Tender For Provn Of Sheltered Waiting Area For Ch Run Patients Parking Shed Ac In Astra Computer Lab Addn Altn And Special Repairs To Security Office And Provn Of Certain B R Work Services
Tender Value
Ref. Documents
Estimated cost
Bid Submission
02 Oct 2025
0 days left
EMD
2.25 Lakhs
Bank guarantee accepted
Document Fee
1000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Jalahalli → Karnataka
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender For Provn Of Sheltered Waiting Area For Ch Run Patients Parking Shed Ac In Astra Computer Lab Addn Altn And Special Repairs To Security Office And Provn Of Certain B R Work Services
BOQ
| Sl. No. | Item Description |
| 1 | Servicing/ Periodical maintenance of following capacity DG Set of any make consisting of complete servicing and checking entire system as per manufacturer\"s catalogue including testing complete with replacing of minorconsumable itemslike grease, nut bolts etc during conducting periodic servicing as per the manufacturer\"s recommendation at the time of routine monthly checks. Capacity 05 to 15KVA DG Set - Location:- Immols (East)/MI room/IMH area & MGR- 04 No Maintenance Schedule of DG Sets :- The contractor shall carried out following activity during the period of contract :- |
| 2 | (a)Daily maintenance of DG Sets to be carried out :- |
| 3 | (i) Clean the external surface of the DG set. |
| 4 | (ii)Check engine oil level. |
| 5 | (iii) Check engine coolant level. |
| 6 | (iv) Check fuel in the tank. |
| 7 | (v)Check all nuts and bolts. |
| 8 | (vi) Check tension of fan belts. |
| 9 | (vii) Check batteries and battery connections. |
| 10 | (viii)Check fuel lines and fuel tank. |
| 11 | (b)Weekly maintenance of AMF Panels :- |
| 12 | (i) Checking all electrical connections. |
| 13 | (ii)Checking all contact points/ Bus bars. |
| 14 | (iii) Checking timers (AC/ DC). |
| 15 | (iv) Checking all selector switches (voltmeter and Ammeter). |
| 16 | (v)Check RPM, Voltage, Amps and Hz. |
| 17 | (vi) Checking indicator lamps. |
| 18 | (vii) Checking main auxiliary contacts and relays. |
| 19 | (viii)Checking contact coils. |
| 20 | (ix)Checking, volt/ amps/ energy/ PF/ KWH meters/ CT\"s. |
| 21 | (x) Checking auto/ manual functions. |
| 22 | (xi)Check and tight screws and bolts. |
| 23 | (xii)Check battery charger output voltage. |
| 24 | (xiii) Cleaning the panel. |
| 25 | (xiv) Checking all MCCB\"s and fuses. |
| 26 | (xv) Checking alarms and hooter. |
| 27 | (c) Monthly maintenance of DG Sets to be carried out :- |
| 28 | (i)Check oil bath cleaner oil level. |
| 29 | (ii) Check for proper tension in the belts. |
| 30 | (iii) Check starting battery electrolyte level and specific gravity. |
| 31 | (iv) Check the fuel lines from the tank for leakages. |
| 32 | (v) Check the end cover of the alternator and tighten the bolts. |
| 33 | (vi) Check physically the exhaust silencer for rigidness. |
| 34 | (vii) Check the water hoses for leakages if any. |
| 35 | (viii) Drain sediment from fuel filter & fuel tank. |
| 36 | (ix) Check dry type air filter element and clean. |
| 37 | (x) Check engine alternator coupling and mounting bolts. |
| 38 | (xi) Tight all bolts and nuts in alternator terminal box. |
| 39 | (xii)Check for any unusual sound during cranking of the engine. |
| 40 | (xiii)Check for any fuel/ water leakages. |
| 41 | (xiv)Check for any unusual vibrations. |
| 42 | (xv)Check proper charging of battery. |
| 43 | (xvi)Check exhaust system for any leakages. |
| 44 | (xvii) Check for proper circulation of coolant/ cooling of engine. |
| 45 | (xviii) Check physically the exhaust silencer for rigidness. |
| 46 | (xix) Check throttles linkage. |
| 47 | (xx) Checking to electric control panel throttle linkage. |
| 48 | (xxi) Supply and greasing to all bearing & movable parts. |
| 49 | (d)Quaterly Schedule to be carried out :- |
| 50 | (i)Checking of hydraulic governor oil level and toping up level. |
| 51 | (ii) Clean the crank case breather. |
| 52 | (iii)Check battery charging system & topping up electrolyte and maintenance of specific gravity. |
| 53 | (iv) Checking electric connection & generator control panel. |
| 54 | (v) Greasing to all bearing and movable parts. |
| 55 | Note :- The unitrate quoted is deemed to be inclusive of the followings :- |
| 56 | (a)DG Sets are placed at various locations of East, West area of AFS Jalahalli, 2DC area and AFTC. Therefore,the bidders areadvised to visit the location of DG Sets before quoting the tender. |
| 57 | (b)Servicing/ repair of DG Set shall be carried out by authorised dealer/ agency of manufacturer as approved by Engineer-in-Charge and where service/ repair is being carried out at site shall be under the expert supervision of authorised service agent. |
| 58 | (c) The make of DG sets are Kirloskar/ Ashok Leyland/ Greaves Cotton/Mahendra/ Cummins |
| 59 | (d)The contractor shall employ minimum 02 No. manpower (01 -Electrcian , 01 Helper) at each area required for routine maintenance of DG sets. |
| 60 | (e)Filling of DHPP (N) in all mentioned DG Sets at various locations will be the responsibility of the contractor. However, DHPP (N) for filling in DG sets will be issued by MES free of cost through proper NIV. The labour part for filling of DHPP (N) in DG sets is deemed to be inclusive in unit quoted rate. |
| 61 | (f) DHPP (N) required at the time of maintenance/ testing will be issued by MES. |
| 62 | (g)Representative of contractor shall maintain & update the maintenance/ breakdown register regularly and same will be checked by Engineer-in-Charge periodically. |
| 63 | (h)The monthly check shall be done once in a month but whenever breakdown occurs in DG set, the contractor has to attend all complaint unlimitedly through authorised service agent of the equipment/ machinery. |
| 64 | (j)The unit rate is deemed to be included for Cleaning of the surrounding area of DG set upto 5 mtr from plinth protection ofE/M installations includingremoving of accumulated earthof any width and depth upto 15cm cleaning / Cutting the grass with hand operated petrol/ kerosene driven grass cutting machine andremoving thegrass waste to outside MD land. |
| 65 | (k)In case of minor defect, entire Job shall be completed within 06 hrs from the time of registration of complaint, failing which penalty charges @ Rs. 500/- per hours shall be recovered from the contractor. |
| 66 | (l)In case of major defect, the period for attending of complaint shall be decided by the GE/EIC by assessing the extent of repair required through joint inspectionby Engineer-in-Charge and authorised service agent of the equipment at the site. If complaint is not rectified within the stipulated period and the GE is not satisfied with the reason for delay, then penalty at the rate of Rs. 600/- per hours shall be deducted from the dues of the contractor. |
| 67 | (m)Please note that above penalty is exclusively other than the condition 67 of IAFW - 2249 and shall be treated as interim condition of the contract and shall be enforced as and when delay in individual job is noticed and no claim whatsoever on this account shall be entertained by the Deptt. |
| 68 | (n) The decision of the Accepting Officer in this regard shall be final and binding. |
| 69 | (o)The contractor shall be responsible to maintain the DG set in serviceable condition for entire contract period. |
| 70 | Description all as per Sl Item No. 01 here in before but for Capacity 20-25KVA DG Set- Location:-2DC area & logistics/ E&ITI/ Sub guard room at ETI & E & ITI -4 Nos |
| 71 | Description all as per Sl Item No. 01 here in before but for Capacity 30KVA DG Set- Location:-Tele. Exchange( East)/E&ITI UEB HALL -2 Nos |
| 72 | Description all as per Sl Item No. 01 here in before but for Capacity 40 KVA DG Set - Location:- Tele Exch :- 01 No |
| 73 | Description all as per Sl Item No. 01 here in before but for Capacity 45 KVA DG Set - Location:-2 AFDC (East)-01 No |
| 74 | Description all as per Sl Item No. 01 here in before but for Capacity50KVA DG setLocation:-AFTC Perimeter/MES Service Centre/MES IB:- 3 Nos |
| 75 | Description all as per Sl Item No. 01 here in before but Capacity 62.5 KVA DG - Location:-Double tank PH &IW School -2 Nos |
| 76 | Description all as per Sl Item No. 01 here in before but for Capacity82.5 KVA DG set, Location:-90 Civ Pump House-1 No |
| 77 | Description all as per Sl Item No. 01 here in before but for Capacity 100 KVA DG set location- ETI Comp. Lab/ETIUEB HALL/ E & ITI Comp. Lab/CTI AFNET- 04 Nos |
| 78 | Description all as per Sl Item No. 01 here in before but for capacity125 KVA DG set Location:-Range pump house/Tech area & LATs Complex/AFTC Pump House :- 4 Nos |
| 79 | Description all as per Sl Item No. 01 here in before but for capacity 160KVA DG Set/ Gurukul-01 No |
| 80 | Description all as per Sl Item No. 01 here in before but for capacity 200 KVA DG Set Location-SMC - 01 No |
| 81 | Description all as per Sl Item No. 01 here in before but for capacity 250 KVA DG SetLocation:-CTI - 01 No |
| 82 | Description all as per Sl Item No. 01 here in before but for capacity 400 KVA DG Set Location:- SMC, Gurukul and New Auditorium AFTC -03 No |
| 83 | Dismantling/ taking down complete radiator assembly of 15 KVA to 30 KVA DG Set and transportation to authorised workshop for following repairs :-(a) Opening the radiator assembly with brazing/ welding for repair/ service.(b)Cleaning of all water tube with diluted solution of HCL and cleaning with water pressure and removing the sludge and dust from inside the tank by flushing out.(c)Determining the leak/ puncher in radiator tubes.(d)Repair of fins by soldering/ brazing.(e)Repair of bottom brass water tank by soldering/ brazing.(f) Repair of radiator hose assembly.(g)Fixing the complete radiator assembly to its original position and testing complete all as specified and directed by Engineer-in-Charge. |
| 84 | Dismantling/ taking down complete radiator assembly of 40 KVA to 50 KVA DG Set and transportation to authorised workshop for following repairs :-(a) Opening the radiator assembly with brazing/ welding for repair/ service.(b)Cleaning of all water tube with diluted solution of HCL and cleaning with water pressure and removing the sludge and dust from inside the tank by flushing out.(c)Determining the leak/ puncher in radiator tubes.(d)Repair of fins by soldering/ brazing.(e)Repair of bottom brass water tank by soldering/ brazing.(f) Repair of radiator hose assembly.(g)Fixing the complete radiator assembly to its original position and testing complete all as specified and directed by Engineer-in-Charge. |
| 85 | Taking down old unserviceable self motorof capacity 5 KVA to 15 KVAand carrying to authorised work shop for servicing includingreplacement of unserviceable spare parts Brush, holder, solonoid switch, armature bush, filed coil complete and refixing, testing all as specified and directed. |
| 86 | Taking down old unserviceable self motorof capacity 20 KVA to 45 KVAand carrying to authorised work shop for servicing includingreplacement of unserviceable spare parts Brush, holder, solonoid switch, armature bush, filed coil complete and refixing, testing complete all as specified and directed. |
| 87 | Removing and replacing the old unserviceable with new AVR (Automatic Voltage Regulator) suitable for Kirloskar curve of capacity 15 to 82.5KVA having input voltage 2 phase + neutral sensing voltage 415 output voltage 95V DC, output current 4A DC voltage regulation +/- 1 % average volts, over excitation current tripping, fuse protection 4A, fast acting and frequency 50 Hzcomplete all as specified and directed. |
| 88 | Material and labourOpening disconnecting LT Cable connections with care from Auto-Main Failure Panel and checking throughly with Fault Detector Instrument at Site and replacement of Minor Defective Parts as required at Site suitable for 7.5 KVA to 82.5 KVA DG Set including replacement of Internal Wiring with Copper Conductor Cable, Beading, etc. complete all as specified and as directed. |
| 89 | Supply and fixingin replacement of Fly wheel ringincluding nuts and bolt suitable for DG Set 7.5 to 62.5 KVA capacity as per existing make complete all as specified and directed. |
| 90 | Material and labourfor servicing/ cleaning of MS diesel tank of DG Set of 20 to 50 KVA capacity by draining out the diesel from tank, cleaning the tank with soap water/ suitable solution and painting the external surface with one coat of synthetic enamel paint of existing colour including replacement of drain valve, outlet pipe complete all as specified and as directed. |
| 91 | Supply and fix in replacement of DGcontroller unitsuitable for DG set 7.5 KVA to 45 KVA of as per existing Make complete all as specified and as directed. |
| 92 | Supply and fixingin replacementcontactor 4 pole,with 1 NO + 1 NC aux contacts and coil voltage 240 V/415 volt suitable for AMF Panels of 5 to 7.5KVADG Set complete all as specified and as directed. MAKE : L&T/BCH/Schneider |
| 93 | Supply and fixingin replacementcontactor 4 pole,with 1 NO + 1 NC aux contacts and coil voltage 240 V/415 volt suitable for AMF Panels of 10 to 15 KVADG Set complete all as specified and as directed. MAKE : L&T/BCH/Schneider |
| 94 | Supply and fixingin replacement microprocessor based AMF controller unit for AMF Panel flush mounting type suitable for DG Set 7.5 to 62.5 KVA capacity as per existing make complete all as specified and directed. |
