| 1 | SCHEDULE \"A\" PART-I: E/M WORKS |
| 2 | Material and labour in repairs for point wiring with 1.5 Sqmm PVC insulated and unsheathed copper cable 1100V, FRLS grade multistranded drawn in and including suitable size PVC conduit totally concealed/surface conduit in walls/ceiling with tee , bend, elbows, junction box etc. with provision of PVC insulated 1.5 sqmm copper conductor cable as earth continuity including not less than 1.0mm thick prefabricated galvanised boxes with white modular cover plate of suitable size for fixing modular switches, sockets regulator and connected the earth wire to common earth dollyforOne light/fan point/bell point/5 Amp indepentent board controlled by one switch complete incl taking down the exisitng all as specified and as directed. Note:-(i) Thequoted rate shall includes all the cost of cutting, chasing, cementing work to the disturbed and makingall the disturbed surfaces of wall / ceiling good to match the existing wall / ceiling along with same colour. |
| 3 | All as per item 1 above but for 5 Amps independant board complete all as specified and as directed |
| 4 | Material and labour in repairs for point wiring with 1.5 Sqmm PVC insulated and unsheathed copper cable 1100V, FRLS grade multistranded drawn in exisiting PVC conduit (any size)totally concealed/surface conduit in walls/ceiling with tee , bend, elbows, junction box etc. with provision of PVC insulated 1.5 sqmm copper conductor cable as earth continuity including not less than 1.0mm thick prefabricated galvanised boxes with white modular cover plate of suitable size for fixing modular switches, sockets regulator and connected the earth wire to common earth dollyforOne light/fan point/bell point/5 Amp indepentent board controlled by one switch complete all as specified and as directed.Note:-(i) Thequoted rate shall includes dragging the old wires and providing the new copper wiring through exisitng conduits and makingall the disturbed surfaces of wall / ceiling good to match the existing wall / ceiling along with same colour. |
| 5 | Description all as per item No. 3 above but for 05Amp switch socket out let,on independent board complete all as specified |
| 6 | S & F in repairs Modular switch 1 way 6A, 1 module single polecomplete all as specified and directed by Engr-in-charge. (Make ABB or eqv) |
| 7 | S & F in repairs Modular switch 1 way 16A, 1 module single polecomplete all as specified and directed by Engr-in-charge.(Make ABB or eqv) |
| 8 | S & F in repairs ceiling rose surface bake litewith 3 terminals complete all as specified and directed by Engr-in-charge. |
| 9 | S & F in repairs of modular Socket, 6A - 2/3 pin combined 2 module, 230 volt,multipurpose, complete all as specified.(Make ABB or eqv) |
| 10 | S & F in repairs ofmodular Socket 15A/16A - 2/3 pin combined 2 module,230 volt, multipurpose,complete all as specified.(Make ABB or eqv) |
| 11 | S & F in repairs of modular Fan step regulator, 100W - 1 modulecomplete all as specified. |
| 12 | S & F in repairs of modular Fan step regulator, 100W - 2 modulecomplete all as specified. |
| 13 | S& F for modularmodular white cover plate with frame 4 module complete all as specified and directed. |
| 14 | S& F for modularmodular white cover plate with frame upto 4 to 8 module complete all as specified and directed. |
| 15 | S& F for modularmodular metal/pvc flush box 4 module complete all as specified and directed |
| 16 | S& F for modularmodular metal/pvc flush box upto 4 to 8 module complete all as specified and directed |
| 17 | Supply and fix switch piano flush type,5 Amps 240 volts single pole one way. |
| 18 | S/Fin repairs socketonly 5 amps flush type. |
| 19 | S/Fin repairs socketonly 15 amps flush type. |
| 20 | S/F in repairs switch socket combination 2 in 1, 5 amps flush type. |
| 21 | S/F in repairs switch socket combination 15/16 amps, 5 in 1, flush type. |
| 22 | S/F in repairsswitch socket combination 2 in 1, 5 amps box type. |
| 23 | S/F in repairs switch socket combination 15/16 amps, 5 in 1, box type. |
| 24 | S&F in repairsfan regulator electronic type, rotary step type , 240 Volt. |
| 25 | S&F in repair Bell push flush type, 5 Amps complete all as specified and directed |
| 26 | S&F in repair buzzer Ding dong, AC 230 volts single pole |
| 27 | S & F in repairsLight Batten Frame wall mountedwith all accessories suitable for mounting 18W LED including taking down old fittings complete all as specified and as directed by the Engineer-in-Charge. |
