| 1 | N.S. Item |
| 2 | Providing and fixing of Tee, Bend and other material for fitting of flow meters with the existing fitting at STP as required at site as per the satisfaction of Engineer-in-charge |
| 3 | `Installation and accessories like Cabling as per siterequirements, Panel Box etc.. Commissioning Charges ofFlow Meter, Customization and programming of flow meter,Configurations as per site requirements and makingconnection with the existing SCADA software / Head Office tothe satisfaction of Engineering In-charge, including one year maintenance charges. Complete in all respects including theConnectivity charges to HSPCB, CPCB and PHED etc.Make:- Forbes Marshall, ABB, SCAN, Endress plus Hauser, Cimcon, Endress Hauser, Schumburger, YLB, Yokogawa, Magnetrol, Danfoss, ultraflux, France, GE, Rosemount(Emerson) with 1 year warranty. |
| 4 | `Supply, Fixing, testing and commissioning of Remote Terminal Unit with power analyzer having inbuilt GSM/GPRS/3G/4G/5G modem. iRTU configuration is 6 Digital inputs, 2 Digital Outputs and 2 Anolog Inputs. iRTU installation inside a panel having isolation transformer. RTU suitable for multi parameter for transferring data to MCS complete in all respect. Complete in all respects including the Connectivity charges to HSPCB, CPCB and PHED Make:- Forbes Marshall, ABB, SCAN, Endress plus Hauser, Cimcon, Endress Hauser, Schumburger, YLB, Yokogawa, Magnetrol, Danfoss, ultraflux, France, GE, Rosemount (Emerson) with 3 year warranty |
| 5 | `Supply, Installation, testing and commissioning Electromagnetic Flow Meter W:Accuracy Class and Display:± 0.5% of measured flow: 2 Line LCD R:Indicator Converter Type: Remote, field mounted 4:Power Supply: Universal Power Supply 85 to 265VAC@45 to 65 Hz 2:Output:4 to 20mA 2:Communication Interface: RS 485 (MODBUS RTU) 0:Data Logger: Not Applicable N:Cable Entry:1/2``NPT 0450:Sensor Size (mm):400 mm (12``) 3:Pressure Rating(Kg/cm2):16 Kg/cm2 D:Design of the Measuring Sensor: Flanged-DIN 1:Flange Material: CS 2:Sensor Lining: PTFE 6:Electrode Material:SS316 1:Earthing ring: None. With built-in earthing electrode. 4:Measuring Tube:SS304 2:Coil Housing: CS 8:Protection Class for Sensor:IP68 P:Approval:Non Hazardous area Cable L=20 mtrs Complete in all respects including the Connectivity charges to HSPCB, CPCB and PHED etc. Make:- Forbes Marshall / ABB / Schumburger / Endress Hauser / YBL /Yokogawa / Magnetrol/ SCAN Ultrasonic Insertion Danfoss, Cimcon, Endress plus Hauser, ABB, Ultaflux, France, GE, Endress plus Hauser, Rosemount (Emerson), ABB. (For Inlet) with 3 year warranty. |
| 6 | Supply, Installation, testing and commissioning Electromagnetic Flow Meter W:Accuracy Class and Display:± 0.5% of measured flow: 2 Line LCD R:Indicator Converter Type: Remote, field mounted 4:Power Supply: Universal Power Supply 85 to 265VAC@45 to 65 Hz 2:Output:4 to 20mA 2:Communication Interface: RS 485 (MODBUS RTU) 0:Data Logger: Not Applicable N:Cable Entry:1/2``NPT 0450:Sensor Size (mm):450 mm (12``) 3:Pressure Rating(Kg/cm2):16 Kg/cm2 D:Design of the Measuring Sensor: Flanged-DIN 1:Flange Material: CS 2:Sensor Lining: PTFE 6:Electrode Material:SS316 1:Earthing ring: None. With built-in earthing electrode. 4:Measuring Tube:SS304 2:Coil Housing: CS 8:Protection Class for Sensor:IP68 P:Approval:Non Hazardous area Cable L=20 mtrs Complete in all respects including the Connectivity charges to HSPCB, CPCB and PHED etc. Make:- Forbes Marshall / ABB / Schumburger / Endress Hauser / YBL /Yokogawa / Magnetrol/ SCAN Ultrasonic Insertion Danfoss, Cimcon, Endress plus Hauser, ABB, Ultaflux, France, GE, Endress plus Hauser, Rosemount (Emerson), ABB. (For By Pass) with 3 year warranty. |
| 7 | `Supply, Installation, Testing, Commissioning, operation and comprehensive Annual maintenance of effluent quality monitoring system at 9.5 MLD STP Kalanwali Town for online (continuous) measurement of pH. Total Suspended Solids (TSS) Chemical Oxygen Demand (COD), Biological Oxygen Demand (BOD) by single analyzer with various sensors (spectral measurement in the UV-VIS range 2000-720 mm) performing reagent and chemical free analysis with automatic cleaning of sensor, single cable and power cables, local data acquisition and display of data on continuous basis for up linking the data to CPCB, HSPCB, PHED, TUV, approved complete in all respect as per central pollution control board (CPCB) guideline for online continuous monitoring system for effluents and as contained in scope of work in the notice inviting tender complete description as per NS item No. 1 of approved DNIT. a) Multi- parameter measuring convertor, for connecting up to 18 intelligent sensors. Scope including 8 analog input/output (4 input and 4 output) (0/4-20m A), wide range power supply optical COD/BOD and TSS probe with spectral processing of the UV VIS range, for measurement in the outlet/effluent/ of municipal waste water treatment plant of 9.5 MLD STP at Kalanwali town with integrated with automatic cleaning. b) Robust digital pH/ORP sensor for p/H/ORP electrodes, with built-in pre- amplifier and temperature sensor with automatic temperature compensation (ATC) cable length 100 meter (minimum).` `c) Sensor adapter cable for all intelligent sensors, with IP68 water proof connection to be intelligent sensors net system) cable length 100 meter (minimum). d) Data transfer to CPCB , HSPCB and PHED servers during 4 years of O and M after commissioning after 3 month trial period (including 4 years of defect liability period ) e) Providing GSM 3G, 4G, 5G modem with mobile network charge for 4 years of O and M after 3 month trial period (including 4 years of defect liability period) Complete in all respects including the Connectivity charges to HSPCB, CPCB and PHED etc. Make:- Lvibond / Systeronics / HATCH / ELICO / Tata Honey Well / Lectro Tex / Aplav / Plico / Systeronics / Forbes Marshall / Polymetron / SWAN / SCAN/ Analytical Instruments / Chemtrols / Dr. Lange / Royce / Endress / Hauser / Hach / Enerson / ABB / Yokogawa / E plus H with 3 year warranty. |