| 95 | Disconnecting the electrical connection from AMF Panel, taking down DG set of cap 40 to 62.5 KVA for major overhauling of engine and transportationto authorised workshop forreplacement of piston assembly complete-4 sets, exhaust valve, cyilinder liner, inlet and outlet valves, sealing cap, copper washers,thermostat elements, spin of filter for lubrication oil, oil seal, valve tappet, gasket for cylinder head, bush for injector, gasket for exhuast manifold,joint for bearing housing, joint for delivery volute, turbo repair kit complete all as specified & directed. |
| 96 | Supply & fix in replacement Cooling Fan (as per existing/ as approved by GE) suitable for DG Set 15 to 50 KVA capacity, complete all as specified and as directed. |
| 97 | Supply and fixingin replacement ofwiring kit of AMF panel of capacity DG set with copper wire ,PVCwire holder and other connected items suitable for DG Set 7.5 to 62.5 KVA capacity as per existing make complete all as specified and directed. |
| 98 | Supply and fixingin replacement Cooling Fansuitable for DG Set 7.5 to 62.5 KVA capacity, complete all as specified and as directed. |
| 99 | Supply and fixing in repairs door beeding gasket for DG of 15 KVA to 50 KVA capacity complete all as specified and directed. |
| 100 | Supply and fix in replacement of selectorswitch 16 A 2 pole 2 way complete all as specified and as directed. |
| 101 | Supply and fix in replacement of RPM meter assembly complete set including rubber gasket, wire as per sample complete all as specified and as directed. |
| 102 | Supply and fix in replacement of electronictimer delay of range12 sec to 120 sec operational in 240V AC supply complete all as specified and directed. Make:- Selectron or equivalent |
| 103 | Supply and fixingin replacement of Relay for control contactor AC control std. Coil Voltage - 24, 110, 240, 415V, 50Hz (2 NO + 2 NC) complete all as specified and directed. Make L& T / BCH/ ABB |
| 104 | Supply and fixingMCCB 250A, 36 KA, 4 Pole, 415V including taking down unserviceable one, complete all as specified and as directed. Make - L&T/ Havells/Indoasian |
| 105 | Supply and fix in replacement of 12V/24V 11 pin PLA relay with base all as specified and as directed. |
| 106 | Supply and fix in replacement of oil drain hose set complete all as specified and as directed. |
| 107 | Material and labourfor battary electrolyte grade 1250 complete all as specified and directed. |
| 108 | Supply and fix in replacement of radiatorfan belt suitable for any capacity DG set complete all as specified and as directed. |
| 109 | Supply and fix in replacement of Relay for single phase preventor 6 wire suitable for all mode operation all as directed. |
| 110 | Supply and fix in replacement of push button for Start/Stop switch allas per sample complete all as specified and as directed. |
| 111 | Supply and fixingin replacement maintenance free lead acid sealed battery (SMF) 12 volts 100 AH complete all as specified and as directed.Make : EXIDE. / Amaron/ Amar Raja/CumminsNote :-Old battery shall be deposited in MES store yard. |
| 112 | Supply and fixingin replacement maintenance free lead acid sealed battery (SMF) 12 volts 90 AH complete all as specified and as directed.Make : EXIDE. / Amaron/ Amar Raja/CumminsNote :-Old battery shall be deposited in MES store yard. |
| 113 | Taking down 12/ 24 volts self starter assembly from DG set and transporting to its authorised workshop for repair/ servicing by replacement of defective spare parts such as carbon brush, carbon ring, bearing, bush, defective wiring, winding and soldering after repair including testing after repair/ service and re-installation in original position for satisfactory functioningcomplete all as specified and directed. |
| 114 | Supply and fixingin replacement self starter 24 Volts of DG Setscomplete all as specified and directed. |
| 115 | Supply and fixingin replacement battery cable assembly (-ve & +ve) complete all as specified and directed.Note :- Items like clamp, lugs, nut, bolts and copper cable of size 25 sqmm upto 1 mtr required for connection is deemed to be inclusive in unit rate quoted. |
| 116 | Dismantling/ taking down complete radiator assembly of 62.5 KVA to 100 KVA DG Set and transportation to authorised workshop for following repairs :-(a) Opening the radiator assembly with brazing/ welding for repair/ service.(b)Cleaning of all water tube with diluted solution of HCL and cleaning with water pressure and removing the sludge and dust from inside the tank by flushing out.(c)Determining the leak/ puncher in radiator tubes.(d)Repair of fins by soldering/ brazing.(e)Repair of bottom brass water tank by soldering/ brazing.(f) Repair of radiator hose assembly.(g)Fixing the complete radiator assembly to its original position and testing complete all as specified and directed by Engineer-in-Charge. |
| 117 | Dismantling/ taking down complete radiator assembly of 125 KVA to 200 KVA DG Set and transportation to authorised workshop for following repairs :-(a) Opening the radiator assembly with brazing/ welding for repair/ service.(b)Cleaning of all water tube with diluted solution of HCL and cleaning with water pressure and removing the sludge and dust from inside the tank by flushing out.(c)Determining the leak/ puncher in radiator tubes.(d)Repair of fins by soldering/ brazing.(e)Repair of bottom brass water tank by soldering/ brazing.(f) Repair of radiator hose assembly.(g)Fixing the complete radiator assembly to its original position and testing complete all as specified and directed by Engineer-in-Charge. |
| 118 | Taking down old unserviceable self motorof capacity 50 KVA to 160 KVAand carrying to authorised work shop for servicing includingreplacement of unserviceable spare parts Brush, holder, solonoid switch, armature bush, filed coil complete and refixing, Testingcomplete all as specified and directed. |
| 119 | Removing and replacing the old unserviceable AVR (Automatic Voltage Regulator) suitable for capacity 100 to 160KVA having input voltage 2 phase + neutral sensing voltage 415 output voltage 95V DC, output current 4A DC voltage regulation +/- 1 % average volts, over excitation current tripping, fuse protection 4A, fast acting and frequency 50 Hzcomplete all as specified and directed. |
| 120 | Material and labourOpening disconnecting LT Cable connections with care from Auto-Main Failure Panel and checking throughly with Fault Detector Instrument at Site and replacement of Minor Defective Parts as required at Site suitable for 100 KVA to 160KVA DG Set including replacement of Internal Wiring with Copper Conductor Cable, Beading, etc. complete all as specified and as directed. |
| 121 | Supply and fixingin replacement of Fly wheel ringincluding nuts and bolt suitable for DG Set 82.5 to 160 KVA capacity as per existing make complete all as specified and directed. |
| 122 | Material and labourservicing/ cleaning of MS diesel tank of DG Set of 62.5-160 KVA capacity by draining out the diesel from tank, cleaning the tank with soap water/ suitable solution and painting the external surface with one coat of synthetic enamel paint of existing colour including replacement of drain valve, outlet pipe complete all as specified and as directed. |
| 123 | Supply and fixingin replacement ofwiring kit of AMF panel of capacity DG set with copper wire ,PVCwire holder and other connected items suitable for DG Set82.5 to 160 KVA capacity as per existing make complete all as specified and directed. |
| 124 | Supply and fixing in repairs door beading gasket for DG of 62.5 KVA to 160 KVA capacity complete all as specified and directed. |
| 125 | M & L for supply and replace HRC fuse square type suitable for 82.5 to 200 KVA DG set by taking out the defective use and changing, connecting and testing the same on load all as specified and directed . |
| 126 | Supply and fixingin replacementcontactor 4 pole,with 1 NO + 1 NC aux contacts and coil voltage 240 V/415 volt suitable for AMF Panels of 20 to 25 KVADG Set complete all as specified and as directed. MAKE : L&T/BCH/Schneider |
| 127 | Supply and fixingin replacementcontactor 4 pole,with 1 NO + 1 NC aux contacts and coil voltage 240 V/415 volt suitable for AMF Panels of 30 to 45 KVADG Set complete all as specified and as directed. MAKE : L&T/BCH/Schneider |
| 128 | Supply and fixingin repairs change over switch 100 Amps capacity 4 pole 3 phase with enclosure complete all as specified and directed. Make-Legrand/ L&T / Indoasian |
| 129 | Supply and fix in replacement of DGcontroller unitsuitable for DG set 50 KVA to 100KVA of as per existing Make complete all as specified and as directed. |
| 130 | Supply and fixingin replacement Cooling Fansuitable for DG Set 82.5 to 160 KVA capacity, complete all as specified and as directed. |
| 131 | Supply and fixingMCCB 200A, 36 KA, 4 Pole, 415V including taking down unserviceable one, complete all as specified and as directed. Make - L&T/ Havells/Indoasian |
| 132 | Supply and fix in replacement ofelectronic Oil pressure sensor complete with wiring, connectors, bottle thimble all as directed |
| 133 | Supply and fix in replacement of radiator hose of any capacity complete all as specified and directed. |
| 134 | Material and labourfor replacement of door hinges of Acoustic enclosureheavy duty metal type for Left/Right side complete all as specified and directed. |
| 135 | Material and labourfor distilled water in 5 ltr/ 2 ltr sealed cane to be filled in batteries complete all as specified and directed. |
| 136 | Disconnecting the existing battery of capacity 12V 90 to 180 AH from the DG set, taking it to battery workshop, draining out the complete unserviceable electrolyte acid from the battery, filling up with new Electrolyte acid to the required level, charging the battery, testing the battery for correct specific gravity, bringing back to the location, connecting to DG set, start the engine for satisfactory functioning all as directed by Engineer-in-charge. |
| 137 | Supply and fixing in replacement of brass terminal suitable for 12 Volts, 90/130/150/180 AHbattery complete all as specified & directed. |
| 138 | Supply and fixingBattery charging alternator assembly 12 Volts of DG Sets complete including taking down existing one complete all as specified & directed. |
| 139 | Material and labour for repairs to 12V battery charging alternator assembly by removing, dismantling, replacing the unserviceable burnt rotor and stator assembly completly including insulation sleeves and refixing to the engine and testing to the satisfaction of DC volts & Ampsby charging of battery complete all as specified & directed. |
| 140 | Supply and fixingin replacement maintenance free lead acid sealed battery (SMF) 12 volts 130 AH complete all as specified and as directed.Make : EXIDE. / Amaron/ Amar Raja/Cummins Note :-Old battery shall be deposited in MES store yard. |
| 141 | Supply and fix in replacement of lubrication oil filter element with \"O\" ring of Make MICO / Kirloskar / Mahle/ Cummins as required at site for 5 to 7.5KVA capacities of DG Sets complete all as specified and as directed. |
| 142 | Supply and fix in replacement of lubrication oil filter element with \"O\" ring of Make MICO / Kirloskar / Mahle/ Cummins as required at site for 15KVA capacities of DG Sets complete all as specified and as directed. |
| 143 | Supply and fix in replacement of lubrication oil filter element with \"O\" ring of Make MICO / Kirloskar / Mahle/ Cummins as required at site for 20to 22.5KVA capacities of DG Sets complete all as specified and as directed. |
| 144 | Description all as per sl item No 143 here in before but25 KVADG set. |
| 145 | Description all as per sl item No 143 here in before but 30 KVADG set. |
| 146 | Description all as per sl item No 143 here in before but 40 KVADG set |
| 147 | Description all as per sl item No 143 here in before but45 KVA DG Set |
| 148 | Description all as per sl item No 143 here in before but 50 KVADG set. |
| 149 | Description all as per sl item No 143 here in before but 62.5 KVADG set. |
| 150 | Description all as per sl item No 143 here in before but82.5 KVADG set |
| 151 | Description all as per sl item No 143here in before but100 KVADG set |
| 152 | Description all as per sl item No 143 here in before but125 KVADG set |
| 153 | Description all as per sl item No 143 here in before but 160 KVADG set |
| 154 | Description all as per sl item No 143 here in before but 200 KVA DG Set |
| 155 | Description all as per sl item No 143 here in before but 400 KVA DG Set |
| 156 | Supply and fixingin repairs earth Fault relay complete all as specified and directed. |
| 157 | Supply and fix in replacement of turbo cooler rubber hose of any capacity complete all as specified and as directed. |
| 158 | Supply and providing coolant concentrate in sealed container for top up complete all as specified and directed.Make : Valvoline/ Fleet guard/ Mahle |
| 159 | Supply and fix in replacement of electronic Fuel Level sensor complete with wiring, connectors, bottle thimble complete all as specified and directed. |
| 160 | Supply and fix in replacement of radiator mounting pad set of any size complete all as specified and directed. |
| 161 | Supply and fix in replacement of oil seal assembly of any capacity as per sample complete all as specified and directed. |
| 162 | Supply and fixingMCCB 400A, 3P, 36 KA, 415V, including taking down unserviceable one, complete all as specified and as directed. Make -L&T / Havells/Indoasian |
| 163 | Supply and fixingin replacementcontactor 4 pole,with 1 NO + 1 NC aux contacts and coil voltage 240 V/415 volt suitable for AMF Panels of 50 to 63 KVADG Set complete all as specified and as directed. MAKE : L&T/BCH/Schneider |
| 164 | Supply and fix in replacement of add-on auxilury contactorblock 2No-2NC complete all as specified and as directed. |