| 28 | S & F in repairsTube Light Batten Frame wall mountedwith all accessories suitable for mounting 9/10W LED including taking down old fittings complete all as specified and as directed by the Engineer-in-Charge. |
| 29 | Supply and fixing in repairspost top lantern LED type 25/36 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete all as specified and directed |
| 30 | S & F in repairs Square surface mounted LED light (2\"x2\") of minimum (36 Watt) warm/cool day light with all accessories internally prewired and including connecting up with twin core twisted copper conductor cable of suitable size complete all as specified and as directed by the Engineer-in-Charge. |
| 31 | S & F in repairsHigh bay LED flood light fittings of 100 Watts cap with pressure die cast aluminium housing IP-65 protection heat resistance toughen glass cover, electronic driver all accessories internally prewired connecting with flexible copper conductor of size 1.5sqmm including taking down existing light fittings of any description all as specified and directed. |
| 32 | S & F in repairs Building Security light LED type of minimum 35Watts Pressure die cast aluminium housing IP 66 protection with all accessories internally prewired and including connecting up with twin core twisted copper conductor cable of suitable size including bracket made of 40mm dia GI light grade pipe of 1.2m long bent to shape fixed with suitable MS clamps, bolts, nuts and washers duly painted including taking down old fittings complete all as specified and as directed by the Engineer-in-Charge. |
| 33 | S & F in repair Aviation obstruction light LED type filament-less bulb complete including standard fixing arrangements including timer switch complete all as specified and as directed. |
| 34 | S & F in repairsLight Batten Frame wall mountedwith all accessories suitable for mounting 20Watts LED including taking down old fittings complete all as specified and as directed by the Engineer-in-Charge. |
| 35 | S & F in repairs LED bulb 7/9 watts with holder pin/thread typecomplete all as specified and as directed by the Engineer-in-Charge. |
| 36 | S & F MCCB Enclosure Box suitable for 63 to 250 Amps outdoor type, IP 65 rating including all accessories for connecting MCCB and Cables complete all as specified by Engr-in-Charge. |
| 37 | S & F in repairs MCCB 4 Pole, 63 Amps, 50 Hz, 16KA, 415 Volts with all necessary aluminium lugs and glands, etc complete all as directed |
| 38 | S & F in repairs MCCB 4 Pole, 100 Amps, 50 Hz, 16KA, 415 Volts with all necessary aluminium lugs and glands, etc complete all as directed |
| 39 | S & F in repairs MCCB 4 Pole, 125 Amps, 50 Hz, 25KA, 415 Volts,adjustable thermal and fixed magnetic type with all necessary aluminium lugs and glands, etc complete all as directed |
| 40 | S & F in repairs MCCB 4 Pole, 160 Amps, 50 Hz, 25KA, 415 Volts, adjustable thermal and fixed magnetic typewith all necessary aluminium lugs and glands, etc complete all as directed |
| 41 | S & F in repairs MCCB 4 Pole, 200/250 Amps, 50 Hz, 36KA, 415 Volts, adjustable thermal and fixed magnetic typewith all necessary aluminium lugs and glands, etc complete all as directed |
| 42 | S & F in repairs MCCB 4 Pole, 400 Amps, 50 Hz, 36KA, 415 Volts, adjustable thermal and fixed magnetic typewith all necessary aluminium lugs and glands, etc complete all as directed |
| 43 | Supply and fixing in replacement of Factory made sheet metal enclosure for VTPN MCCB DBs double door (Fixed flush to the wall), with provision of MCCB as incommer & outgoing as TPN 415 volt,8 Way, with suitable rated bus bar suitable for having MCB’s , complete all as specified (Note : MCCB/MCBs will be measured and paid separately under relavent items ) |
| 44 | Supply and fixing in replacement of Factory made sheet metal enclosure for VTPN MCCB DBs double door (Fixed flush to the wall), with provision of MCCB as incommer & outgoing as TPN 415 volt,4 Way, Isuitable rated bus bar and suitable for having MCB’s , complete all as specified. (Note : MCCB/MCBs will be measured and paid separately under relavent items ) |
| 45 | Supply and fixingin replacementof Factory made sheet metal enclosure for DBs double door (Fixed flush to the wall), TPN, 415 volt,4 Way, suitable rated bus bar and suitable for having MCB’s , complete all as specified. (Note : MCBs will be measured and paid separately under relavent items ) |
