w ,OEM driver,PF 0.9,CCT 5700K complete of capacity 20 wattage. 89 S & F in repair ceiling fan capacitor of capacity4 MFD , 440 V , all as specified and directed 90 S & F in repair pvc square block unbreakable for mounting LED batten on walls , all as specified and directed