| 165 | Supply and fix in replacement of Auto source transfer controller unitsuitable for 400 KVA DG set AMF panel of any capacity and as per existing Make complete all as specified and directed. |
| 166 | Supply and fixing in repairs electronic type diesel float switch assembly complete all as specified and directed. |
| 167 | Supply and fixing in repairs mechanical type diesel float switch assembly complete all as specified and directed. |
| 168 | Supplyand Replacement of fuel filter element with \"O\" ring of Make MICO / Kirloskar / Mahle/ Ashok Leyland/ Cummins as required at site for 5 to 7.5 KVA capacities of DG Setsall as directed by Engineer-in-Charge. |
| 169 | All as per item No 168 here in before but15 KVADG set. |
| 170 | All as per item No 168 here in before but 20 to 22.5 KVADG set. |
| 171 | All as per item No 168 here in before but 25 KVADG set. |
| 172 | All as per item No 168 here in before but 30 KVADG set. |
| 173 | All as per item No 168 here in before but40 KVADG set |
| 174 | All as per item No 168 here in before but45 KVA DG Set |
| 175 | All as per item No 168 here in before but50 KVADG set. |
| 176 | All as per item No 168 here in before but62.5 KVADG set. |
| 177 | All as per item No 168 here in before but82.5 KVADG set |
| 178 | All as per item No 168 here in before but100 KVADG set |
| 179 | All as per item No 168 here in before but 125 KVADG set |
| 180 | All as per item No 168 here in before but 160 KVADG set |
| 181 | All as per item No 168 here in before but 200 KVA DG Set |
| 182 | All as per item No 168 here in before but 250 KVA DG Set |
| 183 | All as per item No 168 here in before but 400 KVA DG Set |
| 184 | Supply and fix in replacement of flush type LED Digital multi functional meter withparameter (V,I,PF) suitable for DG set AMF panelcompleteof Model A class 1 complete all as specified & directed. |
| 185 | Supply and fix in replacment of valve door packing of any capacity complete all as specified and directed. |
| 186 | Supply and fixing in repairs door glass and beading for DG Set of any capacity complete all as specified and directed. |
| 187 | Supply and fixingin replacementcontactor 4 pole,with 1 NO + 1 NC aux contacts and coil voltage 240 V/415 volt suitable for AMF Panels of 82.5KVADG Set complete all as specified and as directed. MAKE : L&T/BCH/Schneider |
| 188 | Supply and fixingMCCB 400A, 4P, 36 KA, 415V, including taking down unserviceable one, complete all as specified and as directed. Make -L&T / Havells/Indoasian |
| 189 | Supply and fix in replacement of selectorswitch 16 A 3 pole 3 way complete all as specified and as directed. |
| 190 | Supply and fixingin repairs change over switch 63 Amps capacity 4 pole 3 phase with enclosure complete all as specified and directed. Make-Legrand/ L&T / Indoasian |
| 191 | Supply and fixing in replacement indicator lamp RYB complete all as specified and as directed. |
| 192 | Material and labour for removing old paint from surface of acoustic enclosure and outer canopy, alternater upto 125 KVA with sand paper and painting complete DG set & panel board including canopy with synthetic enamel paint (of colour as directed by Engineer-in-Charge) using spray gun with compressed air and writing Ser No./ MES No. in block letters with white paint and size of letter n.exc 30 cm height complete all as specified and as directed. |
| 193 | Supply and fix in replacement of fuelhose set nylon type of any capacity complete all as specified and directed. |
| 194 | Supply andfix in replacement of water pump assembly of water cooling system of DG set any capacity complete all as specified and directed. |
| 195 | Supply and fixingin replacement stop solenoid assembly 12V/ 24V DC for micro pump (two coil) heavy duty electrical control make energise to stop of DG Setscomplete all as specified and directed.Make :- Kirloskar or existingbrand of defective components or any reputed suitable make as approved by GE |
| 196 | Supply and fixingin replacement self starter 12 Volts of DG Sets complete all as specified and directed. |
| 197 | Supply and fixingin replacement maintenance free lead acid sealed battery (SMF) 12 volts 150 AH complete all as specified and as directed.Make : EXIDE. / Amaron/ Amar Raja/Cummins Note :-Old battery shall be deposited in MES store yard. |
| 198 | Supply and fixing in repairs 24V DC solenoid switch complete all as specified and directed. |
| 199 | Material and labourfor lubrication oil SAE 15 W - 40grade API CI 4 plustype in sealed container for DG set Top up and change the oil in the sump after completely flushing the old oil from the tank/sump and cleaning the same complete all as specified and as directed. (Make : Castrol/Valvoline/Servo) |
| 200 | Supply and Fix in replacement of temeprature guage of any capacity complete all as specified and as directed. Make:- Kirloskar/Greaves or equivalent. |
| 201 | Taking down carefully DG set of any capacity from foundation after disconnecting nuts, bolts, earthing lead, LT connection cable etc and shifting within a distance of 12 Km for repair / refilling of foundation or reinstallation after repair including making connections of cables complete all as specified and directed. Note: Weight of DG set is between 1 to 2 ton, necessary T & P and lifting arrangement shall be contractor responsibility and the unit rate quoted shall be deemed to include the same. |
| 202 | Supply and fixingin replacementcontactor 4 pole,with 1 NO + 1 NC aux contacts and coil voltage 240 V/415 volt suitable for AMF Panels of 100 KVADG Set complete all as specified and as directed. MAKE : L&T/BCH/Schneider |
| 203 | Supply and fix in replacement of electronic water temp gauge sensor double pin in byepass complete with wiring, connectors, bottle thimble complete all as specified and directed. |
| 204 | Material and labourreplacement of existing unserviceable door lock arrangement to DG set canopywith new door lock & key etc as per existing size & type complete all as specified & directed. |
| 205 | Supply and fixingON LOAD change over switch 4 pole 400 A with sheet metal enclosure in LT panel boards/ feeder pillar boxes including disconnecting and removing existing defective item from electric circuit including necessary connected fasteners, burnt cables, accessories etcall as per site requirement/existing make/model all as specified and as directed.Make:L&T/ HAVELLS/INDO ASIAN |
| 206 | Supply and fix in replacement of electronic water temp gauge sensor single pin for engine block complete with wiring, connectors, bottle thimble complete all as specified and directed. |
| 207 | S & F Pre- painted galvalume aluminium zinc coating GI based corrugated steel sheet 0.50mm thick of any colour having tensile strength of 550 Mpa as in roof covering/ cladding to wall, fixed with self tapping screws & including dismantling of any type of sheets in roof coverings complete all as specified & directed |
| 208 | Dismantling structural steel work incl doors, gates but excluding framed trusses etc complete all as specified and directed. |
| 209 | S&Fin framed work as in doors or gates of angle,tubes or other section with gusset plates, rails, Plain sheet braces,guard bar etc., complete, to be prepared for hanging or sliding with and includinghinges or steel hanging door fittings (exclusive of steel sheeting or other covering) and hanging; also fastening and fixing Fe 410 -W (Gde- E- 250) quality-A complete all as specified and directed. |
| 210 | S & F MS Steel work in tubular trusses including special shaped washer etc. complete using ERW or induction butt welded tubes conforming to I. S.1161 1979 grade St.-240 complete all as specified & directed |
| 211 | M&L for welding in repairs not exceeding 10 Cm length & thickness of metal to be welded not exceeding 6mm comlete all as spcified and directed. |
| 212 | M & L Providing two coats of synthetic enamel paint over a coat of red oxide primer on steel surfaces over 10 cm width or girth including preparation of new steel surfaces complete all as specified and directed. |
| 213 | M & L for 100 mm thick PCC 1:2:4 type B-2 (using 40mm graded crushed stone agg) as in PCCin Hard standing etc.with , spike rolling ,or making impression of expanded metal, while the concrete is green complete all as specified including Demolition of old Concrete (un reinforced) of any description and in anypositionnot otherwise specifically provided. |
| 214 | Forming Construction joints 30 mm deep x 10 mm wide filled with epoxy sealing compound grade \"A\" complete all as specified and directed. |
| 215 | M&L for cement plaster rendering 15mm thick on fair faces of brick/concrete surfaces with two coats i.e. (10mm thick backing coat in CM 1:6 and 5mm thick finishing coat in CM 1:4), finished even and smooth without using extra cement and including taking down old cement plaster on brick or stone walls, or concrete walls etc., hacking for key, scrubbing down with water, etc., including removal of rubbish off the premises complete all as per specified and directed. |
| 216 | M&L preparation of newly plastered surfaces and applying three coats of white washing on walls surfaces complete all as specified and directed. |
| 217 | M&L for Preparation of old painted surfaces of steel and applying one coat of synthetic enamel paintover 10 cm width or girth, not other wise describedcomplete all as specified and as directed. |
| 218 | Site clearance by Scraping of grass/wild growth/trees n.exc 0.30m girth etc in soft/loose soil by manually/mechanically including removing of rubbish from the site to a distance exc, 250m but n. exc 500m and deposited where directed at a level not exc. 1.5m above the starting point, complete all as specified and as directed |
| 219 | M&L for machine pressed pre polished pre-cast concrete interlocking paver block any shape and size confirming to IS 15658-2006 of 60mm thickness, M-35 Grade over sand cushion with grey cement and no pigment and side kerb concrete, incl removal debris and necessary demolition all as specified and directed by Engr-in-Charge. |
| 220 | M & L for Sand filling under floors or in foundations including watering and consolidation and all as specified and directed. |
| 221 | Dismantling posts or struts (wood, steel, or RCC) any section, any length not exc 5m including taking out embedded portion in concrete, brick work, masonry etc and all as specified and directed and incl necessary excavation and earthwork for new post holesall as specified and directed. |
| 222 | M&L for Cement concrete 1:3:6 type C2 (using 40 mm graded stone agg) as in foundation filling and for mass concrete complete all as specified and directed |
| 223 | S & FMS angle iron hand rails, fencing posts, flat iron including embeding in concrete and screwing etc. wind ties for roof including securing bolts;posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire, etc.; flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting, etc., and similar work conforming to Fe-290 Gde E-165 complete all as specified and directed. |
| 224 | S&F MS round bars 10 mm dia and overFe 290 (Gde - E-165) cut to length bent to shape required including cranking, bending spirally, hooping for columns, hooking ends all as specified and directed. |
| 225 | S &F Mild steel screw bolts (machine made) dia of neck 16 to 20mm with hexagonal or square heads at one end and screwed the other, or screwed both ends, each screwed end to be fitted with washers and one hexagonal or square nut, n exc 5cm long all as specified and directed. |
| 226 | Supply only of chain link fencing MS galvanised sqaure wire mesh of any size, dia of wire 4mm including line wires, to any type of standard rails, straining bolts, etc all as specified and directed. |
| 227 | Fixing only in repairs chain link fencing including line wires, any mesh, size and type to any type of standards, rails, straining bolts, etc inlcuding provision of binding wire and dismantling fencing wire mesh of any typeetc all as specified and directed. |
| 228 | M&L for Cement concrete 1:3:6 type C2 (using 40 mm graded stone agg) as in foundation filling and for mass concrete and all as specified and directed including Demolition ofConcrete (un reinforced) of any description and in anypositionnot otherwise specifically provided. . |
| 229 | M&LPre-Cast cement concrete block masonry PCC 1:3:6 type C1 (20 mm graded agg) with solid blocks exc. 10cm in width and set in cement mortar 1:6 including demolition of brick work / stone masonry/PCC block built in cement mortar of any description as specified and directed. |
| 230 | M & L rendering 15 mm thick CM 1:4 on brick or concrete surfaces finished even and smooth with out using extra cement complete all as specified and directed. |
| 231 | M&L Preparation of newly plastered surfaces of walls and applying two coats cement base paint on walls over a coat of alkali resistant primer all as specified and directed. |
| 232 | M&L in plain cement concrete PCC coping 1:2:4 type B1 (using 20 mm graded stone agg) including necessary form work as specified and directed. |
| 233 | M&L Plain cement concrete (1:3:6) type C1 (20 mm graded stone aggregate), 75mm thick, as in plinth protection courses/footpath, top surface of concrete finished even and smooth with out using extra cement,including expansion joint 10mm thick filled with mastic filling comprising of 01 part of heated blown beitumen and 3 parts of sandincluding demolition existing cement concrete including disposal of demolition material upto MD land complete all as specified and directed by Engineer-in-charge |