| 46 | Supply and fixing in repair of Factory made sheet metal enclosure for DBs (Fixed flush to the wall), SPN, 240 volt,8 Way, suitable rated bus barand suitable for having MCB’s , complete all as specified. (Note : MCBs will be measured and paid separately under relavent items ) |
| 47 | Supply and fixing in repair of Factory made sheet metal enclosure for DBs (Fixed flush to the wall), SPN, 240 volt,4 Way, suitable rated bus barand suitable for having MCB’s , complete all as specified. (Note : MCBs will be measured and paid separately under relavent items ) |
| 48 | Supply and fixingof MCB 6 to 32Amp, 240 Volt, SP, breaking capacity 10 KA \"C\" series,complete all as specified |
| 49 | Supply and fixing ofMCB 40-100 Amp, 415 Volt, TPN, breaking capacity 10 KA \"C\" series, , complete all as specified |
| 50 | Supply and fixingof MCB 6 to 32Amp, 240 Volt, SPN, breaking capacity 10 KA \"C\" series, , complete all as specified |
| 51 | Supply and fixingof MCB 63 Amp, 415 Volt, TP, breaking capacity 10 KA \"C\" series, , complete all as specified |
| 52 | M&L for sub main wiring withfour run of 10.0 Sq. mm PVC un-sheathed, copper conductor cable, 1100 Volt,and onerun of copper earth wire 10.0 Sq mm drawn through PVC concealed/surfaceconduict of 40 mm dia, including taking down unsv sub main wiring of any type, complete all as specified.Note: Copper conductor 05 run along with PVC concealed conduictshall be measured as one length & Cutting of chases/walls and making good the disturbed surface are included in the rate. |
| 53 | M&L for sub main wiring withtwo run of 10.0 Sq. mm PVC un-sheathed, copper conductor cable, 1100 Volt,and onerun of copper earth wire 10.0 Sq mm drawn through PVC concealed/surfaceconduict of 40 mm dia, including taking down unsv sub main wiring of any type, complete all as specified.Note: Copper conductor 03 run along with PVC concealed conduictshall be measured as one length & Cutting of chases/walls and making good the disturbed surface are included in the rate. |
| 54 | M&L for sub main wiring withtwo run of 6.0 Sq. mm PVC un-sheathed, copper conductor cable, 1100 Volt,and onerun of copper earth wire 6.0Sq mm drawn through PVC concealed/surface conduict of 25 mm dia, including taking down unsv sub main wiring of any type, complete all as specified. Note: Copper conductor 2 run and one run of copper earth wire along with PVC concealed conduictshall be measured as one length & Cutting of chases/walls and making good the disturbed surface are included in the rate. |
| 55 | M&L for sub main wiring withtwo run of 4.0 Sq. mm PVC un-sheathed, copper conductor cable, 1100 Volt,and onerun of copper earth wire 4.0 Sq mm drawn through PVC concealed/surface conduict of 25 mm dia, including taking down unsv sub main wiring of any type, complete all as specified. Note: Copper conductor 2 run and one run of copper earth wire along with PVC concealed conduictshall be measured as one length & Cutting of chases/walls and making good the disturbed surface are included in the rate. |
| 56 | M&L for sub main wiring withtwo run of 2.5 Sq. mm PVC un-sheathed, copper conductor cable, 1100 Volt,and onerun of copper earth wire 2.5 Sq mm drawn through PVC concealed/surface conduict of 25 mm dia, including taking down unsv sub main wiring of any type, complete all as specified. Note: Copper conductor 2 run and one run of copper earth wire along with PVC concealed conduictshall be measured as one length & Cutting of chases/walls and making good the disturbed surface are included in the rate. |
| 57 | Supply lay and testing of cable in trenches/walls/floor XLPE insulated, armoured electric cable (heavy duty 1100volt grade with stranded aluminium conductor of size 10sqmm 4.0 core complete all as specified and directed by Engr-in-charge. |
| 58 | Excavation in trenches not exc.1.5m wide and not exceeding 1.5m in depth and getting out in hard/dense soil for laying of cable complete all as specified. |
| 59 | Returning, filling in, including spreading, levelling, watering and well ramming in layer not exceeding 25 cm thick complete all as specified |
| 60 | Removing excavated surplus soils meterial not exc.50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified. |
| 61 | Material and labour fornatural river sand as cushioning of cables, including spreading and punning down complete all as specifiedand directed by Engineer in charge. Note : punned thickness shall be measured for payment purpose |
| 62 | Supply and laying in trenches Bricks common burnt clay building bricks, sub-class ‘B’ designation 75 laid perpendiculat to the trench for cable protection complete all as specified and as directed |
| 63 | Material and labour for50 mm dia GI steeltubes \"light grade\"for cable protection including sealing both ends complete all as specified and as directed by Engineer-in-charge. |
| 64 | Material and labour forcutting existing road/PCC/drain for laying of underground cable and including necessary earth work and making good to match with the exisitng surface with PCC1:3:6 type CI using 20mm graded aggregates complete all as specified and as directed. |
| 65 | S & F in repairs moduler sheet metal enclosure with single pole and neutral enclosure with a two pin and earth plug and socket complete with one MCB, SP, 20 Amps, 240 volts, 10 KA complete suitable for AC all as specified and directed. |
| 66 | Supply and laying of synthetic insulation rubber mat of size 1MX2MX2mm thickness of voltage upto 3.3KV power supply, insulation category of class A for indoor LT panel for electric shock safety complete all as specified |
| 67 | Labour only for cleaning , tightening nuts &screw and all associatedworks for DB & LT panel complete |
| 68 | Labour only for refixing disoriented pvc surface wiring , light fitting and all associatedworkscomplete. Note: Dilapidated conduit / casing cappingshall be measured and paid seperately of this schedule |
| 69 | Supply only pvc conduit upto 25 mm. |
| 70 | Supply only pvc casing capping 25 mm. |
| 71 | Supply and replacement of LED driver suitable for LED Light fittings of upto 36-75 watt LEDlight of any type complete all as specified |
| 72 | Taking down existing electric geysers of any type and capacity for inspection and checking serviceability in-situ or at workshop ,washing the inner tank with anti corrosion solution, the inlet & outlet valves, safety valve, dead weight and refixing the geysers in position and testing for proper functioning including soldering/welding where required to stop the leakage and other jobs connected with plumber and mason , reassembling the geyser set and refixing the same in original position including checking for proper function complete all as directed by Engr-in-Charge. [Note: a) The cost of transportation is included in quoted rateb)Spare parts shall be measured and paid seperatrly as supply only item of this schedule] |
| 73 | Supply only pressure release valve 15mm dia suitabel for existing geysercomplete. |
| 74 | Supply only geyser element 1.5 KW / 2.0 KW capacity complete all as specified and directed by Engr-in-Charge. |
| 75 | S & F in repairs gun metal check valve / non return valve 15 mm dia suitable for Geyser of any make/capacity complete. All as specified and directed by Enge in charge. |
| 76 | S & F in repairs Thermostat of necessary capacity (1.5/2 KW) complete all as specified and directed by Engr-in-Charge. |
| 77 | Supply only inner tank of geyser capacity 25 ltr made out of copper suitable for existing Geyser of any type and make to match the existing size and shape of inner tank of Geyser installed at site. All as specified and directed by Enge in charge. |
| 78 | Supply onlymetal clad plug top 20A (enclosure type)suitable to fix in sheet and metal enclouser for geyser. All as specified and directed by Enge in charge. |
| 79 | Supply only hot / coldwater stainless steel pipe connection of15mm bore heavy duty, length upto 45cm with brass nut joints and washers at both ends complete. All as specified and directed by Enge in charge. |
| 80 | S&F wall mounted type Bus Bar Terminal Box, 3 Phase and Neutral [TPN], 415 Volts,cap 250-650 Amps Capacity with cable glandand of specification as specified below [a] Conductor Material - Aluminium[b] Bus Duct Construction - Sandwich Type [c] Bus Duct Rating - upto 400 Amps [d] Rated Operation Voltage [UE] - 415 / 690 Volts and maximum up to 1000 Volts. [e] Rated Insulation Voltage [UE] - 1100 Volts [f] Degree of Protection - IP54 / IP 55 for Indoor complete all a s specified and as directed |
| 81 | Supply and fixing in repairs to S-Line sandwich construction bus bar trunking system with Al bus bars 400 amps 50 KA breaking capacity with multilayer class \"F\" insulation, 415 V , three phase 4 wire with 100% Neutral without internal earth, apoxy painted 1.5mm GI housing, uniblock joints between sections, fixed to walls/ coloumns/ roofs etc with necessasry clamps , breackets , adjustbale handing rods etc complte all as specifeid and as directed (make : C&S, L&T, Legrand, ABB) |