| 234 | Renewingcement concrete tilesin patches, area n exc 5 sqm including removing and cleaning old tiles, preparing beds and laying or setting, jointing and pointing new or old tilescomplete all as directed.Note : The rate included for cutting out broken tiles, removing and cleaning loose tiles, preparing bed removing rubbish, removing and replaing old with new tiles to match, complete with all cuttings etc, that may be required. New tiles requiredis deemed to be included all as directed. The unit rate is also including necessary beding in cement mortor/Sand filling. |
| 235 | M&L for preparation of new/old any type ofsurfaces ofany description, over 10 cm width or girth, not otherwise described and applying two coats of floor guard paint over a coat of red oxide primer complete all as specified and directed. |
| 236 | M&L for broken stone boulders hard core of guage n.exc 63mm deposited spread and level laid in layers n.exc 15cm thick, watered and rammed to a true surface in repairs complete all as specified and directed. |
| 237 | M&L in repairs 300x300x25mm thick prepolished cement concrete chequered tiles jointed in neat cement slurry and pointed in white or coloured cement to match the floor and including 20mm thick screed bed in CM 1:4 and incl removal of old debris and including necessary demolition of old unserviceable tiles etc complete all as specified and directed |
| 238 | M&L PCC (1:4:8) type D2 using 40mm graded aggregate 75mm thick as in sub base of floor finished even and rough to receive top layer and all as specified and directed including Demolition ofConcrete (un reinforced) of any description and in anypositionnot otherwise specifically provided. |
| 239 | Material and labourfor Preparation of old decoratedplastered or unplastered surfaceof wall, brooming down or steel wire brushing down smoke soot, moulds mass, efflorescent , trading, oil, greasy spots and applying one coat of cement based paint complete all as specified and as directed. |
| 240 | Material and labourfor Preparation of old decoratedplastered or unplastered surfaceof wall, chajja, balcony, facia etc., brooming down or steel wire brushing down smoke soot, moulds mass, efflorescent, trading, oil, greasy spots and applyingone coat of whitewashcomplete all as specified and directed. |
| 241 | Excavation in trenches not exceeding 1.5 mtr in width and not exceeding 1.5 mtr in depth for laying of cables up to proper level and laying of pipelines etcinsoft/loose soil, complete all as specified and directed. |
| 242 | Returning, filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm thick, complete all as specified and directed. |
| 243 | Removing surplus excavated material (soil) not exc 50 meter and depositing where directed at a level not exc 1.5 meter above the starting point, complete all as specified and directed. |
| 244 | Material and labour for Spreading ribbed soil in trenches as in cable cushioning all as per IS 1255-1983, complete all as specified and directed.Note :- (i)Excavated approved soil shall be ribbed by using sieve to separate composite particles etc. as per IS and refilling in trenches before laying of cable 8 CM and 15 CM after laying of cable. This is then gently punned down to a depth of 10 cm above the top of upper most cable (ii) For the purpose of measurement only punned thickness shall be considered for payment. |
| 245 | Material and labour for well burnt bricks ‘B’ class as mechanicalprotection to under ground cables laying with length of the bricks equal to the width of the trench, complete all as specified and directed. |
| 246 | Material and labour for Cutting existing road/PCC/Drain for laying of GI or any type of pipe including necessary earthwork, excavation exc 600mm depth but not exc 1mtr depth, 800 mm wide including making good existing surface with 150 mm thick PCC 1:2:4 type B1 using 20mm graded stone aggregate, complete all as specified and directed. Note :-The tenderer shall take into consideration for following points while quoting rate for this item andthe unit rate is deemed to be inclusive for :-(i) Earth work and excavation in any type of soil(ii) Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 cm thick ,complete all as specified and as directed.(iii) Removing excavated material out side MD land.(iv)Laying of any type/any bore of pipe in trenches including taking down existing unserviceable pipe. Supply of pipe shall be measured and paid separately(v)150 mm thickPCC 1:2:4 type B1 using 20mm graded stone aggregate as inroad to make good existing disturbed surfaces. |
| 247 | Supply and laying of GI pipe light grade for cable protection of size 100mm bore complete with fitting completeincluding taking down unserviceable one all as inspecified and directed. |
| 248 | Material and labour in repair for 3 ½ core 240 Sqmm XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheathed laying in trenches/cable ducts, fixed to wall/pole, complete all as specified and directed. Make : Havells, Polycab, RPG Asian |
| 249 | Material and labour in repair for 3 ½ core 185 Sqmm XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheathed laying in trenches/cable ducts, fixed to wall/pole, complete all as specified and directed. Make : Havells, Polycab, RPG Asian |
| 250 | Material and labour in repair formaking straight through joint with suitablejointing kit consisting of water proof adhesivesfor UG cable of size 3.50 core 185 Sqmm to 240 Sqmm, complete all as specified and directed. |
| 251 | Disconnecting of burnt/ damaged cables from panels/ junction boxes etc, cutting out the burnt out ends, making new end joints by supply and fixing new aluminium lugs/ insulation tape etc and reconnecting using new nuts/ bolts/ washer etc and restoring three phase and neutral in the junction box, complete all as specified and as directed for thecable sizefrom 185 Sqmmto 240 Sqmm 3.5 core of underground LT armoured cables.Note :- Earth work required for extending the incoming/ outgoing cable in junction box/ panel board etc shall deemed to be included in the unit rate quoted. |
| 252 | Supply, installation, commissioning and testing of factory assembled, floor mounted, free standing type tested LT Feeder pillar panel, with canopy, as per electrical specifications for outdoor installation to be made of IP65 Polycarbonate modular enclosures. The enclosures made of polycarbonate, should be weather/vermin proof, anti -acid, anti-corrossive, UV resistance in accordance with IEC 61439-1, fire retardant and self extingushing in accordance with IEC 60695-2-11, UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties, RoHS compliants & Halogen free. The manufacturer of boards/panels shall submit a copy oftype test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tightened to base with thermoplastic screws having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosure should be minimum 200mm for air circulation & to minimize temp rise. Panel should be fitted with one No.polycarbonate IP 65, 9 W LED translucent bulk head luminaire color lamp not less than 6500K, PF >0.95 under canopy for easy maintenance. Panel shall be fitted outside with one No of 16 Amp 3 Pole IP65 industrial socket and 01 No. of 32Amp 5P IP 65 industrial socket. 3 Phase and neutral 400 Amp current carrying capacity of aluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the following switch gears and mounting the panel board on ground with PCC (1:3:6) type C-1 using 20mm graded aggregate forbedding upto a height of 45 CM above ground level, including dismanting and taking out old U/s LT panel board and reconnecting existing LT UG Cable with new panel board amplete all as specified and all as directed and comprising of the following:- |
| 253 | (a) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 250 Amp, 36 KA- 02 Nos (Incomer).(b) On Load Change over front operated of capacity 250 Amp, 4 Pole, 415 V - 01 No.(c) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 63 Amp, 16 KA- 01 No (O/G).(d)Multifunction Meter (V,I,PF) with suitable capacity of CT\"s- 01 No.(e) Indicating lamp (R-Y-B) set LED type with backup MCB for 3 Phase Supply - 01 set(f) Space for spare Feeder - 01 No.Note :-(i) The Contractor shall submit the drawing for approval of GE before executing the work.(ii) Insulators, bus bar sleeves, lugs, gland etc including complete wiring with suitable size of copper wire are all inclusive in unit quoted rate. (iii) Make of Switch gear : Schneider/L&T/C&S.(iv) MCCB should be ICu =100% ICs.(v) Make of LT Panel/FPB shall be as mentioned in list of makes (PS). |
| 254 | Supply, installation, commissioning and testing of factory assembled, floor mounted, free standing type tested LT Feeder pillar panel, with canopy, as per electrical specifications for outdoor installation to be made of IP65 Polycarbonate modular enclosures. The enclosures made of polycarbonate, should be weather/vermin proof, anti -acid, anti-corrossive, UV resistance in accordance with IEC 61439-1, fire retardant and self extingushing in accordance with IEC 60695-2-11, UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties, RoHS compliants & Halogen free. The manufacturer of boards/panels shall submit a copy oftype test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tightened to base with thermoplastic screws having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosure should be minimum 200mm for air circulation & to minimize temp rise. Panel should be fitted with one No.polycarbonate IP 65, 9 W LED translucent bulk head luminaire color lamp not less than 6500K, PF >0.95 under canopy for easy maintenance. Panel shall be fitted outside with one No of 16 Amp 3 Pole IP65 industrial socket and 01 No. of 32Amp 5P IP 65 industrial socket. 3 Phase and neutral 150 Amp current carrying capacity of aluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the following switch gears and mounting the panel board on ground with PCC (1:3:6) type C-1 using 20mm graded aggregate forbedding upto a height of 45 CM above ground level, including dismanting and taking out old U/s LT panel board and reconnecting existing LT UG Cable with new panel board amplete all as specified and all as directed and comprising of the following:- |
| 255 | (a) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 100 Amps10 KA- 01 No(Incomer).(b) Change over switch 100A, 4P front operated - 01 No.(c) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 63 Amps10 KA- 04 Nos (O/G).(d) MCB SPNof 240 V of capacity 40 Amps 10 KA- 01 No.(e) Multifunction Meter (V,I,PF) with suitable capacity of CT\"s- 01 No.(f) Indicating lamp (R-Y-B) set LED type with backup MCB for 3 Phase Supply - 01 set.(g) Space for spare feeder - 01 No. Note :-(i) The Contractor shall submit the drawing for approval of GE before executing the work.(ii) Insulators, bus bar sleeves, lugs, gland etc including complete wiring with suitable size of copper wire are all inclusive in unit quoted rate. (iii) Make of Switch gear : Schneider/L&T/C&S.(iv) MCCB should be ICu =100% ICs.(v) Make of LT Panel/FPB shall be as mentioned in list of makes (PS). |
| 256 | Dismantling/ taking down complete radiator assembly of 250 KVA to 400 KVA DG Set and transportation to authorised workshop for following repairs :-(a) Opening the radiator assembly with brazing/ welding for repair/ service.(b)Cleaning of all water tube with diluted solution of HCL and cleaning with water pressure and removing the sludge and dust from inside the tank by flushing out.(c)Determining the leak/ puncher in radiator tubes.(d)Repair of fins by soldering/ brazing.(e)Repair of bottom brass water tank by soldering/ brazing.(f) Repair of radiator hose assembly.(g)Fixing the complete radiator assembly to its original position and testing complete all as specified and directed by Engineer-in-Charge. |
| 257 | Taking down old unserviceable self motorof capacity 200 KVA to 400 KVAand carrying to authorised work shop for servicing includingreplacement of unserviceable spare parts Brush, holder, solonoid switch, armature bush, filed coil complete and refixing, Testingcomplete all as specified and directed. |
| 258 | Removing and replacing the old unserviceable with newAVR (Automatic Voltage Regulator) suitable for Kirloskar curve of capacity 200 KVA to 400 KVAhaving input voltage 2 phase + neutral sensing voltage 415 output voltage 95V DC, output current 4A DC voltage regulation +/- 1 % average volts, over excitation current tripping, fuse protection 4A, fast acting and frequency 50 Hzcomplete all as specified and directed.Make : As per OEM recommendation. |
| 259 | Material and labourOpening disconnecting LT Cable connections with care from Auto-Main Failure Panel and checking throughly with Fault Detector Instrument at Site and replacement of Minor Defective Parts as required at Site suitable for 200 KVA to 400 KVA DG Set including replacement of Internal Wiring with Copper Conductor Cable, Beading, etc. complete all as specified and as directed. |
| 260 | Supply and fix in replacement of DGcontroller unitsuitable for DG set 125 KVA to 400 KVA as per existing Make complete all as specified and as directed. |
| 261 | Supply and fixingin replacementcontactor 4 pole,with 1 NO + 1 NC aux contacts and coil voltage 240 V/415 volt suitable for AMF Panels of 125 KVADG Set complete all as specified and as directed. MAKE : L&T/BCH/Schneider |
| 262 | Supply and fixingin replacementcontactor 4 pole,with 1 NO + 1 NC aux contacts and coil voltage 240 V/415 volt suitable for AMF Panels of 160 KVADG Set complete all as specified and as directed. MAKE : L&T/BCH/Schneider |