| 82 | M&L in repairs to Plug-in Box for tapping of 3 Phase supply in each floor and equipped with MCCB, 63 Amps, TPN, 25 KA with front rotatory handle configuration 3P4W with 100% Neutralsuitable to match the exisiting slots of S-Line Sandwich costruction Bus Bar trunking system with multilayer Class -F insulation , 415 Volts complete all as specified and as directed. |
| 83 | M & L for Painting of complete LT Panels type metering console with distr system of any size and makewith existing colour with 2 coats of synthetic enamel spray painting after cleaning of surface by scrubbing all dust particles/ grease/ oil etcand writing with Red colour GE (ND) (V)complete all as specified and as directed. |
| 84 | Supply and replacement of LED driver suitable for LED Light fittings of upto 75-100 watt LEDlight of any type complete all as specified |
| 85 | Supply and replacement of LED driver suitable for LED Light fittings of upto 100-150 watt LEDlight of any type complete all as specified |
| 86 | M&L for 25x4mm galvanised iron strip for earthing connection to building, complete all as specified. |
| 87 | Dismantling earthpit chamber manually without disturbing the earth continutiy strp/wire, funnel, water pipe carefully and placing with new PCC earth pit chamber made of PCC 1:3:6 type C1 chamber (450mm 450mmx 300mm depth)& ,CI frame with CI 10mm thick cover alongwith new wire mesh water funnel complete all as specified and as directed |
| 88 | M&L for 4mm galvanised iron earth wirefor earthing connection to building, complete all as specified. |
| 89 | M&L Earthing complete with GI plate electrode 600x600x6mm thick, buried directly and preferably vertically in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected with GI earth strip of 25X4 mmby means of bolts, nuts, check nuts and washers of GI or steel all as shown in electrical plate No 3, connected to earthing with DBs all as specified including earth work and excavation in any type of soil, PCC 1:3:6 type C1 chamber,CI frame with CI 10mm thick cover,20mm dia GI medium grade pipe for watering , and water funnel with wirw mesh, 40mm dia light grade GI pipe for protection of strip complete all as specified and testing on completion. |
| 90 | M&L Earthing complete with GI plate electrode 600x600x6mm thick, buried directly and preferably vertically in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected with GI earth wire of 4 mm dia by means of bolts, nuts, check nuts and washers of GI or steel all as shown in electrical plate No 3, connected to earthing with DBs all as specified including earth work and excavation in any type of soil, PCC 1:3:6 type C1 chamber,CI frame with CI 10mm thick cover,20mm dia GI medium grade pipe for watering , and water funnel with wirw mesh, 20mm dia light grade GI pipe for protection of strip complete all as specified and testing on completion. |
| 91 | Note (a)The rate quoted by the tenderer for item Ser No.01 to 89 above shall deemed to be inclusive for the following provisions in addition to the other conditions specified in the tender documents. No claim whatsoever shall be entertained at a later date on this account:- (i) Though the time period for completion of contract will be as specified in CA/work order, yet due to exigency of electrical related items emergency/priority works must be completed (within 24 Hours) on getting information through SMS/E-mail regarding the nature of repair to be carried out he shall immediately respond the same and make all out efforts to carry out the same on priority within 24 hours. In case of any delay in responding/ attending the repairs within 48 hours, the GE may at his absolute discretion impose penalty on the contractor at Rs 100/- per day per each work upto 05 (Five) days and Rs 200/- per day there after till completion of the work. Incase of delay without valid reasons as decided by GE. |
| 92 | (ii) Further, the above penalty is applicable even for the multiple works at multiple locations of work at the same period. It is responsiblity of contractor to make suitable arrangement for attending the repairs simultaneously at all the places.(iii) The decision of the GE as to weather of particular repair has been attended or not on a particular day will be final and binding. The above penality shall be in addition to the provisions made in clause 50 of IAFW-2249 i.e. (Compensation for delay in completion of work).Note (b) :- Tenderers/ Bidders are advised to visit the site and quote the rate accordingly. |