| 263 | Supply and fixingin replacement microprocessor based AMF controller unit for AMF Panel flush mounting type suitable for DG Set 82.5 to 400 KVA capacity as per existing make complete all as specified and directed. |
| 264 | Supply and fixingin replacement Cooling Fansuitable for DG Set 200 to 400 KVA capacity, complete all as specified and as directed. |
| 265 | Material and labourservicing/ cleaning of MS diesel tank of DG Set of 200-400 KVA capacity by draining out the diesel from tank, cleaning the tank with soap water/ suitable solution and painting the external surface with one coat of synthetic enamel paint of existing colour including replacement of drain valve, outlet pipe complete all as specified and as directed. |
| 266 | M & L for supply and replace HRC fuse square type suitable for 250 to 400 KVA DG set by taking out the defective use and changing, connecting and testing the same on load all as specified and directed . |
| 267 | Supply and fixingin replacement ofwiring kit of AMF panel of capacity DG set with copper wire ,PVCwire holder and other connected items suitable for DG SetDG Set 200 to 400 KVA capacity as per existing make complete all as specified and directed. |
| 268 | Supply and fixingin replacement maintenance free lead acid sealed battery (SMF) 12 volts 180 AH complete all as specified and as directed.Make : EXIDE. / Amaron/ Amar Raja/Cummins Note :-Old battery shall be deposited in MES store yard. |
| 269 | Supply and fixingON LOAD change over switch 4 pole 630 A with sheet metal enclosure in LT panel boards/ feeder pillar boxes including disconnecting and removing existing defective item from electric circuit including necessary connected fasteners, burnt cables, accessories etcall as per site requirement/existing make/model all as specified and as directed.Make:L&T/ HAVELLS/INDO ASIAN |
| 270 | Supply and fix in replacement of Air filter elementinner and outer as required at site with \"O\" ring of Make MICO / Kirloskar / Mahle/ Cummins as required at site for 5 to 7.5 KVA capacities of DG Sets complete all as specified & directed. |
| 271 | Description all as per Sl.item No 270 here in before but 15 KVADG set. |
| 272 | Description all as per Sl.item No 270 here in before but20 to 22.5 KVADG set. |
| 273 | Description all as per Sl.item No 270 here in before but 25 KVADG set. |
| 274 | Description all as per Sl.item No 270 here in before but 30 KVADG set. |
| 275 | Description all as per Sl.item No 270 here in before but40 KVADG set |
| 276 | Description all as per Sl.item No 270 here in before but45 KVADG set |
| 277 | Description all as per Sl.item No 270 here in before but50 KVADG set. |
| 278 | Description all as per Sl.item No 270 here in before but62.5 KVADG |
| 279 | Description all as per Sl.item No 270 here in before but82.5 KVADG set |
| 280 | Description all as per Sl.item No 270 here in before but 100 KVADG set |
| 281 | Description all as per Sl.item No 270 here in before but 125 KVADG set |
| 282 | Description all as per Sl.item No 270 here in before but 160 KVADG set |
| 283 | Description all as per Sl.item No 270 here in before but 200 KVA DG Set |
| 284 | Description all as per Sl.item No 270 here in before but 250 KVA DG Set |
| 285 | Description all as per Sl.item No 270 here in before but 400 KVA DG Set |
| 286 | Supply and fixingin repairs change over switch 125 Amps capacity 4 pole 3 phase with enclosure complete all as specified and directed. Make-Legrand/ L&T / Indoasian |
| 287 | Supply and fixingin replacementcontactor 4 pole,with 1 NO + 1 NC aux contacts and coil voltage 240 V/415 volt suitable for AMF Panels of 250 KVA/200 KVADG Set complete all as specified and as directed. MAKE : L&T/BCH/Schneider |
| 288 | Supply and fixingin replacement of Fly wheel ringincluding nuts and bolt suitable for DG Set 200 to 400 KVA capacity as per existing make complete all as specified and directed. |
| 289 | Supply and fixingin replacementcontactor 4 pole,with 1 NO + 1 NC aux contacts and coil voltage 240 V/415 volt suitable for AMF Panels of 400 KVA DG Set complete all as specified and as directed. MAKE : L&T/BCH/Schneider |
| 290 | Supply, installation, testing & commissioning of maintenance free chemicalearthing system comprising of 17mm dia copper bondedrod 3 mtr long horizontally pre welded T-terminal rod with provision for connection size of 50 x 150mm long, 6mm thickness with equal space either side, with 12mm dia hole of 02 numbers each on either side of the terminal clamp with 250 microns (average) coating thickness, tested and certified by CPRI India alongwith 50 Kg earth energizer compound and 10 litres earth resistance reducingliquid. The earthing energizer compound and resistance reducing earthing liquid shall be tested as per IEC-62561-7 read with ASTM G57-06, CI 3.4 A by any NABL accredited lab. The above mentioned rod shall be installed in 4-6 inch bore, 12 feet depth with a distance of minimum 3 meters between each installation including taking down existing one, complete all as specified and directed..Make : Model HTSP 317 of safeTrode or equivalent in Snaga/ Cubes 6 Global |
| 291 | The quoted rate shall also deemed to be included the following :- (i)Prior toinstallation of maintenance free chemicalearthing, soil resistivity test to be carried out at the location where earthingwork to be donein presence of Engr-in- Charge/JE (E/M),user and the report has tosubmitto Garrison Engineer with recommendation of manufacturer, if required additional interconnection ofearthing (not more than 08 number of earthing) to achive earth result less then 1 Ohms. The arrangement done for soil resistivity testingandsubmission of report with recommendationdeemed to be included in the quoted rate. |
| 292 | (ii) The description/ size/ qty of items mentioned in above are for indicating only however qty/ size may vary at site condition to maintain the earth resistance 1 ohm. The contractor shall quote rate by considering all factors. |
| 293 | (iii) Rateofearth energizer compound of 25 Kg of 02 bags and earthresistance reducingliquid 10 litre per cane for each pit deemed to be included in the quoted rate. |
| 294 | (iv)Resistivity of earth energizer compound and resistance reducing earthing liquid shall be certified by any NABL accredited lab carried out as per IEC-62561-7 read with ASTMG57-06, CI-3.4A and the certificate of same shall be submitted by the contractor along with the sample approval |
| 295 | (v) Earth enhancing material should not leach into the adjacent soil or underground water channels and its PH value should be in neutral range complete all as specified and as directed. It should solidify when mixed with water and set like concrete. |
| 296 | (vi) Copper strip of size 20 x 3 mm shallbe fixed on proper post insulator at the instrument end (copper strip upto 7.5 RM shall be considered in unit quoted rate and extra will be measured and paid separately). |
| 297 | (vii)Testing of earth shall be carriedout in presence ofdepartmental and user representativeand report shall be submitted to Garrison Engineer duly signed by all concerned. |
| 298 | (viii)Earth resistance tester will be provided by the contractor.Tester should be calibrated from authorised company/ lab. |
| 299 | (ix)Earthing shall be tested after completion of work by the contractor in presence of Engr-in-charge, user and proper record shall be maintained duly signed by all concerned.After testing if the desired earth resistance of less than 1 Ohm is not obtained, the earthing will be redone at no extra cost to Govt. till desired result is obtained. |
| 300 | (x) The contractor shall give a written guarantee of minimum three years for maintaining the earth resistance less than 1 Ohm after certified date of completion. |
| 301 | (xi) No further maintenance or periodic watering or recharge shall be required in earthing during its guarantee period of over 03 years in all type of soil including soft/ disintegrated or hard rock. |
| 302 | (xii) During the guarantee period, if earth resistance is not maintained less than 1 ohm the contractor has to redo or rectify at no extra cost to Govt till desired result is maintained. |
| 303 | (xiii) A security deposit of value equal to 2.5 % of the rate quoted for chemical earthing for each earthing shall be retained from payment due to the contractor from final bill for the guarantee period. |
| 304 | (xiv) The electrode shallcarry manufacturer\"s name . |
| 305 | (xv) The connection clamp shall be permanentlly welded to the copper boundedrodto avoid any kind of connectivity loss,.The pre-welded copper bounded rod shall not need any additional clamp for termination. |
| 306 | (xvi) The acceptable earth resistance at earth busbar/ test point shall not be more than 0.1 ohm. |
| 307 | (xvii)Earth work such as auguring andmaking good the surrounding area shall carried out in any type of soil. |
| 308 | (xviii)The contractor shall submit CPRI India certified document for copper bounded rod to ensure genuineness of material. |
| 309 | (xix) Sign boardof mild steel sheet 2 mm thick duly painted with two coats of synthetic enamel paint over a coat of red oxideZinc chrome primer showing result of earthing shall be fixed near the earth pit after completion as directed by engr -in- charge. |
| 310 | Material and labour for Earth pit cover madeof heavy duty poly plastic of high grade polypropylene tested and certified by any NABL accredited lab for load bearing capacity not less than 7.2 tonnes with top dia not less than 250mm, bottom dia not less than 330 mm and height not less than 260 mm for each electrode pit complete including taking down old unserviceable pit cover of any decription all as specified and directed.Make : Model SEPC 250 of SAFE TRODE or equivalent in Snaga/ Cubes 6 Global |
| 311 | Attending complaints for non-functional/ unserviceable street light/perimeter lights/high mast light/flood light etc of any type/size fitted on poles/walls/post/pillars etc)by deploying technically qualified and experienced technicians to find out defects and taking out unserviceable parts such as electronic driver, pvc insulated copper conductor cable for connecting street light fittings etc and repairing by changing the defective parts including minor repair to cable connection/loose connection, screws,nuts & bolts and insulation tape to insulate the LT joint etc and testing complete all as specified and as directedat CQAE (WE) |
| 312 | Note : The following items are deemed to be inclusive of quoted rate :- |
| 313 | The above job shall be carried out by a trained electrician having ITI in electrical, documentary proof of the education of tradesman shall be produced to the Engr-in-Charge before commencement of work. |
| 314 | Contractor or his Authorised Representative has to inspect all Street/ Security Lights on Daily basis at their own arrangement between 7.00 PM to 9.00 PM and maintain the record in Register which will be put up to Engineer-in-Charge/ JE on the very regular basis. (Every succeding day) |
| 315 | A Joint Inspection for Serviceability of all Street/Security Lights will be carried out from 7.00 PM to 9.00 PM on every MONDAY by Engineer-in-Charge/ JE (E/M)/ User along with Contractor or his authorised Representative. |
| 316 | Contractor has to arrange own moveable Generatorof suitable capacity for repairing and testing of the Street/ Security Lights, defect rectification of Cables, etc. and to check the serviceability after repair.No Electricity shall be provided by the Department on this account. |
| 317 | Quoted Unit Rate shall deemed to be inclusive of attending any breakdown of Street/ Security Lights during night. Contractor has to arrange Electrician and Helper and all necessary T&P and Equipment\"s to remove the breakdown. Fault will be intimated through Telephone/ SMS. |
| 318 | Contractor shall provide conveyance to the employed labour for maintaining the services without any extra cost to department. |
| 319 | Vehicle mounted ladder for maitenance services shall be provided by the contractor at no extra cost to department. |
| 320 | Material requiredfor the repairing of the lights shall be measured and paid separately under respective item(s) . But labour required for taking down, dismantling, repairing and replacing parts and reinstalling and testing the lights fittings shall deemed to beincluded in the rate quoted. |
| 321 | Necessary T&P, Safety Belt, Vehicle, Aluminium Ladder, etc. will be arranged by the Contractor and Cost for the same shall deem to be included in the Quoted Unit Rate. |
| 322 | All safety measures and provn of all safety devices, first aid box etc shall be provided by the contractor.Contractor will be solely responsible forfull safetyof the tradesmen deployed for providing the services and department will have no liability for any type of accident. Unit rate quoted will be deemed to include the cost of the same and no extra payment shall be made on this account. |
| 323 | All type of T & P, PVC insulation tapes, minor nuts/ bolts/ washers etc required for maintaining the services shall be provided by the contractor without any extra cost to department. |
| 324 | Attending and repairing complaint for onelightof any type shall be measured and paid as one Job. |
| 325 | Earth work (if necessary at Site) for removing of any Cable Fault will be Measured and Paid under respective Items. |
| 326 | Contractor has to ensure serviceability of all Street/ Security Lights in above mentionedDOMESTIC & TECHNICAL AREA on Daily basis in any weather condition at their own arrangement. |
| 327 | In case of any delay in attending the complaint more than 12 hrs after handing over routine/urgent work, the contractor shall be liable to pay the penalty as described in penalty clause given here as under. |
| 328 | The penalty shall be applicable to the contractor if the delay is noticed by the Engr-in-Charge more than twelve hrs after handing over works of urgent nature to the contractor. The Engr-in-Chargeshall handover the slip containing specification of work to the contractor by lodging the time and signature of contractor be obtained on slip.The contractor shall attend the complaint immediately and shall report to Engr-in-Charge with in 12 hrs. The contractor will keep his tradesmen in stand by for attending any routine / urgent works from the executive.If the nature of job is such that the work cannot be completed within period of 12hrs then the facts shall be brought to the notice of the GE/Engr-in-Chargeand the period for the working to the complaint shall be decided by the GE/EIC. If the delay is more then twelve hrs period and the GE is not satisfied with the reason for delay then penalty at the rate of Rs 50/- per job shall be deducted from the dues of the contractor. Please note that this penalty is exclusively other than condition 67 of IAFW - 2249 and shall be treated as interim condition of the contract and shall be enforce above as and when delay in individual job is noticed and no claim whatsoever on this account shall be entertained by the Deptt. |
| 329 | The decision of the Accepting Officer in this regards shall be final and binding. |
| 330 | Supply only the electronic controller with accessories (LED outdoor Driver) ofsuitable capacityof 200 wattLED fittings complete all as specified and directed. Make - CG/Phillips/Bajaj or equivalent as per site requirement |
| 331 | Supply only electronic controller with accessories (LED outdoor Driver) ofsuitable capacityof 120 to 150 wattLED fittings complete all as specified and directed. Make - CG/Phillips/Bajaj or equivalent as per site requirement |
| 332 | Supply only PVC insulated Copper Conductor Cable 1.5 Sqmm, 3 Core Round Flexible for connection of Street Light Fitting, complete all as specified and as directed. Make : Havells/ Plaza/ Finolex or equivalent |
| 333 | Supply only electronic controller with accessories (LED outdoor Driver) ofsuitable capacityof 80 to 100 wattLED fittings complete all as specified and directed. Make - CG/Phillips/Bajaj or equivalent as per site requirement |
| 334 | Supply only electronic controller with accessories (LED outdoor Driver) ofsuitable capacity of 60 to 75 wattLED fittings complete all as specified and directed. Make - CG/Phillips/Bajaj or equivalent as per site requirement |
| 335 | Supply only electronic controller with accessories (LED outdoor Driver) ofsuitable capacityof 40 to45 wattLED fittings complete all as specified and directed. Make - CG/Phillips/Bajaj or equivalent as per site requirement |
| 336 | Supply only electronic controller with accessories (LED outdoor Driver) of suitable capacity upto 36 wattLED fittings complete all as specified. Make - CG/Phillips/Bajajor equivalent as per site requirement |
| 337 | M&L for wiring of unserviciableTimer panel boxand replacement of existing size of copper wire withcopper lugs and other connected items complete all as specified and as directed |
| 338 | Supply and fix digital timer switch 24 hrs including taking down of old one complete all as specified and as directed. Make:- Legrand /Indo Asian /L&T |
| 339 | Supply and fix as in repair NO/NC of capacitysuitable for 32-40 A contactorincluding taking down of old one complete all as specified and as directed . Make:- Legrand /Indo Asian /L&T |
| 340 | Supply and fixcontactor of capacity 32- 40 A 3 Pole 415 V with 2NO+2NCincluding taking down of old one complete all as specified and as directed .Make:- Legrand /Indo Asian /L& T |
| 341 | Supply and fix MCB 40 Amps, TP, 415 volt, breaking capacity 16 KA conforming to IS 13647-II: , including taking down of old one complete all as specified and as directed. Make:- Legrand /Indo Asian /L& T |
| 342 | Supply and fixingthe surge protection device 5KV voltage compatible with industrial and out door type LED fixturesincluding taking down of old one complete all as specified and directed. Make - CG/Phillips/Bajaj or equivalent as per site requirement |
| 343 | Material and labour for applying one coat of cement base paint to RCCpole 7/9.0 metre long after scraping / brushing and cleaning the pole and street light bracket to be painted with one coat of Aluminium paint. Cement base paint shall be done on pole above 1.5 metre height from ground level and balance 1.5 mtr from groundlevel will be painted by alternate layer of black and white with synthetic enamel paint (30 Cms Each)Pole Nos shall be written on pole withblack paint in yellow circle of 150mm dia, complete, all as specified and directed. |
| 344 | Material and labour for Painting of steel tubular pole 7/9.0 metre long, by applying one coat of aluminium paint after scraping / brushing and cleaning the rust on pole and street light bracket. Aluminium painting will be done on pole above 1.5 metre height from ground level and balance 1.5 mtr from groundlevel will be painted by alternate layer of black and white with synthetic enamel paint (30 Cms Each). Pole Nos shall be written on pole withblack paint in yellow circle of 150mm dia, complete all as specified and directed. |
| 345 | Taking down and errecting steel swagedtubular pole 8.5/9 mtr long,bracket for fixingstreet lightand refixing the sameincluding necessary PCC 1:4:8, type D2 (using 40 mm graded stone aggregate) in foundation size of 50 x 50 x 45 cm and copingwith 1:2:4, type B1 (using 20 mm graded stone aggregate) complete all as specifiedand directed. |
| 346 | M &L for PCC (1:3:6) type C1 (using 20mm graded stone aggregate) as in copping to poleincluding necessary form work slightly rounding or squaring, complete all as specifiedand as directed. |
| 347 | M & L for PCC 1:4:8 type D2 (using 40mm graded stone aggregate) as in foundation and mass concrete for poles etc, complete all as specified and as directed |
| 348 | Supply & Erecting Mild steel tubular swaged pole 9 meter long 410, SP-31 complete with cast iron base plate, bracket, finial taper plug, bolt, nuts & screws and painted on both side (internally & externally), external surface painted with two coat of aluminum paint over coat of primer and painting with blackup to 1.5 meter from top of PCC 1:3:6 using 20 mm graded stone aggregate coping white colour paint as in strips of equal width with marking pole numbers by using one coat of synthetic enamel paint including necessary PCC 1:4:8 with 40 mm graded stone aggregate as in foundation and coping as per TD drawing including dismantling of old damaged pole complete all as specified and as directed.Note (i)Excavation, earth work and PCC work for embedding pole shall be measured and paid seperately.(ii) Pole upto 1.5 m top of copping shall be painted with 2 coats of black and white strips alternate 30cm each over one coat of red oxide primer (iii) Steel tubular pole above 1.5 m shall be painted with 2 coats of aluminium paint over a coat of red oxide primer. The rate for above items shall be deemed to be inclusive in the quoted rate. |
| 349 | Supply and fix in repair weather proof PVC junction box approved by CPRI for street light control box made out of not less than 2mm thick and size 250mm x 200 mm x 105mm (approx) complete with hinged door locking arrangement and consisting of 2 Nos of suitable size cable glands consisting of 01 No. panel mounted connector 4 pole 32A-1 No, MCB SP 6A 10KA-01No, including connecting up with the electrical connections and fixing with clamps etc complete and all as specified anddirected. |
| 350 | Supply and fix in repair of LED street light 35/36 Watt fitting, environmental friendly long life, made up of pressure die cast aluminium housing with mid power LED as lighting source and PC cover having TOP Opening separate driver compartment with IP66 protection and impact resistance of IK07. Make : Philips/CG/Bajaj/ Halonix |
| 351 | Supply and fix in repair of LED street light 45/48 Watt fitting, environmental friendly long life, made up of pressure die cast aluminium housing with mid power LED as lighting source and PC cover having TOP Opening separate driver compartment with IP66 protection and impact resistance of IK07. Make:Halonix/Philips/CG/Bajaj |
| 352 | Supply and fix in repair bracket for street light fitting made out of40 mm dia light grade GI tubing bent to required shape 1.5m long including necessary GI clamps, nuts bolts and washers and fixing to the pole etc complete all as specified and directed. |
| 353 | Supply and fix 1100 Volts grade heavy duty flat weather proof twin core cable of size 4 Sqmm with multistrand aluminium conductor including taking down of old one complete all as specified and directed. Make: Plaza/Polycab/ Finolex/Havells |
| 354 | Supply and fix in repair Time switch Digital 24 hour, 440 V three phasewith contactor TP of rating 32 Amps and MCB TPN of rating 40A fitted in steel enclosure with necessary accessories to fixing RCC/steel tubular pole including bracket, nuts, bolts, washers etc. and making all necessary connections through connectors complete all as specified and as directed. Make : L&T/ Havells/ Indoasian |
| 355 | Material and labour in repair for 4 core 16 Sqmm XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheathed laying in trenches/cable ducts, fixed to wall/pole, complete all as specified and directed. .Make :- Havells/Polycab/ RPG Asian |
| 356 | Material and labour in repair for 4 core10 Sqmm XLPEinsulated heavy duty electric cable with aluminium single stranded conductor 1100 volts grade served with an inner sheathed of PVC tape armoured with galvanised steel wire or tape and overall sheather laying in trenches/cable ducts, fixed to wall/pole complete all as specified and directed.Make :- Havells/Polycab/ RPG Asian |
| 357 | Disconnecting of burnt/ damaged cables from panels/ junction boxes etc, cutting out the burnt out ends, making new end joints by supply and fixing new aluminium lugs/ insulation tape etc and reconnecting using new nuts/ bolts/ washer etc and restoring three phase and neutral in the junction box, complete all as specified and as directed for thecable sizefrom 10Sqmmto 16 Sqmm 3.5 core of underground LT armoured cables.Note :- Earth work required for extending the incoming/ outgoing cable in junction box/ panel board etc shall deemed to be included in the unit rate quoted. |
| 358 | S & F aluminium lugs suitable for aluminum cable of size 10 to 35 Sqmm complete all as specified and directed |
| 359 | S & F aluminium lugs suitable for aluminum cable of size 50 to 120 Sqmm complete all as specified and directed |
| 360 | Supply, installation, testing and commissioning of smart street light control system using GSM/Lux based technology having20 KW 3 phase 64 Amp load capacity per phase and can be operated by IVRS/SMS/lux based infrared sensor etc complete with following:-(i) Nature switch operation should be based on natural light lux level. Require illuminnance level for switching on is ≤ 60 luxand for switching off ≥ 10 lux. The smart unit should have 4 timers that can be set via SMS.(ii)Surge protection device (SPD) should provide protection agaist indirect lightning & switching surges. It should conform to IEC61643-11 and should have 40 KA capacity.(iii) The sensor & SPD along with suitable power contactors and incoming-outgoing MCCB/MCBs should be enclosed in a enclosure made of rust proof, electric shock proof , metal weather proof conforming to IP65 with angle iron frame of suitable size 04 Nos legs 600 mm long , PCC 1:2:4 typeB1using 20 mm graded aggregate for grouting of base including taking down old unserviceable panel etc complete.The scope of work also comprising the following :-The GPRS shall have seven segment display to show voltage, current, network and street light status , it should also have indicator for showing supply status , timer , overload or high low voltage. It should also able to measure voltage, current and automatic set street light overload current. Unit have facility to call back to registered number for power on/off and if any fault occurs at site.in SMS it should also monitor power/on/off time light on off time, ampere, voltage, unit mode, network percentage date and mobile number who called device number. The device should also have battery backup with minimum 24 hours backup capacity.The panel should have three operation mode :-1. GSM mode -in this mode light should be switched as per GSM controller\"s preset time by user by sms , 4 clock base timer facility should be availble 2. Nature switch based-in this mode light will be switched as per nature light lux level 3. Bypass mode -in this mode light will switched on directly for testing purpose and emeregncy switching .In GSM controller there should be facility to register 4 user by sms/call and alerts will be sent on all registered number and also call back on power on/off and faults on first registered number.The GSM controller should also compatible for cloud based data transmission for interfacing with web for future use,Password protection for Accessing the control of device via SMS/IVRS, complete all as specified and directed including the following subcomponent, supply and fixing features :- |
| 361 | (a) TPN MCCB 100 Amps capacity, 10 KA, 415 Volts -01 No. (Incoming) with separate SPD of 40 KA capacity. (Make of MCCB- L & T, C&S Havells)(b)Supply Resign cast CT\"S - set of 3(c)GSM based smart street light controller.(d) Lux based sensor to operate external as per light intensity.(e)Line Contactor, AC 3duty, 3 phase, 415 volts. 50 Hz , 32 Amps -02 Nos (make - L & T, BCH, Havells)(f)MCB SP 32 Amps- 06 Nos(make -L & T, BCH, Havells)(g)Terminal block suitable for 100 Amp rating with brass contacts for INPUT/ and 63 Amp for OUTPUT termination.(h) GSM/Timer/Bypass Mode switch.(j) Panel wiring for control circuit with copper flexible 1.5 Sqmm & power wiring 10 Sqmm flexible.Make- Tricolite/ Kewintech/HPL |
| 362 | Supply and fix in repair weather proof PVC junction box approved by CPRI for street light control box made out of not less than 2mm thick and size 300x200x100mm (approx) complete with hinged door locking arrangement and consisting of 2 Nos of suitable size cable glands consisting of 01 No. panel mounted connector 4 pole 32A-1 No, MCB SP 6A 10KA-01No, including connecting up with the electrical connections and fixing with clamps etc complete and all as specified anddirected. |
| 363 | Supply and fixing in repair new generation energy saving and environmental friendly long life LED street light made up of pressure die cast aluminium housing with high power LED as lighting source and lens embedded PC cover having TOP OPENING seperate driver compartment with IP66 protection and impact resistance of IK07 with 10KV Built-in Surge Protection Device of 60 to 72 watt complete all as specified and directed. Make :Halonix/Philips/CG/Bajaj |
| 364 | Supply and fixing in repair new generation energy saving and environmental friendly long life LED street light made up of pressure die cast aluminium housing with high power LED as lighting source and lens embedded PC cover having TOP OPENING seperate driver compartment with IP66 protection and impact resistance of IK07 with 10KV Built-in Surge Protection Device of 90 watt complete all as specified and directed. Make:Halonix/Philips/CG/Bajaj |
| 365 | Supply and fix 1100 Volts grade heavy duty flat weather proof twin core cable of size 6 Sqmm with multistrand aluminium conductor including taking down of old one complete all as directed and specified. Make: Plaza/Polycab/ Finolex/Havells |
| 366 | Supply only of GI pipe light grade for cable protection of size 50mm bore with fittings, complete all as specified and directed. |
| 367 | Material and labour in repair for 3 ½ core 25 Sqmm XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheathed laying in trenches/cable ducts, fixed to wall/pole, complete all as specified and directed. .Make :- Havells/Polycab/ RPG Asian |
| 368 | Material and labour in repair formaking straight through joint with suitablejointing kit consisting of water proof adhesivesfor UG cable of size 3.50 core 16 Sqmm to 25 Sqmm, complete all as specified and directed. |
| 369 | Disconnecting of burnt/ damaged cables from panels/ junction boxes etc, cutting out the burnt out ends, making new end joints by supply and fixing new aluminium lugs/ insulation tape etc and reconnecting using new nuts/ bolts/ washer etc and restoring three phase and neutral in the junction box, complete all as specified and as directed for thecable sizefrom 25Sqmmto 50 Sqmm 3.5 core of underground LT armoured cables.Note :- Earth work required for extending the incoming/ outgoing cable in junction box/ panel board etc shall deemed to be included in the unit rate quoted. |
| 370 | Supply, installation, testing and commissioning of smart street light control system using GSM/Lux based technology having12 KW 3 phase 32 Amp load capacity per phase and can be operated by IVRS/SMS/lux based infrared sensor. Nature switch operation should be based on natural light lux level. Require illuminnance level for switching on is ≤ 60 luxand for switching off ≥ 10 lux. The smart unit should have 4 timers that can be set via SMS.Surge protection device (SPD) should provide protection agaist indirect lightning & switching surges. It should conform to IEC61643-11 and should have 40 KA capacity. The sensor & SPD along with suitable power contactors and incoming-outgoing MCCB/MCBs should be enclosed in a enclosure made of rust proof, electric shock proof , metal weather proof conforming to IP65 with angle iron frame of suitable size 04 Nos legs 600 mm long , PCC 1:2:4 typeB1 for grouting of base including taking down unserviceable panel etc complete. The scope of work also comprising the following :-The GPRS shall have seven segment display to show voltage, current, network and street light status , it should also have indicator for showing supply status , timer , overload or high low voltage. It should also able to measure voltage, current and automatic set street light overload current. Unit have facility to call back to registered number for power on/off and if any fault occurs at site.in SMS it should also monitor power/on/off time light on off time, Ampere, voltage, unit mode, network percentage date and mobile number who called device number. The device should also have battery backup with minimum 24 hours backup capacity.The panel should have three operation mode :-1. GSM mode -in this mode light should be switched as per GSM controller\"s preset time by user by sms , 4 clock base timer facility should be availble 2. Nature switch based-in this mode light will be switches as per nature light lux level 3. Bypass mode -in this mode light will switched on directly for testing purpose and emeregncy switching .In GSM controller there should be facility to register 4 user by sms/call and alerts will be sent on all registered number and also call back on power on/off and faults on first registered number.The Gsm controller should also compatible for cloud based data transmission for interfacing with web for future use,Password protection for Accessing the control of device via SMS/IVRS complete all as specified and directed. |
| 371 | (a) MCCB 100 Amps capacity, 10 KA, 415 Volts -01 No (Incoming) with separate SPD of 40 KA capacity. (Make of MCCB- L & T, BCH, Havells)(b)Supply Resign cast CT\"S - set of 3(c)Gsm based smart street light controller.(d) Lux based sensor to operate external as per light intensity.(e)Line Contactor, AC 3duty, 3 phase, 415 volts. 50 Hz , 25 Amps -03 Nos (make - L & T, BCH, Havells)(f)MCB SP 32 Amps- 03 Nos(make -L & T, BCH, Havells)(g)Terminal block suitable for 100 A rating with brass contacts for INPUT/ and 63 A for OUTPUT termination.(h) GSM/Timer/Bypass Mode switch.(j) Panel wiring for control circuit with copper flexible 1.5 sqmm & power wiring 10 sqmm flexible.Make- Tricolite/ Kewintech/HPL |
| 372 | Supply and fix in repair LEDfloodlight fitting 200Wintegral type light fixture, cast aluminum body, reflector, drivers, LEDsand accessories with system wattage 200W etc complete all as specified and directed. Make :Bajaj/Philips/CG/Halonix. |
| 373 | Supply and fixing in repair IP65 rated LED Bollard with robust design and efficient light distribution 10 watt on existing pipe of any size and height with all accessories prewired fixed with FI clamps nuts bolts etc., including taking down existing fittings all as specified and directed Make : Crompton or equivalent in Halonix/Bajaj/ Philips |
| 374 | Supply and fix in repairs LED decorative post top lantern fitting 40W, 230V AC with IP 65 protection and resistant to impact and corrosion with necessary electrical connection completeall as specified as directed. Make: Bajaj / Philips/Halonix/ CG |
| 375 | Supply and fix 1100 Volts grade heavy duty flat weather proof twin core cable of size 10 Sqmm with multistrand aluminium conductor including taking down of old one complete all as directed and specified. Make: Plaza/Polycab/ Finolex/ Havells |
| 376 | Supplying, errecting and fixingas in repair GItubular swaged welded pole of over all height 6.0 m long for all in one solar lightcompletewith cast iron base plate, finial tapper plug cap, bolt, nut and washer etc., complete all as specified and directed . |
| 377 | Supply and fix in repair smart integrated solar all in one LED solar street lightfitting 12 V,25 Watts with IP 66/65 protection, built-in MPPT charge controller,Lithium ion battery,mono crystalline solar panel,PIR motion sensor complete withanodised reflector, toughened heat resistant glass cover,LED 25 watts white colour lamp, connector block with all accessories prewired including bracket,welding,drilling,bolts,nuts and any alteration required for fixing the panel with existing pole, complete all as specified and as directed. Make:Philips/CG/Havells/Bajaj |
| 378 | Surface dressing in hard / dense soilnot exceeding 15 cm deepand clearing all the grass weeds etc in the sub station yards after removing stone aggregate asideall as directed at site including setting / spreading back the aggregate complete all as specified and directed at site. |
| 379 | Attending complaints for malfunctioning of ACBsat different locations of AFS Jalahalliby deploying technically qualified and experienced technicians to find out defects and rectify the fault.Note : The following items are deemed to be inclusive of quoted rate :-(a) The above job shall be carried out by a trained engineer as and when called telephonically /SMS by Engr-in-Charge .(b) Quoted Unit Rate shall deemed to be inclusive of attending any breakdown of fire panelduring day/night. Contractor has to depute Engineer/ technician and all necessary T&P and Equipment\"s to rectify the breakdown. Complaint of Fault will be intimated through Telephone/ SMS.(c) The major spare parts shall be measured and paid under respective item of BOQ.(d) All type of T & P, Safety Belt, Vehicle, Aluminium Ladder, PVC insulation tapes, minor nuts/ bolts/ washers etc required for maintaining the services shall be provided by the contractor without any extra cost to department. (e) All safety measures and provn of all safety devices, first aid box etc shall be provided by the contractor.Contractor will be solely responsible forfull safetyof the tradesmen deployed for providing the services and department will have no liability for any type of accident. Unit rate quoted will be deemed to include the cost of the same and no extra payment shall be made on this account.(f) In case of any delay in attending the complaint more than 12 hrs after handing over routine/urgent work, the contractor shall be liable to pay the penalty as described in penalty clause given here as under. (g) In case services affected due to delay in attending the complaint, a penalty of Rs 1000 per day will be levied from the contractor.(h) Please note that this penalty is exclusively other than the condition 67 of IAFW-2249 and shall be treated as interim condition of the contract. |
| 380 | M&L for repairing of ACBs fitted in the LT Panelwith copper wire and other connected items suitable for ACBs capacity upto 1250 Ampsas per existing make including testing and checking theconnection and serviciablity ofincoming cable from Main LT Panels to ACBs Panels and complete all as specified and directedNote:-The major spare parts shall be measured and Paid separately. However, the labour element is included in unit quoted rate for replacement of wornout/ defective components. |
| 381 | Supply onlyunder voltage relay 415 V AC suitable for LT ACB breaker 1250 Amps conecting and testing all as specified and directed by Engineer-in-charge Make: L&T/C&S//Crompton |
| 382 | Supply only microprocessor basedtriprelay with display 415 V AC suitable for LT ACB breaker 1250 Amps conecting and testing all as specified and directed by Engineer-in-charge Make: Schenider/Legrand |
| 383 | Supply only Closing coil for ACB complete all as specified and directed . |
| 384 | Supply onlyVoltage monitoring regulator (UV,OV,SV) of Suitable ratings for AMF panels. |
| 385 | Supply and fixingMCCB 630 A, 4P, 50 KA, 415V, including taking down unserviceable one, complete all as specified and as directed. Make -L&T / Havells/Indoasian |
| 386 | Material and labour forBoring of holes under road, pavement hard standings by trenches technology using ultra sound technique and necessary machine including HDPE pipes of 150 mm dia suitable for 0.4 Mpa working pressure complete all as specified and directed. |
| 387 | Material and labour in repair for 3 ½ core 120 Sqmm XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheathed laying in trenches/cable ducts, fixed to wall/pole, complete all as specified and directed. Make : Havells, Polycab, RPG Asian |
| 388 | Material and labour in repair formaking straight through joint with suitablejointing kit consisting of water proof adhesivesfor UG cable of size 3.50 core 120 Sqmm to 185 Sqmm, complete all as specified and directed. |
| 389 | Disconnecting of burnt/ damaged cables from panels/ junction boxes etc, cutting out the burnt out ends, making new end joints by supply and fixing new aluminium lugs/ insulation tape etc and reconnecting using new nuts/ bolts/ washer etc and restoring three phase and neutral in the junction box, complete all as specified and as directed for thecable sizefrom 120 Sqmmto 185 Sqmm 3.5 core of underground LT armoured cables.Note :- Earth work required for extending the incoming/ outgoing cable in junction box/ panel board etc shall deemed to be included in the unit rate quoted. |
| 390 | Supply, installation, commissioning and testing of factory assembled, floor mounted, free standing type tested LT Feeder pillar panel, with canopy, as per electrical specifications for outdoor installation to be made of IP65 Polycarbonate modular enclosures. The enclosures made of polycarbonate, should be weather/vermin proof, anti -acid, anti-corrossive, UV resistance in accordance with IEC 61439-1, fire retardant and self extingushing in accordance with IEC 60695-2-11, UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties, RoHS compliants & Halogen free. The manufacturer of boards/panels shall submit a copy oftype test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tightened to base with thermoplastic screws having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosure should be minimum 200mm for air circulation & to minimize temp rise. Panel should be fitted with one No.polycarbonate IP 65, 9 W LED translucent bulk head luminaire color lamp not less than 6500K, PF >0.95 under canopy for easy maintenance. Panel shall be fitted outside with one No of 16 Amp 3 Pole IP65 industrial socket and 01 No. of 32Amp 5P IP 65 industrial socket. 3 Phase and neutral 150 Amp current carrying capacity of aluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the following switch gears and mounting the panel board on ground with PCC (1:3:6) type C-1 using 20mm graded aggregate forbedding upto a height of 45 CM above ground level, including dismanting and taking out old U/s LT panel board and reconnecting existing LT UG Cable with new panel board amplete all as specified and all as directed and comprising of the following:- |
| 391 | (a) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 100 Amp, 25 KA- 01 No (Incomer). (b)Change over switch 125 Amp, 4P front operated-01 No(c) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 63 Amp, 10 KA- 03 Nos(O/G).(d) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 40 Amp, 10 KA- 02 Nos(O/G)(e) Multifunction Meter (V,I,PF) with suitable capacity of CT\"s- 01 No.(f) Indicating lamp (R-Y-B) set LED type with backup MCB for 3 Phase Supply - 01 set(g) Space for spare feeder - 01 No. Note :-(i) The Contractor shall submit the drawing for approval of GE before executing the work.(ii) Insulators, bus bar sleeves, lugs, gland etc including complete wiring with suitable size of copper wire are all inclusive in unit quoted rate. (iii) Make of Switch gear : Schneider/L&T/C&S.(iv) MCCB should be ICu =100% ICs.(v) Make of LT Panel/FPB shall be as mentioned in list of makes (PS). |
| 392 | Supply, installation, commissioning and testing of factory assembled, floor mounted, free standing type tested LT Feeder pillar panel, with canopy, as per electrical specifications for outdoor installation to be made of IP65 Polycarbonate modular enclosures. The enclosures made of polycarbonate, should be weather/vermin proof, anti -acid, anti-corrossive, UV resistance in accordance with IEC 61439-1, fire retardant and self extingushing in accordance with IEC 60695-2-11, UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties, RoHS compliants & Halogen free. The manufacturer of boards/panels shall submit a copy oftype test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tightened to base with thermoplastic screws having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosure should be minimum 200mm for air circulation & to minimize temp rise. Panel should be fitted with one No.polycarbonate IP 65, 9 W LED translucent bulk head luminaire color lamp not less than 6500K, PF >0.95 under canopy for easy maintenance. Panel shall be fitted outside with one No of 16 Amp 3 Pole IP65 industrial socket and 01 No. of 32Amp 5P IP 65 industrial socket. 3 Phase and neutral 400 Amp current carrying capacity of aluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the following switch gears and mounting the panel board on ground with PCC (1:3:6) type C-1 using 20mm graded aggregate forbedding upto a height of 45 CM above ground level, including dismanting and taking out old U/s LT panel board and reconnecting existing LT UG Cable with new panel board amplete all as specified and all as directed and comprising of the following:- |
| 393 | (a) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 250 Amps, 36 KA- 01 No (Incomer).(b) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 200 Amps, 25 KA- 01 No.(c) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 100 Amps,25 KA- 02 Nos.(d) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 63 Amps,10 KA- 01 No.(e) Multifunction Meter (V,I,PF) with suitable capacity of CT\"s- 01 No.(f) Indicating lamp (R-Y-B) set LED type with backup MCB for 3 Phase Supply - 01 set.(g) Space for spare feeder - 01 No. Note :-(i) The Contractor Shall submit the drawing for approval before executing the work.(ii) Insulators, bus bar sleeves, lugs, gland etc including complete wiring with suitable size of copper wire are all inclusive in unit quoted rate. (iii) Make of Switch gear : Schneider/L&T/C&S.(vi) MCCB should be ICu =100% ICs.(v) Make of LT Panel/FPB shall be as mentioned in list of makes (PS). |
| 394 | Supply and fixing in repair LED flood light 150 watt made up of die cast aluminium housing with toughened glass and high power LEDs and secondary lenses with IP 66 protection and system efficiency ≥ 125 LPW with option for 3000K 10 KV SPD corrosion resistant complete with driver and lampProtection including street light fitting bracket nuts, bolts, washers complete, all as specified and directed. Make:Halonix/Philips/CG/Bajaj |
| 395 | Supply and fixing LED flood light 100 watt 230 V AC outdoor type including necessary bracket with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp including taking down of old unserviceable fitting of any capacity. Make : Halonix/Philips/CG/Bajaj |
| 396 | Taking down existing GI earthstrip 25x3mm thick as earthing lead with its accessories and re fixing to wall/roofs etc. drawn in conduit/GI pipe etc complete all as specified and as directed.Note:- Unit rate is deemed to be included for old broken insulators/ clamps to replace with new insulators of existing size as per site and making good disturbed surfaces of floors/walls/ceiling etc complete all as directed. |
| 397 | Supply and fixing in replacement of aluminium strip 25x3mm fixed with epoxy based insulator for down conductor air terminal network including drilling two Nos holes at each joint, one set of lead washers between strips, two sets GI nut andbolt, gutties, screws etc,.on wall /roof including necessary fixing arrangement up to height 20mtrcomplete all as specified and directed.Note:- Unit rate is deemed to be included for old broken insulators/ clamps to replace with new insulators of existing size as per site and making good disturbed surfaces of floors/walls/ceiling etc complete all as directed.(ii) All safety measures shall be the responsibility of the contractor |
| 398 | Taking down of unserviceable aluminium strip 25x3mm and refixing the same with epoxy based insulator/post insulator/spacerfor down/ lightening conductor air terminal network including drilling two Nos holes at each joint, one set of lead washers between strips, two sets GI nut andbolt, gutties, screws etc.on wall /roof including necessary fixing arrangement up to height 20mtrcomplete all as specified and directed.Note:- Unit rate is deemed to be included for old broken insulators/ clamps to replace with new insulators of existing size as per site and making good disturbed surfaces of floors/walls/ceiling etc complete all as directed.(ii) All safety measures shall be the responsibility of the contractor |
| 399 | Material and labourin repairs Galvanised Earth strip of size 32 x 6 mm fixed on proper post insulator at the instrument end complete all as per specified and as directed. |
| 400 | Supply and fixing in repair test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 Nos. 8mm dia 25mm long hexagonal. head screw, complete all as specified and directed. |
| 401 | S&Fas in repair PCC earthing pitof outersize 450X450 X300 MM and RCC pit cover of required size including necessaryearth work complete all as specified and as directed. |
| 402 | S&F in repair copper strip 20 x 3mm thick as earthing lead fixed to wall/roofs etc including taking down existing old unserviceable copper strip etc, complete all as specified anddirected. |
| 403 | Material and labour for Brazing of copper/Aluminium for continuity, complete all as specified and as directed. |
| 404 | Supply, installation, commissioning and testing of factory assembled, floor mounted, free standing type tested LT Feeder pillar panel, with canopy, as per electrical specifications for outdoor installation to be made of IP65 Polycarbonate modular enclosures. The enclosures made of polycarbonate, should be weather/vermin proof, anti -acid, anti-corrossive, UV resistance in accordance with IEC 61439-1, fire retardant and self extingushing in accordance with IEC 60695-2-11, UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties, RoHS compliants & Halogen free. The manufacturer of boards/panels shall submit a copy oftype test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tightened to base with thermoplastic screws having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosure should be minimum 200mm for air circulation & to minimize temp rise. Panel should be fitted with one No.polycarbonate IP 65, 9 W LED translucent bulk head luminaire color lamp not less than 6500K, PF >0.95 under canopy for easy maintenance. Panel shall be fitted outside with one No of 16 Amp 3 Pole IP65 industrial socket and 01 No. of 32Amp 5P IP 65 industrial socket. 3 Phase and neutral 250 Amp current carrying capacity of aluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the following switch gears and mounting the panel board on ground with PCC (1:3:6) type C-1 using 20mm graded aggregate forbedding upto a height of 45 CM above ground level, including dismanting and taking out old U/s LT panel board and reconnecting existing LT UG Cable with new panel board amplete all as specified and all as directed and comprising of the following:- |
| 405 | (a) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 125 Amp, 36 KA- 01 No (Incomer).(b) On Load Change over front operated of capacity 160 Amp, 4 Pole, 415 V - 01 No.(c) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 63 Amp, 10 KA- 03 Nos. (d) MCB SPNof 240 V of capacity 40 Amps 10 KA- 02 Nos.(e) Multifunction Meter (V,I,PF) with suitable capacity of CT\"s- 01 No.(f) Indicating lamp (R-Y-B) set LED type with backup MCB for 3 Phase Supply - 01 set.(g) Space for spare feeder - 01 No. Note :-(i) The Contractor shall submit the drawing for approval of GE before executing the work.(ii) Insulators, bus bar sleeves, lugs, gland etc including complete wiring with suitable size of copper wire are all inclusive in unit quoted rate. (iii) Make of Switch gear : Schneider/L&T/C&S.(iv) MCCB should be ICu =100% ICs.(v) Make of LT Panel/FPB shall be as mentioned in list of makes (PS). |
| 406 | Supply, installation, commissioning and testing of factory assembled, floor mounted, free standing type tested LT Feeder pillar panel, with canopy, as per electrical specifications for outdoor installation to be made of IP65 Polycarbonate modular enclosures. The enclosures made of polycarbonate, should be weather/vermin proof, anti -acid, anti-corrossive, UV resistance in accordance with IEC 61439-1, fire retardant and self extingushing in accordance with IEC 60695-2-11, UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties, RoHS compliants & Halogen free. The manufacturer of boards/panels shall submit a copy oftype test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tightened to base with thermoplastic screws having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosure should be minimum 200mm for air circulation & to minimize temp rise. Panel should be fitted with one No.polycarbonate IP 65, 9 W LED translucent bulk head luminaire color lamp not less than 6500K, PF >0.95 under canopy for easy maintenance. Panel shall be fitted outside with one No of 16 Amp 3 Pole IP65 industrial socket and 01 No. of 32Amp 5P IP 65 industrial socket. 3 Phase and neutral 600 Amp current carrying capacity of aluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the following switch gears and mounting the panel board on ground with PCC (1:3:6) type C-1 using 20mm graded aggregate forbedding upto a height of 45 CM above ground level, including dismanting and taking out old U/s LT panel board and reconnecting existing LT UG Cable with new panel board amplete all as specified and all as directed and comprising of the following:- |
| 407 | (a) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 400 Amp, 36 KA- 01 No (Incomer).(b) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 250 Amp, 25 KA- 01 No.(c) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 160 Amp, 16 KA- 05 Nos. (d) Multifunction Meter (V,I,PF) with suitable capacity of CT\"s- 01 No.(e) Indicating lamp (R-Y-B) set LED type with backup MCB for 3 Phase Supply - 01 set.(f) Space for spare feeder - 01 No. Note :-(i) The Contractor shall submit the drawing for approval of GE before executing the work.(ii) Insulators, bus bar sleeves, lugs, gland etc including complete wiring with suitable size of copper wire are all inclusive in unit quoted rate. (iii) Make of Switch gear : Schneider/L&T/C&S.(iv) MCCB should be ICu =100% ICs.(v) Make of LT Panel/FPB shall be as mentioned in list of makes (PS). |
| 408 | Note :- An amount of Rs 2,16,724.00 on account of credit schedule for schedule \"A\" part II shall be deducted from the total amount of BOQ to arrive at the contract sum. |
AI Tender Summary
Tender Timeline
Sep 04, 2025
11:30 IST
Tender Published
Tender notice published.
CompletedOct 02, 2025
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
CompletedOct 09, 2025
Bid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓
Disclaimer